Where the ceiling is strong enough to bear the indoor 

• 

unit weight.
Where the false ceiling is not noticeably on an incline.

• 

Where suffi cient clearance for maintenance and service 

• 

can be ensured. 

(see diagram below)

Where piping between indoor and outdoor units is 

• 

possible within the allowable limit. (Refer to the installa-
tion manual for the outdoor unit.)

12 or 
more

12 or 
more

12 or more

24 or more

Ceiling

(length : in.)

H

Ensure suffi cient space for the bottom of the product 

• 

(H dimensions) so that a downward slope of 1/100 can 
be maintained for drain piping, as described for the 
intake duct installation and in “

6. DRAIN PIPING 

WORK

”.

[ PRECAUTION ]

Install the indoor and outdoor units, power supply wiring 

• 

and connecting wires at least 3.5 ft. away from televi-
sions or radios in order to prevent image interference or 
noise. (Depending on the radio waves, a distance of 
3.3 ft. may not be suffi cient enough to eliminate the 
noise.)
If installing the wireless kit in a room with electronic 

• 

fl uorescent lighting (inverter or rapid start type), the 
remote controller’s transmission distance may be short-
ened. Indoor units should be installed as far away from 
fl uorescent lighting as possible.

 DANGER

Do not install unit in an area where fl ammable materials are 

 

present due to the risk explosion resulting in serious injury 
or death.

 WARNING

If the supporting structural members are not strong enough 

 

to take the unit’s weight, the unit could fall out of place and 
cause serious injury.

PREPARATIONS BEFORE INSTALLA-

4. 

TION AND INSTALLATION

When installing the product, refer to “3. SELECTING 

(1) 

INSTALLATION SITE” and consider the product size 
as shown below.

C

D

11

E

B

A

F

G

1-1/8

Gas line

H

1-3/16

(1-3/16)

1

3-1/4

I

2-7/8

(1-3/16)

Liquid line

(length: in.)

Model

A

B

C

D

E

F

G

H

I

12 · 18 type

46-
3/4

22

17-
1/2

19-
1/2

10

14-
1/2

11-

15/16

17-
1/8

17-

15/16

24 · 30 · 36 · 
42 · 48 · 54 
type

53-
3/4

24

20

22

12

19-
5/8

11-

15/16

19-
5/8

19-

15/16

Make sure the range of the unit’s external static pres-

(2) 

sure is not exceeded. (up to 0.5 in.)

Check if the unit is horizontally level.

(3) 

Condensation may form on the product in some 

(4) 

operating environments. Be sure to provide (fi eld-
supplied) and install a second drain pan.

 WARNING

Be sure to install the product in a vertical orientation. Using 

 

the product in a horizontal orientation may result in problems 
such as reduced capacity.

01_EN_3P250363-1.indd   4

01_EN_3P250363-1.indd   4

6/18/2009   2:01:14 PM

6/18/2009   2:01:14 PM

Summary of Contents for VRV FXTQ12PVJU

Page 1: ...lly before installation Keep this manual in a handy place for future reference This manual should be left with the equipment owner Lea cuidadosamente estas instrucciones antes de instalar Guarde este...

Page 2: ...ck that the refrigerant gas does not leak throughout the system Do not install unit in an area where flammable materials are present due to risk of explosions that can cause serious injury or death Sa...

Page 3: ...efrigerant is charged in a state of gas its composition can change and the system will not work properly The indoor unit is for R 410A See the catalog for indoor models that can be connected Normal op...

Page 4: ...HECK AFTER INSTALLATION IS FINISHED a Items to be checked after completion of work Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor unit fixed firmly T...

Page 5: ...should be installed as far away from fluorescent lighting as possible DANGER Do not install unit in an area where flammable materials are present due to the risk explosion resulting in serious injury...

Page 6: ...nt panels upper lower 1 Slide the front panel lower along the field piping until it 2 is far enough away that it will not be affected by heat from brazing as shown in the diagram below Braze up to the...

Page 7: ...care regarding the following when performing duct work Verify that duct work does not exceed the unit s setting range of external static pressure up to 0 5 in Install canvas ducts at air outlets and...

Page 8: ...230 Min 187 Max 253 1 1 15 0 37 0 9 18 type 1 5 0 37 1 2 24 type 1 6 0 56 1 3 30 type 2 3 0 56 1 8 36 type 3 0 0 56 2 4 42 type 3 9 0 56 3 1 48 type 5 0 0 56 4 0 54 type 6 5 0 56 5 2 MCA Minimum Circ...

Page 9: ...LATION MANUAL on how to install and lay the wiring for the remote controller See also the Wiring Diagram Label located inside the unit s fan housing Connect the remote controller and transmission wiri...

Page 10: ...aged Refer to the table below for the tightening torque of the terminal screws Terminal block Tightening torque ft lbf Remote controller transmission wiring terminal block 6P 0 58 0 72 Power supply wi...

Page 11: ...e the customer keeps the Field Settings manual along with the operating manual in a safe place SETTINGS WHEN USING THE OPTIONAL RE 10 1 MOTE SENSOR This product does not include an air inlet thermisto...

Page 12: ...crystal display to identify the point of trouble An explanation of malfunction codes and the corresponding trouble is provided in CAUTION FOR SERVICING of the outdoor unit If the display shows any of...

Page 13: ...3P250363 1 EM09A009 0906 HT 00_CV_3P250363 1 indd 2 00_CV_3P250363 1 indd 2 5 29 2009 2 10 00 PM 5 29 2009 2 10 00 PM...

Reviews: