ESIE15-11A
|
Part 3. Field settings
8. Selfcleaning panel BYCQ140D7G
23/09/16
Page 47
VRV4 indoor units
8. Selfcleaning panel BYCQ140D7G
DIP-switches on PCB
14/
24
2
when to display cleaning requirement on the
remote control according to number of operating
hours
01
Display after 1.250h
02
Display after 2.500h
03
Display after 5.000h
3
Display filter change on the remote control
according to number of operating hours
01
no display
02
Display after 32.000h
03
Display after 48.000h
04
Display after 72.000h
4
Panel indicator (green)
01
On while in a/c operation and filter cleaning operation
02
possible to turn on while in filter cleaning operation only
03
off while in a/c operation and filter cleaning operation
04
On
8
auto cleaning program
01
choice between auto and schedule
02
only schedule (auto not in menu)
9
Dust amount setting
01
standard
02
dust amount big
BS1
Cleaning test
Push for 1 second to start the cleaning test
BS2
Error reset
Push for 1 second to reset an error
DIP DS1 – 1
Self-cleaning available / unavailable
ON - not available
OFF - available
DIP DS1 – 2
Light intensity of the infrared sensor
ON - high
OFF - normal