SiE-05C
Functions
Functions Inverter K Series
27
1.3
List of Safety Devices and Functinal Parts Setting Values
1.3.1
Outdoor Unit
RSXY5~10K
Note
1. These parts are for heat pump model only.
2.
∗
: For products produced after Aug. ‘99.
Item
Symbol
Name
Type
RSX(Y)5K
RSX(Y)8K
RSX(Y)10K
Comp-
ressor
Inverter
side Model
Output
Y1
INV
JT100BAVYE
3.5 kW
JT100BAVTYE
3.5 kW
JT100BAVTYE
3.5 kW
STD
JT100BATYE
2.2 kW
JT160BATYE
3.75kW
YAL
INV
JT100BAVYE
3.5 kW
JT100BAVTYE
3.5 kW
JT100BAVTYE
3.5 kW
STD
JT100BATYH
2.2 kW
JT160BATYH
3.75kW
TAL
INV
JT100BAV
3.5 kW
JT100BAVT
3.5 kW
JT100BAVT
3.5 kW
STD
JT100BAT
2.2 kW
JT160BAT
3.75kW
Compressor safety
thermostat
Discharge pipe thermistor 135˚C OFF
J1HC/
J2HC
Crank case heater
33W
33W+33W
F2C
Over-current
relay
Y1
—
HOE-20F-TRA1
10A
HOE-20F-TRA1
13A
YAL
—
HOE-20F-TRA1
10A
HOE-20F-TRA1
13A
TAL
—
HOE-20-TRA1
15A
HOE-26-TRA1
24A
Safety
device
Q1M
Q2M
Fan motor
190W
140W+230W
Safety thermostat
Open 135˚C ± 5˚C
140W: Open 120 ± 5˚C, 230W: 135 ± 5˚C
S1P
Pressure switch (for high
pressure safety)
20SP-688-6
OFF: 27.5+0~-1.0kg/cm
²
ON: 20.0+1.0~-1.0kg/cm
²
—
S1HP
Pressure switch (for high
pressure safety)
—
20SP-688-6 OFF: 27.5+0~-1.0kg/cm
2
ON: 20.0+1.0~-1.0kg/cm
²
S2HP
Pressure switch (for high
pressure safety)
—
20SP-688-6 OFF: 27.5+0~-1.0kg/cm
2
ON: 20.0+1.0~-1.0kg/cm
²
Fusible plug
FPG-3D 70~75˚C
Sensor
SENPH Pressure sensor
PS8030A 0~30kg/cm
²
(0~2.94MPa)
SENPL
Pressure sensor
PS8030A 0~10kg/cm
²
(0~0.98MPa)
R1T
Thermistor (for outdoor air) 3.5~360K
Ω
R2T
Thermistor
(for heat exchange)
3.5~360K
Ω
R3T
Thermistor
(for discharge pipe)
3.5~400K
Ω
—
R3-1T
Thermistor (for inverter
discharge pipe)
—
3.5~400K
Ω
R3-2T
Thermistor (for standard
discharge pipe)
—
3.5~400K
Ω
R4T
Thermistor
(for suction pipe)
3.5~360K
Ω
R5T
Thermistor
for inverter oil temperature)
—
3.5~400K
Ω
(
∗
3.5~360K
Ω
)
Other
functions
/parts
Y1E
Note 1
Electronic
expansion valve
When
cooling
ON: 2,000 pulses (completely open); OFF: 0 pulses (completely closed)
When
heating
ON: PI control; OFF: 0 pulses (completely closed)
Y2S
Solenoid valve
(for hot gas bypass)
NEV603
Y3S
Solenoid valve
(for inverter injection)
NEV202 (
∗
ST10D)
Y4S
Solenoid valve
(for standard injection)
—
NEV202 (
∗
ST10D)
Y1S
Note 1
Solenoid valve
(pressure equalizing)
—
NEV202 (
∗
ST10D)
SI-05C.BOOK Page 27 Monday, November 6, 2000 4:13 PM