ESIE15-11A
|
Part 3. Field settings
4. Wired remote controller BRC1E51
Page 34
23/09/16
VRV4 indoor units
1e
0
"set temp mode changeover" visibility
in main menu
01
visible
02
hide from main menu
1
enable temperature display in °C or °F
01
not visible
from factory locked to °C
02
visible
visible in menu, choice between °C
and °F
2
"setback" - function
01
not available
Setback is home leave function
02
available
3
selection set temperature in limit oper-
ation when power on/off
01
not keep
02
keep
4
timer setting: when centralized control
(similar to BRC1D528 setting 1b-5)
01
not visible
to avoid conflict between timer inside
centralized remocon and BRC1E
02
visible
5
hour indication
01
not visible in menu
default 24h is activated
02
visible in menu
enduser can choose 24h or 12h dis-
play
6
count down timer
01
not visible in menu
02
visible in menu
A
Offset for master remocon sensor
01
-3°C
with this setting it's possible to modify
the readout by remocon of the ambi-
ent temperature
02
-2,5°C
03
-2°C
04
-1,5°C
05
-1°C
06
-0,5°C
07
0°C
08
+0,5°C
09
+1°C
B
offset for slave remocon sensor
01
-3°C
with this setting it's possible to modify
the readout of ambient temperature of
the secondary remocon
02
-2,5°C
03
-2°C
04
-1,5°C
05
-1°C
06
-0,5°C
07
0°C
08
+0,5°C
09
+1°C