ESIE15-11A
|
Part 3. Field settings
5. Wired remote controller BRC1E52
Page 40
23/09/16
VRV4 indoor units
1e
0
"set temp mode changeover" visibility
in main menu
01
visible
02
hide from main menu
1
enable temperature display in °C or °F
01
not visible in menu
from factory locked to °C
02
visible in menu
visible in menu, choice between °C
and °F
2
Setback function
01
not available
02
available for heating
03
available for cooling
04
available for heating &
cooling
4
timer setting: when centralized control
(similar to BRC1D528 setting 1b-5)
01
not visible
to avoid conflict between timer inside
centralized remocon and BRC1E
02
visible
5
hour indication
01
not visible in menu
default 24h is activated
02
visible in menu
enduser can choose 24h or 12h dis-
play
6
count down timer
01
not visible in menu
02
visible in menu
9
Display of 'change-over' and 'central-
ised' symbols
01
not visible on remocon
whether or not the 'arrows' symbol is
visible on the remocon
02
visible in remocon
10
Display of info on remocon when acti-
vating prohibited function which is
locked through centralised control
01
show key-symbol
02
show message
11
switching delay in automatic mode
01
15 min
02
30 min
03
60 min
04
90 min