SiE-05C
Pump Down Operation when Replacing The Compressor
Special Service Mode PLUS Series
337
2.1.2
Setting Mode 2 Pump Down Procedure
SET
Normal mode
Setting item
Setting contents
LED display
20 21 22 23 24 25 26
No
EMG
Emergency operation when
inverter type outdoor unit
malfunctions
1
Pump down
operation 1
Pump down operation
for inverter type
11
Pump down
operation 2
Pump down operation for constant
speed type outdoor unit 1
12
Pump down
operation 3
Pump down operation for constant
speed type outdoor unit 2
13
Pump down
operation
Normal
operation
Setting mode 2
Pump down operation
Mode
display
Low pressure
display
Mode
display
Low pressure
display
Mode
display
Low pressure
display
Mode
display
Low pressure
display
(Normal complete)
Compressor operation
Push and hold the Mode
button (BS1) for 5 seconds.
or 60 minutes elapse or stop due to malfunction
(Stop due to malfunction)
(VF167)
(k: kg/cm
2
)
(When malfunctioning)
Mode
display
Low pressure
display
The indoor unit will not accept
remote controller operation
when "under centralized
control" is displayed.
· Low pressure display
: Low pressure > 3.5k
: Low pressure < 3.5k
: Low pressure < 2.5k
: Low pressure < 1.5k
Push 14 times.
MODE button (BS1)
SET
SET button (BS2)
R
RETURN button (BS3)
MODE
MODE
MODE
SET
SET
SET
SET
R
R
R
R
R
SI-05C.BOOK Page 337 Monday, November 6, 2000 4:13 PM