background image

English 

10

[ PRECAUTIONS ]

Crossover wiring is needed when using group control and 2 

• 

remote controllers at the same time.
Connect the indoor unit at the end of the crossover wire (P

• 

¹, 

P²) to remote controller 2 (SUB).

Indoor unit 1

Indoor unit 2

Max. No. of 
indoor units

Crossover wire (P

1

.P

2

)

Remote controller 1
(MAIN)

Remote controller 2
(SUB)

REMOTE CONTROL (FORCED OFF AND ON/

9-3 

OFF OPERATION)

Connect input lines from the outside to the terminals T

• 

¹ and 

T² on the terminal block (6P) for remote controller to achieve 
remote control.
See the “

• 

10. FIELD SETTING AND TEST RUN

” for details 

on operation.

Input A

1

P

2

P

1

F

2

F

1

T

2

T

FORCED

OFF

REMOTE

CONTRL

TRANSMISSION

WIRING

Wire specifi cation

Sheathed vinyl cord or cable (2 wires)

Gauge

AWG18 – 16

Length

Max. 328 ft.

External terminal

Contact that can ensure the minimum 
applicable load of 15 V DC, 1 mA.

CENTRALIZED CONTROL

9-4 

For centralized control, it is necessary to designate the 

• 

group No. For details, refer to the manual of each optional 
controllers for centralized control.

FIELD SETTING AND TEST RUN

10. 

Field settings may have to be performed using the re-

mote controller, depending on the type of installation.

Make sure the terminal block box covers are closed 

(1) 

on the indoor and outdoor units.

Depending on the type of installation, make the fi eld 

(2) 

settings from the remote controller after the power is 
turned on, following the “Field Settings” manual which 
came with the remote controller.

The settings can select “Mode No.”, “FIRST CODE NO.” 

• 

and “SECOND CODE NO.”.
The “Field Settings” included with the remote controller 

• 

lists the order of the settings and method of operation.

SETTING

Mode No.

FIELD SET 
MODE

SECOND 
CODE NO.

FIRST 
CODE NO.

Lastly, make sure the customer keeps the “Field Settings” 

• 

manual, along with the operating manual, in a safe place.

SETTINGS WHEN USING THE OPTIONAL RE-

10-1 

MOTE SENSOR

This product does not include an air inlet thermistor.
It uses a remote controller thermistor for control purposes.
For this reason, it is necessary to install an optional remote 
thermistor in the following cases:

When the remote controller will be installed at a location 

• 

where it cannot accurately measure the indoor temperature.
When using a remote controller without a built-in thermistor 

• 

(simple remote controller, central remote controller, wireless 
remote controller, no remote controller).
When using a remote controller thermistor, change the 
settings as described below:
(The SECOND CODE NO. is set to “03” when shipped.)

Mode No.

FIRST 

CODE NO.

SECOND 

CODE NO.

To use both the remote 
controller thermistor and the 
remote thermistor

10 (20)

2

01

To use only the remote 
thermistor

02

To use only the remote 
controller thermistor

03

REMOTE CONTROL SETTING

10-2 

Forced off and ON/OFF operation should be selected by select-

• 

ing the SECOND CODE  NO. as shown in the table below.
(The SECOND CODE NO. is set to “01” when shipped.)

External ON/OFF input

Mode No.

FIRST 

CODE NO.

SECOND 

CODE NO.

Forced off

12 (22)

1

01

ON/OFF operation

02

Input A of forced off and ON/OFF operation work as shown 

• 

in the table below.

Forced off

ON/OFF operation

Input A “on” to force a stop 
(remote controller reception 
prohibited)

Unit operated by changing input 
A from “off” to “on”

Input A “off” to allow remote 
controller

Unit stopped by changing input A 
from “on” to “off”

SETTING THE FILTER SIGN DISPLAY INTERVAL

10-3 

Explain the following to the customer if the fi lter dirt settings 

• 

have been changed.
The fi lter sign display time is set to 2500 hours (equivalent 

• 

to 1 year’s use) when shipped.

01_EN_3P250363-1.indd   10

01_EN_3P250363-1.indd   10

6/18/2009   2:01:21 PM

6/18/2009   2:01:21 PM

Summary of Contents for VRV FXTQ12PVJU

Page 1: ...lly before installation Keep this manual in a handy place for future reference This manual should be left with the equipment owner Lea cuidadosamente estas instrucciones antes de instalar Guarde este...

Page 2: ...ck that the refrigerant gas does not leak throughout the system Do not install unit in an area where flammable materials are present due to risk of explosions that can cause serious injury or death Sa...

Page 3: ...efrigerant is charged in a state of gas its composition can change and the system will not work properly The indoor unit is for R 410A See the catalog for indoor models that can be connected Normal op...

Page 4: ...HECK AFTER INSTALLATION IS FINISHED a Items to be checked after completion of work Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor unit fixed firmly T...

Page 5: ...should be installed as far away from fluorescent lighting as possible DANGER Do not install unit in an area where flammable materials are present due to the risk explosion resulting in serious injury...

Page 6: ...nt panels upper lower 1 Slide the front panel lower along the field piping until it 2 is far enough away that it will not be affected by heat from brazing as shown in the diagram below Braze up to the...

Page 7: ...care regarding the following when performing duct work Verify that duct work does not exceed the unit s setting range of external static pressure up to 0 5 in Install canvas ducts at air outlets and...

Page 8: ...230 Min 187 Max 253 1 1 15 0 37 0 9 18 type 1 5 0 37 1 2 24 type 1 6 0 56 1 3 30 type 2 3 0 56 1 8 36 type 3 0 0 56 2 4 42 type 3 9 0 56 3 1 48 type 5 0 0 56 4 0 54 type 6 5 0 56 5 2 MCA Minimum Circ...

Page 9: ...LATION MANUAL on how to install and lay the wiring for the remote controller See also the Wiring Diagram Label located inside the unit s fan housing Connect the remote controller and transmission wiri...

Page 10: ...aged Refer to the table below for the tightening torque of the terminal screws Terminal block Tightening torque ft lbf Remote controller transmission wiring terminal block 6P 0 58 0 72 Power supply wi...

Page 11: ...e the customer keeps the Field Settings manual along with the operating manual in a safe place SETTINGS WHEN USING THE OPTIONAL RE 10 1 MOTE SENSOR This product does not include an air inlet thermisto...

Page 12: ...crystal display to identify the point of trouble An explanation of malfunction codes and the corresponding trouble is provided in CAUTION FOR SERVICING of the outdoor unit If the display shows any of...

Page 13: ...3P250363 1 EM09A009 0906 HT 00_CV_3P250363 1 indd 2 00_CV_3P250363 1 indd 2 5 29 2009 2 10 00 PM 5 29 2009 2 10 00 PM...

Reviews: