background image

12

3P184443-12N

English

Not recommended but in case of emergency:

You must use a torque wrench but if one is not available, you may follow the installation method 
described below.

When you keep tightening the flare nut with a spanner, there is a point where the tightening torque 
suddenly increases. From that position, further tighten the flare nut at the angle shown below:

Pipe size

Further tightening angle

Recommended arm length of tool

ø1/4”

60 – 90 degrees

Approx. 6 in.

ø1/2”

30 – 60 degrees

Approx. 10 in.

After the work is finished, make sure to check that there is no gas leak.

 CAUTION

CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING

Do not use flux when brazing refrigerant piping. Therefore, use the phosphor copper brazing filler metal 
(B-Cu93P-710/795:ISO 3677) which does not require flux.
Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based 
flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the 

refrigerant oil.

•  Before brazing field refrigerant piping, nitrogen gas shall be blown through the piping to expel air from 

the piping.

If brazing is done without nitrogen gas blowing, a large amount of oxide film develops inside the piping, 

and could cause system malfunction.

• 

When brazing the refrigerant piping, only begin brazing after having carried out nitrogen substitution 
or while inserting nitrogen into the refrigerant piping. Once this is done, connect the indoor unit with a 

flared connection.

• 

Nitrogen should be set to 2.9 psig with a pressure-reducing valve if brazing while inserting nitrogen into 
the piping. 

(Refer to Fig.15)

Refrigerant piping

Part to be 

brazed 

Taping

Nitrogen

Pressure-reducing valve

Nitrogen

Hand valve

Fig. 15

•  Make absolutely sure to execute thermal insulation works on the pipe-connecting section after 

checking gas leakage by thoroughly studying the following figure and using the attached insulation for 
fitting (8) and (9). Fasten both ends with the clamps (4). 

(Refer to Fig. 16)

•  Wrap the sealing pad (11) only around the insulation for the joints on the gas piping side.

(Refer to Fig. 16)

Summary of Contents for VRV FXZQ07MVJU9

Page 1: ...manual in a handy place for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f r...

Page 2: ...r to install this product Improper installation can result in water or refrigerant leakage electrical shock fire or explosion Meanings of DANGER WARNING CAUTION and NOTE Symbols DANGER Indicates an im...

Page 3: ...and causing injuries Take into account strong winds typhoons or earthquakes when installing Improper installation may result in the unit falling and causing accidents Make sure that a separate power s...

Page 4: ...greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Piping and follow the procedures Since...

Page 5: ...ening be sure to lift it by holding on to the hanger brackets without exerting any pressure on other parts especially drain piping and other resin parts Decide upon a line of transport Leave the unit...

Page 6: ...each 1 each 2 pcs 1pc 2pcs Shape 8 For gas pipe 9 For liquid pipe 10 Large 11 Small 2 3 OPTIONAL ACCESSORIES The optional decoration panel and remote controller are required for this indoor unit Refer...

Page 7: ...the system is not clear b Items to be checked at time of delivery Also review the SAFETY CONSIDERATIONS Items to be checked Check Are the control box cover air filter and suction grille attached Did y...

Page 8: ...5 18MVJU9 11 1 4 Confirm the space of 11 5 8 or more CAUTION The indoor and outdoor units and the power supply wiring and remote controller wiring must be installed at least 40 in away from any televi...

Page 9: ...seen from A Hanger bracket False ceiling in Fig 3 Fig 4 NOTE Installation is possible with a ceiling dimension of 26 in marked with However to achieve a ceiling panel overlapping dimension of 13 16 in...

Page 10: ...the unit As for the parts to be used for installation work be sure to use the provided accessories and specified parts designated by Daikin 1 For new ceilings 1 1 Install the indoor unit temporarily...

Page 11: ...may malfunction and cause water to drip 1 5 Remove the washer fixing plate 7 used for preventing the washer from falling and tighten the upper nut 1 6 Remove the paper pattern for installation 5 2 Fo...

Page 12: ...to the refrigerant circuit such as air If any refrigerant gas leaks while working on the unit thoroughly ventilate the room immediately Do not mix air or other gas with the specified refrigerant in th...

Page 13: ...the flux contains fluorine it will damage the refrigerant oil Before brazing field refrigerant piping nitrogen gas shall be blown through the piping to expel air from the piping If brazing is done wit...

Page 14: ...sloping downwards at a gradient of at least 1 100 to prevent air pockets from forming If the drain hose cannot be sufficiently set on a slope refer to PRECAUTIONS FOR DRAIN RAISING PIPING on page 14...

Page 15: ...n accessory unit in Ceiling slab Level or tilted slightly up accessory Fig 21 11 3 4 in 40 60 in NOTE To ensure no excessive pressure is applied to the included drain hose 1 do not bend or twist the h...

Page 16: ...ing work around the control box make sure none of the connectors come undone Be sure to attach the control box cover before turning on the power Next press the inspection test run button on the remote...

Page 17: ...supply terminal block Ground Single phase power supply 60 Hz 208 230V REMOTE CONTROL TRANSMISSION WIRING FORCED OFF Fig 24 CAUTION Drain piping connections Do not connect the drain piping directly to...

Page 18: ...itioner Do not connect the ground wire to gas and water pipes lightning rods or telephone ground wires Gas pipes might cause explosions or fire if gas leaks Water pipes no grounding effect if hard vin...

Page 19: ...ly terminal block Use Fig 26 as a guide and allow at least 3 1 4 in for removing the sheath After connection attach the sealing material Refer to Fig 25 Be sure to attach it to prevent infiltration of...

Page 20: ...ightening torque for the terminal blocks Use the correct screwdriver for tightening the terminal screws If the blade of screwdriver is too small the head of the screw might be damaged and the screw wi...

Page 21: ...g Transmission wiring control box cover Remote controller and transmission wiring ex How to attach sealing materials accessory REMOTE CONTROL TRANSMISSION WIRING FORCED OFF accessory Clamp 4 Clamp 4 L...

Page 22: ...d other power wiring at least 2 in so that they do not pass through the same place together Proximity may cause electrical interference malfunctions and breakage 9 2 WIRING EXAMPLE Fit the power suppl...

Page 23: ...llers Outdoor unit Control box Fig 30 3 When including BS unit F1 F2 F1 F2 F1 F2 F1 F2 P1 P2 P1 P2 F1 F2 T1 T2 F1 F2 F1 F2 P1 P2 P1 P2 F1 F2 T1 T2 L1 L2 L1 L2 L1 L2 L1 L2 IN D OUT D IN D OUT D IN D OU...

Page 24: ...1 mA 2 Actuation The following table explains FORCED OFF and ON OFF OPERATIONS in response to input A FORCED OFF ON OFF OPERATION Input ON stops operation impossible by remote controllers Input OFF ON...

Page 25: ...ing FIELD SET MODE Mode No SECOND CODE NO FIRST CODE NO Fig 32 11 1 SETTING AIR OUTLET DIRECTION See the installation manual included with the sealing material of air discharge outlet kit sold separat...

Page 26: ...ay be a problem with the wiring or power so check the wiring again Table 5 Remote control display Content CENTRAL CONTROL is lit up There is a short circuit at the FORCED OFF terminals T1 T2 U4 is lit...

Page 27: ...3P184443 12N EM12A030 1303 DE...

Reviews: