SiE-05C
Outline of Control
Functions PLUS Series
247
4.18.2 Emergency Operation 2
Setting forced backup operation by setting mode 2 enables emergency operation with INV outdoor unit and
other STD outdoor unit if STD outdoor unit malfunction.
Operation of faulty STD outdoor unit
In case of cooling only system
Other outdoor units operate by normal operation.
Difference with Backup Operation
Backup operation is conducted for a maximum of 3 hours, but there is no time limit with this mode.
Compressor
Outdoor unit fan
Outdoor unit EEV
Hot gas bypass
Faulty STD outdoor
unit
OFF
H + ON
0 PLS
ON
Compressor
Outdoor unit fan
Function unit’s solenoid valveY5, Y6, Y7
Faulty STD outdoor
unit
OFF
H + ON
ON
SI-05C.BOOK Page 247 Monday, November 6, 2000 4:13 PM