background image

English

REFRIGERANT PIPING WORK

5. 

Observe the requirements listed below for refrigerant 

piping sizes.

Liquid

Gas

12 · 18 type

2/8 in.

4/8 in.

24 · 30 · 36 · 
42 · 48 · 54 type

3/8 in.

5/8 in.

Execute heat insulation work completely on both sides of 

the gas piping and the liquid piping. Otherwise, a water 
leakage can result sometimes.
Use insulation that can withstand temperatures of at least 
250°F. Reinforce the insulation on the refrigerant piping 
according to the installation environment. If the tempera-
ture or humidity in the product installation location might 
reach 86°F or 80%, respectively. Condensation may form 
on the surface of the insulation.

 CAUTION

Follow the points at below.

Use a tube cutter and fl are suitable for the type of refriger-

• 

ant.
To prevent dust, moisture or other foreign matter from infi l-

• 

trating the piping, either pinch the end or cover it with tape.
Do not allow anything other than the designated refrigerant 

 

to get mixed into the refrigerant circuit, such as air, etc. If 
any refrigerant gas leaks while working on the unit, ventilate 
the room thoroughly right away.

Cut off the spin closure.

(1) 

The outdoor unit is charged with refrigerant.

• 

This coil is shipped under 150 P.S.I.G. pressure.

• 

Carry out the following work carefully giving caution to 
blowout of high pressure gas.
(Work detail)
Cut off the spin closure with a tube cutter.
(Both liquid line and gas line)

Cut with a pipe cutter

Connect the piping.

(2) 

Remove the front panels (upper) (lower).

1. 

Slide the front panel (lower) along the fi eld piping until it 

2. 

is far enough away that it will not be affected by heat 
from brazing, as shown in the diagram below.
Braze up to the fi eld piping fi tting port.

3. 

Close the front panels (upper) (lower) once heat from 

4. 

the brazed areas has dissipated.

Field piping fitting port (brazed)

Field piping

After the work is fi nished, make sure to check that 

(3) 

there is no gas leak.

After checking for gas leaks, be sure to insulate the 

(4) 

pipe connections referring to below.

Do not leave a gap

Gas piping

Pipe heat insulation 
material

Liquid piping

Main 
unit

 CAUTION

Be sure to insulate any fi eld piping all the way to the piping 
connection inside the unit. Any exposed piping may cause 
condensation or burns if touched.

When brazing the refrigerant piping, perform nitrogen re-

• 

placement fi rst, or perform the brazing while feeding nitro-
gen into the refrigerant piping. (

see diagram below

)

Refrigerant piping

Part to be brazed

Taping

Pressure-reducing valve

hands 
valve

Nitrogen

Nitrogen

 CAUTION

When brazing a pipe while feeding nitrogen inside the pipe, 

 

make sure to set the nitrogen pressure to 29 psi or less 
using the pressure reducing valve.
(This pressure is such that breeze is blown to your cheek.)

 DANGER

Use of oxygen could result in an explosion resulting in 

• 

serious injury or death. Only use nitrogen gas.
Refrigerant gas may produce toxic gas if it comes in contact 

 

with fi re such as from a fan heater, stove or cooking device. 
Exposure to this gas could cause severe injury or death.

01_EN_3P250363-1.indd   5

01_EN_3P250363-1.indd   5

6/18/2009   2:01:15 PM

6/18/2009   2:01:15 PM

Summary of Contents for VRV FXTQ12PVJU

Page 1: ...lly before installation Keep this manual in a handy place for future reference This manual should be left with the equipment owner Lea cuidadosamente estas instrucciones antes de instalar Guarde este...

Page 2: ...ck that the refrigerant gas does not leak throughout the system Do not install unit in an area where flammable materials are present due to risk of explosions that can cause serious injury or death Sa...

Page 3: ...efrigerant is charged in a state of gas its composition can change and the system will not work properly The indoor unit is for R 410A See the catalog for indoor models that can be connected Normal op...

Page 4: ...HECK AFTER INSTALLATION IS FINISHED a Items to be checked after completion of work Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor unit fixed firmly T...

Page 5: ...should be installed as far away from fluorescent lighting as possible DANGER Do not install unit in an area where flammable materials are present due to the risk explosion resulting in serious injury...

Page 6: ...nt panels upper lower 1 Slide the front panel lower along the field piping until it 2 is far enough away that it will not be affected by heat from brazing as shown in the diagram below Braze up to the...

Page 7: ...care regarding the following when performing duct work Verify that duct work does not exceed the unit s setting range of external static pressure up to 0 5 in Install canvas ducts at air outlets and...

Page 8: ...230 Min 187 Max 253 1 1 15 0 37 0 9 18 type 1 5 0 37 1 2 24 type 1 6 0 56 1 3 30 type 2 3 0 56 1 8 36 type 3 0 0 56 2 4 42 type 3 9 0 56 3 1 48 type 5 0 0 56 4 0 54 type 6 5 0 56 5 2 MCA Minimum Circ...

Page 9: ...LATION MANUAL on how to install and lay the wiring for the remote controller See also the Wiring Diagram Label located inside the unit s fan housing Connect the remote controller and transmission wiri...

Page 10: ...aged Refer to the table below for the tightening torque of the terminal screws Terminal block Tightening torque ft lbf Remote controller transmission wiring terminal block 6P 0 58 0 72 Power supply wi...

Page 11: ...e the customer keeps the Field Settings manual along with the operating manual in a safe place SETTINGS WHEN USING THE OPTIONAL RE 10 1 MOTE SENSOR This product does not include an air inlet thermisto...

Page 12: ...crystal display to identify the point of trouble An explanation of malfunction codes and the corresponding trouble is provided in CAUTION FOR SERVICING of the outdoor unit If the display shows any of...

Page 13: ...3P250363 1 EM09A009 0906 HT 00_CV_3P250363 1 indd 2 00_CV_3P250363 1 indd 2 5 29 2009 2 10 00 PM 5 29 2009 2 10 00 PM...

Reviews: