background image

English 

8

Terminal block (3P)

Terminal block (6P)

Clamp material (1)
(accessory)

Pass the power supply wiring and the ground wire 

(4) 

through the conduit (conduit should be fi eld sup-
plied).

Pass through the 
conduit

Power supply wiring 
and ground wire

Remote controller and 
transmission wiring

Insulation tube (2)

 DANGER

Use only specifi ed wire and connect wires to terminals 

 

tightly. Be careful that wires do not place external stress on 
terminals. Keep wires in neat order so as to not to obstruct 
other equipment. Make sure that the terminal block box 
cover closes tightly. Incomplete connections could result in 
overheating, and in worse cases, electric shock or fi re.

 WARNING

Never connect power supply wiring to the terminal block for 

 

remote controller wiring as this could damage the entire 
system.

 CAUTION

When doing the wiring, make sure the wiring is neat and 

• 

does not cause the terminal block box cover to stick up, then 
close the cover fi rmly. When attaching the terminal block box 
cover, make sure you do not pinch any wires.
Outside the air conditioners, separate the low voltage wiring 

 

(remote controller and transmission wiring) and high voltage 
wiring (ground wire and power supply wiring) at least 5 in. so 
that they do not pass through the same place together. 
Proximity may cause electrical interference, malfunctions, 
and breakage.

[ PRECAUTIONS ]

Refer to the “REMOTE CONTROLLER INSTALLATION 

• 

MANUAL” on how to install and lay the wiring for the remote 
controller.
See also the “Wiring Diagram Label” located inside the unit’s 

• 

fan housing.
Connect the remote controller and transmission wiring their 

• 

respective terminal blocks.

 CAUTION

Do not, under any circumstances, connect the power 

 

supply wiring to the remote controller or transmission 
wiring terminal block. Doing so can destroy the entire 
system.

[ WIRING EXAMPLE ]
No. 1 system      When using 1 remote controller for 

1 indoor unit

Indoor unit A

Indoor unit B

Most
downstream
Indoor unit 

Power supply

single phase

60Hz 208-230V

Power supply

single phase

60Hz 208-230V

Power supply

single phase

60Hz 208-230V

Outdoor unit

F

T

1

L1

1

1

1

P

P

2

P

L2

1

2

P

T

F

2

F

P

F

1

2

2

2

P

1

L2

2

P

2

F

IN/D

1

OUT/D

1

P

F

2

F

1

P

L1

F

1

2

T

2

T

1

P

P

2

1

F

2

L2

F

L1

1

2

T T

P

Remote controller

Remote controller

Remote controller

L1 L2

 (option) 

 (option) 

 (option) 

L1 L2

L1 L2

No. 2 system      For group control or use with 2 remote 

controllers

Outdoor unit

Note)  There is not need to set the indoor unit 
 

address when using group control. 

 

(It is automatically set when the power 

 

is turned on.)

Indoor 
unit A

Indoor unit B

Most down-
stream
indoor unit

For use with 2
remote controllers

Case of group control

L1 L2

Remote controller

Remote controller

Remote controller

1

P

2

P

1

P

2

P

1

P

2

P

1

P

P

2

1

F

2

L2

F

L1

L2

L1

1

2

F

F

1

2

F

F

1

2

T T

1

P

P

2

1

F

2

F

1

2

T T

L2

L1

1

P

P

2

1

F

2

F

1

2

T T

IN/D OUT/D

 (option) 

 (option) 

Power supply

single phase

60Hz 208-230V

01_EN_3P250363-1.indd   8

01_EN_3P250363-1.indd   8

6/18/2009   2:01:19 PM

6/18/2009   2:01:19 PM

Summary of Contents for VRV FXTQ12PVJU

Page 1: ...lly before installation Keep this manual in a handy place for future reference This manual should be left with the equipment owner Lea cuidadosamente estas instrucciones antes de instalar Guarde este...

Page 2: ...ck that the refrigerant gas does not leak throughout the system Do not install unit in an area where flammable materials are present due to risk of explosions that can cause serious injury or death Sa...

Page 3: ...efrigerant is charged in a state of gas its composition can change and the system will not work properly The indoor unit is for R 410A See the catalog for indoor models that can be connected Normal op...

Page 4: ...HECK AFTER INSTALLATION IS FINISHED a Items to be checked after completion of work Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor unit fixed firmly T...

Page 5: ...should be installed as far away from fluorescent lighting as possible DANGER Do not install unit in an area where flammable materials are present due to the risk explosion resulting in serious injury...

Page 6: ...nt panels upper lower 1 Slide the front panel lower along the field piping until it 2 is far enough away that it will not be affected by heat from brazing as shown in the diagram below Braze up to the...

Page 7: ...care regarding the following when performing duct work Verify that duct work does not exceed the unit s setting range of external static pressure up to 0 5 in Install canvas ducts at air outlets and...

Page 8: ...230 Min 187 Max 253 1 1 15 0 37 0 9 18 type 1 5 0 37 1 2 24 type 1 6 0 56 1 3 30 type 2 3 0 56 1 8 36 type 3 0 0 56 2 4 42 type 3 9 0 56 3 1 48 type 5 0 0 56 4 0 54 type 6 5 0 56 5 2 MCA Minimum Circ...

Page 9: ...LATION MANUAL on how to install and lay the wiring for the remote controller See also the Wiring Diagram Label located inside the unit s fan housing Connect the remote controller and transmission wiri...

Page 10: ...aged Refer to the table below for the tightening torque of the terminal screws Terminal block Tightening torque ft lbf Remote controller transmission wiring terminal block 6P 0 58 0 72 Power supply wi...

Page 11: ...e the customer keeps the Field Settings manual along with the operating manual in a safe place SETTINGS WHEN USING THE OPTIONAL RE 10 1 MOTE SENSOR This product does not include an air inlet thermisto...

Page 12: ...crystal display to identify the point of trouble An explanation of malfunction codes and the corresponding trouble is provided in CAUTION FOR SERVICING of the outdoor unit If the display shows any of...

Page 13: ...3P250363 1 EM09A009 0906 HT 00_CV_3P250363 1 indd 2 00_CV_3P250363 1 indd 2 5 29 2009 2 10 00 PM 5 29 2009 2 10 00 PM...

Reviews: