NOTES

• Use ring-type crimp style terminal for connections to 

the power terminal block. (Refer to Fig. 6)
Also, insulate the crimped area by attaching an insula-
tion sleeve, etc.
If these are not available, see the following section.
(a)Wiring of different thicknesses cannot be connected 

to the power terminal block.
(A loose connection could cause abnormal heat-
ing.)

(b)When connecting wire of the same diameter, make 

the connection as shown in the figure 7.

• Use an appropriate screwdriver for tightening the ter-

minal screw.
Using a screwdriver that is too small could damage the 
screw head and prevent proper tightening.

• Over tightening the terminal screw could damage the 

screw.
Refer to the Table 4 for the terminal screw tightening 
torque.

• When fastening the wire, use the included clamp 2)-1 so as not to apply tensile force to the wire connection 

and then securely fasten the wire. Also, after wiring is completed, organize the wiring so that the EL. 
COMPO. BOX lid does not pop up and then properly replace the EL. COMPO. BOX lid.
Make sure no wires are pinched when replacing the EL. COMPO. BOX lid.
Always use the wire through hole to protect the wires.

• Do not pass the transmission wiring and power supply wiring through the same locations and outside of the 

unit keep them separated by at least 50mm.
Not doing so could cause the transmission wiring to pick up electric noise (external noise) and result in a 
malfunction or breakdown.

• After the wiring working is complete, use sealer (field supply) to seal closed the wire through hole.

(Entry by small animals, etc., could cause a malfunction.)

A1P

F1 F2 F1 F2

Transmission wiring from the indoor unit
(To the TO IN/D UNIT F1, F2 terminals)

Ground terminal

Ground wire

Wire

Wire fitting

Terminal block

Power supply wiring
(To the terminal block 
L1, L2 terminals)

Wiring through 
hole (right)

Wiring through hole (left)

Transmission wiring from the outdoor unit
(To the TO OUT/D UNIT F1, F2 terminals)

Clamp 2)
(Accessory)

Clamp 2)
(Accessory)

Clamp 2)
(Accessory)

TO IN/D UNIT TO OUT/D UNIT

Insulation sleeve

Electric wire

Ring-type crimp 
style terminal

Fig. 6

Connect wires of the 
same gauge to both 
sides.

Do not connect 
wires of the same 
gauge to one side.

Do not connect 
wires of different 
gauges.

Fig. 7

Terminal screw size

M3.5 (COOL/HEAT SELECTOR/transmission 

wiring terminal block (A1P))

M4 (Power supply terminal block)
M4 (Ground terminal)

0.80-0.96

1.18-1.44
1.52-1.86

Tightening torque (N/m)

Table 4

Summary of Contents for VRV III BSVQ100P8V1B

Page 1: ...READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE INSTALLATION MANUAL BS unit BSVQ100P8V1B BSVQ160P8V1B BSVQ250P8V1B System air conditioner...

Page 2: ...enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma preve...

Page 3: ...life CAUTION Failure to observe these instructions properly may result in property damage or per sonal injury which may be serious depending on the circumstances WARNING Ask your dealer or qualified p...

Page 4: ...r Do not directly touch refrigerant that has leaked from refrigerant pipes or other areas as there is a danger of frostbite CAUTION Install the BS units power cord and connecting wires at least 1 mete...

Page 5: ...igned for R410A See the catalogue for indoor outdoor unit models that can be connected Normal operation is not possible when connecting units that are originally designed for other refrigerants 2 2 PR...

Page 6: ...icient clearance for maintenance and service can be ensured Refer to Fig 1 Locations where an inspection hole Refer to Fig 2 can be installed to EL COMPO BOX side See Note Where the total piping lengt...

Page 7: ...r the like Install the BS unit so that its weight can be withstood Hanging bracket For supporting the connection pipe Be sure to support the connection piping around the unit using hanging brackets th...

Page 8: ...0 3 pcs 4 locations and washers For M8 Outside diameter dimension 24 to 28mm For M10 Outside diameter 30 to 34mm 2 pcs 4 locations field supply from both the top and bottom sides of the hanging bracke...

Page 9: ...nstallation Make sure that nothing besides the specified refrigerant such as air gets into the refrigerant piping If refrigerant gas leaks during the work ventilate the area The outdoor units are fill...

Page 10: ...the refrigerant pipe joints Using a chlorine flux may cause the pipes to corrode and if it contains fluoride it may cause the refrigerant lubricant to deteriorate adversely affecting the refrigerant...

Page 11: ...door units Piping size outer diameter x minimum thickness Gas pipe Liquid pipe 20 25 32 40 50 12 7x0 80 6 4x0 80 63 80 100 125 15 9x0 99 9 5x0 80 200 19 1x0 80 250 22 2x0 80 mm BS unit Piping size out...

Page 12: ...uid pipe Site piping Gas pipe Site piping Liquid pipe Site piping BS unit Top Accessory pipes 1 2 Accessory pipes 1 1 Gas pipe Site piping Liquid pipe Site piping BS unit Top Suction gas pipe Site pip...

Page 13: ...ation field supply with the seams facing up See figure at right BSVQ100 160P type BSVQ250P type BS unit BS unit Clamp 2 2 Accessory Clamp 2 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3...

Page 14: ...tion Do not turn on the power supply branch switches overload interrupters until all other work is done 7 2 EXAMPLE FOR THE WHOLE SYSTEM 7 3 POWER CIRCUIT SAFETY DEVICE AND CABLE REQUIREMENTS A power...

Page 15: ...the EL COMPO BOX lid and connect the wires to F1 and F2 TO IN D UNIT and F1 and F2 TO OUT D UNIT transmission wiring terminals control PCB A1P At this time pass the wiring into the unit through the w...

Page 16: ...the wire through hole to protect the wires Do not pass the transmission wiring and power supply wiring through the same locations and outside of the unit keep them separated by at least 50mm Not doing...

Page 17: ...er to the Engineering data book Setting method The setting is made using the Local Setting Mode by the remote controller of indoor unit connected to the BS unit For information regarding the setting m...

Page 18: ...MPO BOX NOTES PRINTED CIRCUIT BOARD DIP SWITCH FUSE T 3 15A 250V FLASHING LAMP SERVICE MONITOR GREEN SWITCHING POWER SUPPLY A1P TERMINAL STRIP POWER TERMINAL STRIP CONTROL TERMINAL STRIP C H SELECTOR...

Page 19: ...NOTES NOTES...

Page 20: ...4PW46241 1 Copyright Daikin...

Reviews: