6. REFRIGERANT PIPING WORK

• For instruction for installing piping between the outdoor unit and BS unit, selecting a refrigerant branch kit, 

and installing piping between the refrigerant branch kit and the indoor unit, refer to the installation manual 
and equipment design materials included with the outdoor unit.

• Before beginning the work, always check to make sure the type of refrigerant used is R410A. (The unit will 

not operate correctly with a different type of refrigerant.)

• Insulate all of the piping including the liquid pipes, HP/LP gas pipes, suction gas pipes, gas pipes, equalizer 

pipes (piping between outdoor units when an outdoor multi-unit system), and the pipe connections for 
these. Not insulting these pipes could result in water leaks or burns. In particular, suction gas flows in the 
HP/LP gas piping during full cooling operation, so the same amount of insulation as used for the suction 
gas piping is required. In addition, high-pressure gas flows in the HP/LP gas piping and gas piping, so use 
insulation that can withstand more than 120˚C.

• Reinforce the insulation material when necessary for the installation environment. Refer to the following as 

a guideline.

• For 30˚C, RH75% to 80%: Thickness at least 15mm
• For 30˚C, over RH80%: Thickness at least 20mm

If not reinforced, condensation could form on the surface of the insulation. For details, refer to the Engi-
neering data book.

NOTES

• This product only uses the new refrigerant (R410A). Be sure to use the special pipe cutters for R410A, dur-

ing installation.

• Make sure that nothing besides the specified refrigerant, such as air, gets into the refrigerant piping.
• If refrigerant gas leaks during the work, ventilate the area. (The outdoor units are filled with refrigerant.)

6-1 PIPING MATERIAL SELECTION

• Use only pipes which are clean inside and outside and which do not accumulate harmful sulfur, oxidants, 

dirt, cutting oils, moisture, or other contamination. (Foreign materials inside pipes including oils for fabrica-
tion must be 30mg/10m or less.)

• Use the following items for the refrigerant piping.

Material: Jointless phosphor-deoxidized copper pipe
Size: See “Example of connection” to determine the correct size.
Thickness: Select a thickness for the refrigerant piping which complies with national and local laws.
For R410A, the design pressure is 4.0 MPa (40bar).
The minimum thickness of piping according to Japan’s High-Pressure Gas Safety Law (as of January 
2003) is shown below.
Temper grade (O type, 1/2H type) in the table indicate the material types specified in JIS H 3300.

(unit: mm)

(unit: mm)

• For information regarding the piping allowable maximum length, allowable height difference, and allowable 

length after a branch, refer to the installation manual that came with the outdoor unit or Engineering data 
book.

• The refrigerant branch kit (sold separately) is required for piping branches. For information on how to select 

a refrigerant branch kit, refer to the Installation Manual that came with the outdoor unit or Engineering data 
book.

Temper grade

O type

outer diameter

φ

6.4

φ

9.5

φ

12.7

φ

15.9

smallest thickness

0.80

0.80

0.80

0.99

Temper grade

1/2H type

outer diameter

φ

19.1

φ

22.2

φ

25.4

φ

28.6

φ

31.8

φ

34.9

φ

38.1

φ

41.3

smallest thickness

0.80

0.80

0.88

0.99

1.10

1.21

1.32

1.43

Summary of Contents for VRV III BSVQ100P8V1B

Page 1: ...READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE INSTALLATION MANUAL BS unit BSVQ100P8V1B BSVQ160P8V1B BSVQ250P8V1B System air conditioner...

Page 2: ...enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma preve...

Page 3: ...life CAUTION Failure to observe these instructions properly may result in property damage or per sonal injury which may be serious depending on the circumstances WARNING Ask your dealer or qualified p...

Page 4: ...r Do not directly touch refrigerant that has leaked from refrigerant pipes or other areas as there is a danger of frostbite CAUTION Install the BS units power cord and connecting wires at least 1 mete...

Page 5: ...igned for R410A See the catalogue for indoor outdoor unit models that can be connected Normal operation is not possible when connecting units that are originally designed for other refrigerants 2 2 PR...

Page 6: ...icient clearance for maintenance and service can be ensured Refer to Fig 1 Locations where an inspection hole Refer to Fig 2 can be installed to EL COMPO BOX side See Note Where the total piping lengt...

Page 7: ...r the like Install the BS unit so that its weight can be withstood Hanging bracket For supporting the connection pipe Be sure to support the connection piping around the unit using hanging brackets th...

Page 8: ...0 3 pcs 4 locations and washers For M8 Outside diameter dimension 24 to 28mm For M10 Outside diameter 30 to 34mm 2 pcs 4 locations field supply from both the top and bottom sides of the hanging bracke...

Page 9: ...nstallation Make sure that nothing besides the specified refrigerant such as air gets into the refrigerant piping If refrigerant gas leaks during the work ventilate the area The outdoor units are fill...

Page 10: ...the refrigerant pipe joints Using a chlorine flux may cause the pipes to corrode and if it contains fluoride it may cause the refrigerant lubricant to deteriorate adversely affecting the refrigerant...

Page 11: ...door units Piping size outer diameter x minimum thickness Gas pipe Liquid pipe 20 25 32 40 50 12 7x0 80 6 4x0 80 63 80 100 125 15 9x0 99 9 5x0 80 200 19 1x0 80 250 22 2x0 80 mm BS unit Piping size out...

Page 12: ...uid pipe Site piping Gas pipe Site piping Liquid pipe Site piping BS unit Top Accessory pipes 1 2 Accessory pipes 1 1 Gas pipe Site piping Liquid pipe Site piping BS unit Top Suction gas pipe Site pip...

Page 13: ...ation field supply with the seams facing up See figure at right BSVQ100 160P type BSVQ250P type BS unit BS unit Clamp 2 2 Accessory Clamp 2 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3...

Page 14: ...tion Do not turn on the power supply branch switches overload interrupters until all other work is done 7 2 EXAMPLE FOR THE WHOLE SYSTEM 7 3 POWER CIRCUIT SAFETY DEVICE AND CABLE REQUIREMENTS A power...

Page 15: ...the EL COMPO BOX lid and connect the wires to F1 and F2 TO IN D UNIT and F1 and F2 TO OUT D UNIT transmission wiring terminals control PCB A1P At this time pass the wiring into the unit through the w...

Page 16: ...the wire through hole to protect the wires Do not pass the transmission wiring and power supply wiring through the same locations and outside of the unit keep them separated by at least 50mm Not doing...

Page 17: ...er to the Engineering data book Setting method The setting is made using the Local Setting Mode by the remote controller of indoor unit connected to the BS unit For information regarding the setting m...

Page 18: ...MPO BOX NOTES PRINTED CIRCUIT BOARD DIP SWITCH FUSE T 3 15A 250V FLASHING LAMP SERVICE MONITOR GREEN SWITCHING POWER SUPPLY A1P TERMINAL STRIP POWER TERMINAL STRIP CONTROL TERMINAL STRIP C H SELECTOR...

Page 19: ...NOTES NOTES...

Page 20: ...4PW46241 1 Copyright Daikin...

Reviews: