background image

English

No. 3 system      When including BS unit

Outdoor unit

BS unit

L1 L2

Indoor unit A

Remote controller

(option)

F

F

1

2

F

F

1

2

F

F

1

2

F

F

1

2

IN/D

IN/D

OUT/D

OUT/D

1

P

P

2

1

F

2

L2

F

L1

1

2

T T

1

P

2

P

Power supply

single phase

60Hz 208-230V

Precautions when laying power supply wiring

Wiring of different thicknesses cannot be connected to the 

• 

power supply wiring terminal block. (Slack in the power 
supply wiring may cause abnormal heat.)
Use sleeve-insulated round crimp-style terminals for con-

• 

nections to the power supply wiring terminal block. When 
none are available, connect wires of the same diameter to 
both sides, as shown in the fi gure.

Electric wire

Round crimp-style terminal

Insulation sleeve

Connect wires of 
the same gauge to 
both sides.

Do not connect 
wires of the same 
gauge to one side.

Do not connect 
wires of different 
gauges. 

Follow the instructions are below if the wiring may get 
very hot due to slack in the power supply wiring.

For wiring, use the designated power supply wiring and 

• 

connect fi rmly, then secure to prevent outside pressure 
being exerted on the terminal board.
Use the correct screwdriver for tightening the terminal 

• 

screws. If the blade of screwdriver is too small, the head of 
the screw might be damaged, and the screw will not be 
properly tightened.
If the terminal screws are tightened too hard, screws might 

• 

be damaged.
Refer to the table below for the tightening torque of the 

• 

terminal screws.

Terminal block

Tightening torque (ft · lbf)

Remote controller / transmission 

wiring terminal block (6P)

0.58 – 0.72

Power supply wiring terminal 

block (3P)

0.87 – 1.06

CONTROL BY 2 REMOTE CONTROLLERS (Con-

9-2 

trolling 1 indoor unit by 2 remote controllers)

When using 2 remote controllers, one must be set to “MAIN” 

• 

and the other to “SUB”.

MAIN/SUB CHANGEOVER

Insert a 

(1) 

 screwdriver into the recess between the 

upper and lower part of remote controller and, work-
ing from the 2 positions, pry off the upper part.

The remote controller PC board is attached to the upper 
part of remote controller.

Insert the screwdriver here and gently work 
off the upper part of remote controller.

Lower part of 
remote controller

Upper part of 
remote controller

Turn the MAIN/SUB changeover switch on one of the 

(2) 

two remote controller PC boards to “S”.

(Leave the switch of the other remote controller set to “M”.)

S

M

S

S

M

(Factory setting)

Only one remote controller 
needs to be changed 
if factory settings have 
remained untouched.

Remote controller 
PC board

Wiring Method

 (See ‘‘8. ELECTRIC WIRING WORK’’)

Remove the terminal block box cover.

(3) 

Add remote controller 2 (SUB) to the terminal block 

(4) 

for remote controller (P¹, P²) in the terminal block box.
(There is no polarity.)

Remote controller wiring 
terminal block

Remote 
controller 2
(SUB)

Remote 
controller 1
(MAIN)

1

P

2

P

1

F

2

F

1

T

2

T

FORCED

OFF

REMOTE
CONTRL

TRANSMISSION

WIRING

01_EN_3P250363-1.indd   9

01_EN_3P250363-1.indd   9

6/18/2009   2:01:20 PM

6/18/2009   2:01:20 PM

Summary of Contents for VRV FXTQ12PVJU

Page 1: ...lly before installation Keep this manual in a handy place for future reference This manual should be left with the equipment owner Lea cuidadosamente estas instrucciones antes de instalar Guarde este...

Page 2: ...ck that the refrigerant gas does not leak throughout the system Do not install unit in an area where flammable materials are present due to risk of explosions that can cause serious injury or death Sa...

Page 3: ...efrigerant is charged in a state of gas its composition can change and the system will not work properly The indoor unit is for R 410A See the catalog for indoor models that can be connected Normal op...

Page 4: ...HECK AFTER INSTALLATION IS FINISHED a Items to be checked after completion of work Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor unit fixed firmly T...

Page 5: ...should be installed as far away from fluorescent lighting as possible DANGER Do not install unit in an area where flammable materials are present due to the risk explosion resulting in serious injury...

Page 6: ...nt panels upper lower 1 Slide the front panel lower along the field piping until it 2 is far enough away that it will not be affected by heat from brazing as shown in the diagram below Braze up to the...

Page 7: ...care regarding the following when performing duct work Verify that duct work does not exceed the unit s setting range of external static pressure up to 0 5 in Install canvas ducts at air outlets and...

Page 8: ...230 Min 187 Max 253 1 1 15 0 37 0 9 18 type 1 5 0 37 1 2 24 type 1 6 0 56 1 3 30 type 2 3 0 56 1 8 36 type 3 0 0 56 2 4 42 type 3 9 0 56 3 1 48 type 5 0 0 56 4 0 54 type 6 5 0 56 5 2 MCA Minimum Circ...

Page 9: ...LATION MANUAL on how to install and lay the wiring for the remote controller See also the Wiring Diagram Label located inside the unit s fan housing Connect the remote controller and transmission wiri...

Page 10: ...aged Refer to the table below for the tightening torque of the terminal screws Terminal block Tightening torque ft lbf Remote controller transmission wiring terminal block 6P 0 58 0 72 Power supply wi...

Page 11: ...e the customer keeps the Field Settings manual along with the operating manual in a safe place SETTINGS WHEN USING THE OPTIONAL RE 10 1 MOTE SENSOR This product does not include an air inlet thermisto...

Page 12: ...crystal display to identify the point of trouble An explanation of malfunction codes and the corresponding trouble is provided in CAUTION FOR SERVICING of the outdoor unit If the display shows any of...

Page 13: ...3P250363 1 EM09A009 0906 HT 00_CV_3P250363 1 indd 2 00_CV_3P250363 1 indd 2 5 29 2009 2 10 00 PM 5 29 2009 2 10 00 PM...

Reviews: