8. ELECTRIC WIRING WORK

8-1  GENERAL INSTRUCTIONS

•  All field supplied parts and materials and electric works must conform to local codes.
• 

Use copper wire only.

•  For electric wiring work, refer to also “Wiring diagram label” attached to the control box cover.
• 

For remote controller wiring details, refer to the installation manual attached to the remote controller.

• 

All wiring must be performed by an authorized electrician.

• 

This system consists of multiple indoor units. Mark each indoor unit as unit A, unit B..., and be sure 
the terminal board wiring to the outdoor unit and BS unit are properly matched. If wiring and piping 
between the outdoor unit and an indoor unit are mismatched, the system may cause a malfunction.

• 

A circuit breaker capable of shutting down power supply to the entire system must be installed.

• 

Refer to the installation manual attached to the outdoor unit for the size of power supply wiring 
connected to the outdoor unit, the capacity of the circuit breaker and switch, and wiring instructions.

• 

Be sure to ground the air conditioner.

• 

Do not connect the ground wire to gas and water pipes, lightning rods, or telephone ground wires.

•  Gas pipes : might cause explosions or fire if gas leaks.
• 

Water pipes : no grounding effect if hard vinyl piping is used.

• 

Telephone ground wires or lightning rods : might cause abnormally high electric potential in the 
ground during lightning storms.

8-2  ELECTRICAL CHARACTERISTICS

Units

Power supply

Fan motor

Model

Hz

Volts

Voltage range

MCA

MFA

kW

FLA

FXZQ07MVJU9

60

208/230

Max. 253

Min. 187

0.8

15

0.055

0.6

FXZQ09MVJU9

0.8

15

0.055

0.6

FXZQ12MVJU9

0.8

15

0.055

0.6

FXZQ15MVJU9

0.8

15

0.055

0.6

FXZQ18MVJU9

0.9

15

0.055

0.7

MCA:  Min. Circuit Amps (A)

MFA:  Max. Fuse Amps (A)

kW: 

Fan Motor Rated Output (kW)

FLA:  Full Load Amps (A)

8-3  SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE

Model

Power supply wiring

Remote controller wiring 

Transmission wiring

Field fuses 

Size, Length

Wire

Size

FXZQ07·09·12·15·18MVJU9

15A

Wire size and 
length must 
comply with 
local codes.

Sheathed wire 

(2 wire)

AWG 18-16

Allowable length of transmission wirings and remote controller wiring are as follows.

(1) Outdoor unit-Indoor unit:

Max. 3280 ft. (Total wiring length: 6580 ft.)

(2) Indoor unit-Remote controller:

Max. 1640 ft.

NOTE 

•  Vinyl wiring with sheath or cable (Insulated thickness : 1/16 in. or more)

Summary of Contents for VRV FXZQ07MVJU9

Page 1: ...manual in a handy place for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f r...

Page 2: ...r to install this product Improper installation can result in water or refrigerant leakage electrical shock fire or explosion Meanings of DANGER WARNING CAUTION and NOTE Symbols DANGER Indicates an im...

Page 3: ...and causing injuries Take into account strong winds typhoons or earthquakes when installing Improper installation may result in the unit falling and causing accidents Make sure that a separate power s...

Page 4: ...greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Piping and follow the procedures Since...

Page 5: ...ening be sure to lift it by holding on to the hanger brackets without exerting any pressure on other parts especially drain piping and other resin parts Decide upon a line of transport Leave the unit...

Page 6: ...each 1 each 2 pcs 1pc 2pcs Shape 8 For gas pipe 9 For liquid pipe 10 Large 11 Small 2 3 OPTIONAL ACCESSORIES The optional decoration panel and remote controller are required for this indoor unit Refer...

Page 7: ...the system is not clear b Items to be checked at time of delivery Also review the SAFETY CONSIDERATIONS Items to be checked Check Are the control box cover air filter and suction grille attached Did y...

Page 8: ...5 18MVJU9 11 1 4 Confirm the space of 11 5 8 or more CAUTION The indoor and outdoor units and the power supply wiring and remote controller wiring must be installed at least 40 in away from any televi...

Page 9: ...seen from A Hanger bracket False ceiling in Fig 3 Fig 4 NOTE Installation is possible with a ceiling dimension of 26 in marked with However to achieve a ceiling panel overlapping dimension of 13 16 in...

Page 10: ...the unit As for the parts to be used for installation work be sure to use the provided accessories and specified parts designated by Daikin 1 For new ceilings 1 1 Install the indoor unit temporarily...

Page 11: ...may malfunction and cause water to drip 1 5 Remove the washer fixing plate 7 used for preventing the washer from falling and tighten the upper nut 1 6 Remove the paper pattern for installation 5 2 Fo...

Page 12: ...to the refrigerant circuit such as air If any refrigerant gas leaks while working on the unit thoroughly ventilate the room immediately Do not mix air or other gas with the specified refrigerant in th...

Page 13: ...the flux contains fluorine it will damage the refrigerant oil Before brazing field refrigerant piping nitrogen gas shall be blown through the piping to expel air from the piping If brazing is done wit...

Page 14: ...sloping downwards at a gradient of at least 1 100 to prevent air pockets from forming If the drain hose cannot be sufficiently set on a slope refer to PRECAUTIONS FOR DRAIN RAISING PIPING on page 14...

Page 15: ...n accessory unit in Ceiling slab Level or tilted slightly up accessory Fig 21 11 3 4 in 40 60 in NOTE To ensure no excessive pressure is applied to the included drain hose 1 do not bend or twist the h...

Page 16: ...ing work around the control box make sure none of the connectors come undone Be sure to attach the control box cover before turning on the power Next press the inspection test run button on the remote...

Page 17: ...supply terminal block Ground Single phase power supply 60 Hz 208 230V REMOTE CONTROL TRANSMISSION WIRING FORCED OFF Fig 24 CAUTION Drain piping connections Do not connect the drain piping directly to...

Page 18: ...itioner Do not connect the ground wire to gas and water pipes lightning rods or telephone ground wires Gas pipes might cause explosions or fire if gas leaks Water pipes no grounding effect if hard vin...

Page 19: ...ly terminal block Use Fig 26 as a guide and allow at least 3 1 4 in for removing the sheath After connection attach the sealing material Refer to Fig 25 Be sure to attach it to prevent infiltration of...

Page 20: ...ightening torque for the terminal blocks Use the correct screwdriver for tightening the terminal screws If the blade of screwdriver is too small the head of the screw might be damaged and the screw wi...

Page 21: ...g Transmission wiring control box cover Remote controller and transmission wiring ex How to attach sealing materials accessory REMOTE CONTROL TRANSMISSION WIRING FORCED OFF accessory Clamp 4 Clamp 4 L...

Page 22: ...d other power wiring at least 2 in so that they do not pass through the same place together Proximity may cause electrical interference malfunctions and breakage 9 2 WIRING EXAMPLE Fit the power suppl...

Page 23: ...llers Outdoor unit Control box Fig 30 3 When including BS unit F1 F2 F1 F2 F1 F2 F1 F2 P1 P2 P1 P2 F1 F2 T1 T2 F1 F2 F1 F2 P1 P2 P1 P2 F1 F2 T1 T2 L1 L2 L1 L2 L1 L2 L1 L2 IN D OUT D IN D OUT D IN D OU...

Page 24: ...1 mA 2 Actuation The following table explains FORCED OFF and ON OFF OPERATIONS in response to input A FORCED OFF ON OFF OPERATION Input ON stops operation impossible by remote controllers Input OFF ON...

Page 25: ...ing FIELD SET MODE Mode No SECOND CODE NO FIRST CODE NO Fig 32 11 1 SETTING AIR OUTLET DIRECTION See the installation manual included with the sealing material of air discharge outlet kit sold separat...

Page 26: ...ay be a problem with the wiring or power so check the wiring again Table 5 Remote control display Content CENTRAL CONTROL is lit up There is a short circuit at the FORCED OFF terminals T1 T2 U4 is lit...

Page 27: ...3P184443 12N EM12A030 1303 DE...

Reviews: