ESIE15-11A
|
Part 2. Troubleshooting
2. Error code based troubleshooting
Page 18
23/09/16
VRV4 indoor units
2. Error code based troubleshooting
Error code
Main
Sub
Status outdoor
Reset
Cause
Solution
A0
-
Thermo off O
Power
off/on
Fault board
Check setting 22-1-3: T1-T2 NC.
If correct, indoor board fault.
A1
-
Thermo off O
Power
off/on
Fault Eeprom
Replace board.
A3
-
Cool thermo off
Auto
recovery
Float switch open
during thermo on
(cooling)
Check float switch status, drain
pipe no blockage, drain pipe raiser
< 600 mm.
A6
01
Thermo off
BRC1..
Fan motor locked
Rpm counter no signal from motor
to indoor main board when output.
10
Thermo off
BRC1..
Fan motor overcurrent
Check motor power circuit.
Replace fan motor / indoor board.
11
Thermo off
BRC1..
Fan motor locked
Rpm counter no signal at off
condition.
A7
-
Warning
BRC1..
Off/on
No detection contact
swingmotor
Check swing motor run when
output 230VAC.
Check contact position detection
open & close.
A9
01
Thermo off O
Power
off/on
EV motor fault
detection
Check signal board to expansion
valve.
02
Thermo off O
Power
off/on
EV body leakage
Check temperature coil sensor at
close EV cooling other indoor
AF
Thermo off
BRC1..
Float switch open
during thermo off
Check for drain water returning
from other indoor, expansion valve
correct closing thermo off.
AH
03
Warning
BRC1..
Communication error
main PCB / self
cleaning PCB
Check wire harness connections.
04
Warning
BRC1..
Dust detection sensor
error
Check wire harness connections.
05
Warning
BRC1..
Dust collection error
Check for clogging by dust
between brush-arm and dust
collector box.
06
Warning
BRC1..
Air filter rotation error
Check rotation mechanism air
filter.
07
Warning
BRC1..
Damper rotation error
Check rotation mechanism
damper.
08
Warning
BRC1..
Filter cleaning time
error
Filter auto cleaning program could
not be performed 24 hr operation.
09
Warning
BRC1..
Auto self cleaning
disabled
Check field settings to enable auto
filter cleaning.
AJ
01
Thermo off
Auto
recovery
Capacity adaptor
missing
Add corresponding capacity
adaptor onto spare part PCB
02
Thermo off
Power
reset
Incorrect expansion
valve motor
Use correct expansion valve
motor (between gear type and
direct drive).
C1
01
Thermo off
Auto
recovery
Communication error
main PCB / inverter
PCB fan motor
Check for communication between
main PCB and inverter PCB fan
motor.
02
Thermo off
Auto
recovery
Communication error
main PCB / auxiliary
PCB
Check for communication between
main PCB and inverter PCB fan
motor.