ESIE15-11A
|
Part 3. Field settings
5. Wired remote controller BRC1E52
23/09/16
Page 39
VRV4 indoor units
1c
0
display of actual room temperature
01
off
02
on
1
selection air thermistor shown in room
temp display (for auto mode and set-
back function only)
01
air return (R1T)
For auto-function & setback
02
thermistor of BRC1E
2
Visualisation of mode display on
remocon in auto mode
01
off
Whether or not 'heating/cooling’ is dis-
played during automatic mode (other-
wise only 'automatic' is mentioned on
remocon)
02
on
3
disable level
01
level 2 (low, high; on/off;
operation mode)
02
level 3 (on/off)
4
backlight on
01
permanently off
02
on for 30 seconds when
pushing any button
03
always on
5
operation when backlight is off
01
no
when pushing a button, first backlight
is activated, function of button is not
activated
02
yes
when pushing a button, backlight is
activated and immediately function of
button is activated
6
display of remocon
01
permanent display
the screen always shows values
02
screen goes blank after 5
minutes
touching any button will reactivate the
screen
9
Sensor selection if 2 remocon
01
main controller
temperature sensor of main controller
is used for ambient (in case 1c-1-2)
02
2nd controller
temperature sensor of 2nd controller
is used for ambient (in case 1c-1-2)
10
Offset master remocon sensor
01
-3°C
to modify displayed temperature on
remocon 1
02
-2,5°C
03
-2°C
04
-1,5°C
05
-1°C
06
-0,5°C
07
0°C
08
+0,5°C
09
+1°C
11
Offset slave remocon sensor
01
-3°C
to modify displayed temperature on
remocon 2
02
-2,5°C
03
-2°C
04
-1,5°C
05
-1°C
06
-0,5°C
07
0°C
08
+0,5°C
09
+1°C