Functions
SiE-05C
38
Functions Inverter K Series
Low Outdoor Air
Cooling IN
Conditions (Step 2)
<For products produced after Aug. ’99>
Normal operation
Step 2
•
Cooling with compressor running
(doesn't include oil return)
&
•
High pressure < 7.5 kg/cm²
(0.735 MPa)
&
•
Outdoor air temperature < 20˚C
&
•
Radiator fin temperature < 60˚C
•
Compressor off
or
•
Other than cooling (includes oil return)
or
•
High pressure > 15.8 kg/cm²
(1.548 MPa)
or
•
Outdoor air temperature > 25˚C
or
•
Radiator fin temperature > 80˚C
Condition satisfied
Conditions satisfied
(VF007-1)
Normal operation
Step 2
•
Cooling with compressor running
(doesn't include oil return)
&
•
High pressure < 7.5 kg/cm²
(0.735 MPa)
&
•
Radiator fin temperature < 60˚C
•
Compressor off
or
•
Other than cooling (includes oil return)
or
•
High pressure > 15.8 kg/cm²
(1.548 MPa)
or
•
Radiator fin temperature > 80˚C
Condition satisfied
Conditions satisfied
(VF007-2)