ESIE15-11A
|
Part 3. Field settings
2. Wired remote controller BRC2/3E52
Page 24
23/09/16
VRV4 indoor units
7. Press the Menu/Enter button. The
confirmation screen is displayed.
8. Select Yes and press the Menu/Enter
button. The settings are saved and the
Field settings screen returns.
9. When multiple settings need to be
changed, repeat step "3" to "8".
10. After all changes are completed, press
the Cancel button twice.
11. The backlight goes out and "Checking
the connection. Please stand by" is
displayed during initialization. After the
initialization, the Basic screen returns.
12. Disable the Menu/Enter and Cancel
button when no other settings need to
be changed. To disable, refer to
page 22
.
C
AUTION
• When an optional accessory is installed on the indoor unit, the settings of the indoor unit may be changed. See the
manual of the optional accessory.
• For the details on the field settings of the indoor unit, see the installation manual attached to the indoor unit.
• The outdoor unit field settings can only be configured on the outdoor PCB. Refer to the installation manual attached
to the outdoor unit.
N
OTE
• Though the configuration is performed for the whole group, set the Mode No. in parenthesis when performing an
individual configuration per indoor unit or when checking after the configuration is finished.
• The SECOND CODE NO. at factory shipment depends on the indoor unit model. Default values can be found in the
respective Service Manual of the respective units.
For the following settings, the value is the same for all indoor units.
• Thermostat sensor used for the "Auto" operation mode and the Setback function (room temperature on detailed
display): "02".
• Setback function: "04"
• External input B1: "02"
• External input B2: "02"
• Functions which are unavailable for the connected indoor unit(s) are not displayed.
No
Yes
Field Settings
Save the settings?
Setting
Return
Press the Menu/Enter button.
<Field settings>
7.
8.