7. ELECTRIC WIRING WORK

7-1 GENERAL INSTRUCTIONS

• All wiring must be performed by an authorized electrician.
• All field supplied parts and materials, electric works must conform to local codes.
• Always ground wires. (In accordance with national regulations of the pertinent country.)
• Always turn off the power before performing the electric wire installation work.
• Follow the “WIRING DIAGRAM” attached to the unit body to wire the outdoor unit and indoor units.
• Properly connect wire of the specified wire type and copper thickness. Also use the included clamp to avoid 

applying excessive force to the terminal (field wire, ground wire).

• Do no let the ground wire should come in contact with gas pipes, water pipes, lighting rods, or telephone 

ground wires.

• Gas pipes: gas leaks can cause explosions and fire.
• Water pipes: cannot be grounded if hard vinyl pipes are used.
• Telephone ground and lightning rods: the ground potential when struck by lightning gets extremely high.

• A circuit breaker capable of shutting down the power supply to the entire system must be installed.
• This system consists of multiple BS units. Mark each BS unit as unit A, unit B . . . , and be sure the terminal 

board wiring to the outdoor unit and indoor unit are properly matched. If wiring and piping between the out-
door unit, BS unit and an indoor unit are mismatched, the system may cause a malfunction.

• Do not turn on the power supply (branch switches, overload interrupters) until all other work is done.

7-2 EXAMPLE FOR THE WHOLE SYSTEM

7-3 POWER CIRCUIT, SAFETY DEVICE AND CABLE REQUIREMENTS

• A power circuit (Refer to Table 3) must be provided for connection of the unit. This circuit must be protected with the 

required safety devices, i.e. a main switch, a slow blow fuse on each phase and an earth leakage circuit breaker.

• A main switch or other means for disconnection, having a contact separation in all poles, must be incorporated in 

the fixed wiring in accordance with relevant local and national legislation.

• When using residual current operated circuit breakers, be sure to use a high-speed type (0.1 second or 

less) 30mA rated residual operating current.

• Use copper conductors only.
• Use insulated wire for the power cord.
• Select the power supply cable type and size in accordance with relevant local and national regulations.
• Specifications for local wiring are in compliance with IEC60245.
• Use wire type H05VV-U3G for power supply wiring. And the size must comply with local codes.
• Use vinyl cord with sheath or cable (2 wire) of 0.75-1.25mm

2

 for transmission wiring.

Table 3 

MCA: Min. Circuit Amps (A); 

MFA: Max. Fuse Amps (A)

Units

Power supply

Model

Type

Hz

Voltage

Min.

Max.

MCA

MFA

BSVQ100P
BSVQ160P
BSVQ250P

V1

50

220

198

264

0.1

15

230
240

Power supply wiring

Transmission wiring

Switch

Fuse

Outdoor unit

Power supply

Power supply

Main switch

Main switch

BS unit

Indoor unit

Remote controller

Cooling/Heating selectable indoor unit

Cooling-dedicated 
indoor unit

Summary of Contents for VRV III BSVQ100P8V1B

Page 1: ...READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE INSTALLATION MANUAL BS unit BSVQ100P8V1B BSVQ160P8V1B BSVQ250P8V1B System air conditioner...

Page 2: ...enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma preve...

Page 3: ...life CAUTION Failure to observe these instructions properly may result in property damage or per sonal injury which may be serious depending on the circumstances WARNING Ask your dealer or qualified p...

Page 4: ...r Do not directly touch refrigerant that has leaked from refrigerant pipes or other areas as there is a danger of frostbite CAUTION Install the BS units power cord and connecting wires at least 1 mete...

Page 5: ...igned for R410A See the catalogue for indoor outdoor unit models that can be connected Normal operation is not possible when connecting units that are originally designed for other refrigerants 2 2 PR...

Page 6: ...icient clearance for maintenance and service can be ensured Refer to Fig 1 Locations where an inspection hole Refer to Fig 2 can be installed to EL COMPO BOX side See Note Where the total piping lengt...

Page 7: ...r the like Install the BS unit so that its weight can be withstood Hanging bracket For supporting the connection pipe Be sure to support the connection piping around the unit using hanging brackets th...

Page 8: ...0 3 pcs 4 locations and washers For M8 Outside diameter dimension 24 to 28mm For M10 Outside diameter 30 to 34mm 2 pcs 4 locations field supply from both the top and bottom sides of the hanging bracke...

Page 9: ...nstallation Make sure that nothing besides the specified refrigerant such as air gets into the refrigerant piping If refrigerant gas leaks during the work ventilate the area The outdoor units are fill...

Page 10: ...the refrigerant pipe joints Using a chlorine flux may cause the pipes to corrode and if it contains fluoride it may cause the refrigerant lubricant to deteriorate adversely affecting the refrigerant...

Page 11: ...door units Piping size outer diameter x minimum thickness Gas pipe Liquid pipe 20 25 32 40 50 12 7x0 80 6 4x0 80 63 80 100 125 15 9x0 99 9 5x0 80 200 19 1x0 80 250 22 2x0 80 mm BS unit Piping size out...

Page 12: ...uid pipe Site piping Gas pipe Site piping Liquid pipe Site piping BS unit Top Accessory pipes 1 2 Accessory pipes 1 1 Gas pipe Site piping Liquid pipe Site piping BS unit Top Suction gas pipe Site pip...

Page 13: ...ation field supply with the seams facing up See figure at right BSVQ100 160P type BSVQ250P type BS unit BS unit Clamp 2 2 Accessory Clamp 2 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3...

Page 14: ...tion Do not turn on the power supply branch switches overload interrupters until all other work is done 7 2 EXAMPLE FOR THE WHOLE SYSTEM 7 3 POWER CIRCUIT SAFETY DEVICE AND CABLE REQUIREMENTS A power...

Page 15: ...the EL COMPO BOX lid and connect the wires to F1 and F2 TO IN D UNIT and F1 and F2 TO OUT D UNIT transmission wiring terminals control PCB A1P At this time pass the wiring into the unit through the w...

Page 16: ...the wire through hole to protect the wires Do not pass the transmission wiring and power supply wiring through the same locations and outside of the unit keep them separated by at least 50mm Not doing...

Page 17: ...er to the Engineering data book Setting method The setting is made using the Local Setting Mode by the remote controller of indoor unit connected to the BS unit For information regarding the setting m...

Page 18: ...MPO BOX NOTES PRINTED CIRCUIT BOARD DIP SWITCH FUSE T 3 15A 250V FLASHING LAMP SERVICE MONITOR GREEN SWITCHING POWER SUPPLY A1P TERMINAL STRIP POWER TERMINAL STRIP CONTROL TERMINAL STRIP C H SELECTOR...

Page 19: ...NOTES NOTES...

Page 20: ...4PW46241 1 Copyright Daikin...

Reviews: