![background image](http://html1.mh-extra.com/html/daikin/super-multi-plus-e-series/super-multi-plus-e-series_service-manual_3601835370.webp)
Troubleshooting for BP Unit
SiEN18-622
358
Troubleshooting
6.6
Check
6.6.1 Power Supply Waveforms Check
Check No.14
Measure the power supply waveform between pins 1 and 3 on the terminal board, and check
the waveform disturbance.
Check to see if the power supply waveform is a sine wave (Fig.1).
Check to see if there is waveform disturbance near the zero cross (sections circled in Fig.2)
[Fig.1]
[Fig.2]