ESIE15-11A
|
Part 3. Field settings
6. General indoor units
Page 44
23/09/16
VRV4 indoor units
13 /
23
0
Airflow amount setting (Ceiling height)
01
normal ceiling (<2,7m)
Depends on indoor unit
02
slightly higher ceiling
(2,7m)
03
high ceiling (3m)
1
selection of airflow direction (set when
a blocking path kit has been installed,
4-way blow panel)
01
4 way directions
Note:
freeze-up protection will come
in when the temperature, measured
by R2T is below -1°C for 10 minutes.
02
3 way directions
Note:
freeze-up protection will come
in when the temperature, measured
by R2T is below 0°C for 1 minute or
below 1°C for 15 minutes.
03
2 way directions
2
Swing pattern setting if 4 swing
motors
01
all directions simultane-
ously swing
02
--
03
opposite sides synchroni-
zation swing
3
Output to flap motor
01
enabled
02
disabled
03
--
4
Setting of airflow direction adjustment
range
01
draft prevention
high position (10-40°)
02
standard
standard position (10-65°)
03
ceiling soiling prevention
low position (30-65°)
5
fanspeed setting
01
Standard
for FXFQ-M, FXHQ-M & FXZQ-M
02
Low
03
Low
Setting the static pressure selection
01
Standard (10/15Pa)
for FXDQ-A & FXNQ-A
02
High static pressure
(30/44Pa)
03
Medium static pressure
04
Medium static pressure
6
External static pressure settings
01
30 Pa
only for FXMQ 40 PVE
02
50 Pa
for FXSQ-P/A, FXMQ-P, FXTQ-A
ESP value based on nominal airflow
rate = Hhspeed
03
60 Pa
04
70 Pa
05
80 Pa
06
90 Pa
07
100 Pa
08
110 Pa
09
120 Pa
10
130 Pa
11
140 Pa
12
150 Pa
13
160 Pa
14
180 Pa
only for FXMQ 50 - 125 PVE
15
200 Pa
7
Thermostat swing
01
equipped
02
not equipped