SiEN18-622
Indoor Unit (RA Models)
Function
121
7.3
Programme Dry Function
Programme dry function removes humidity while preventing the room temperature from
lowering.
Since the microcomputer controls both the temperature and air flow volume, the temperature
adjustment and fan adjustment buttons are inoperable in this mode.
In Case of
Inverter Units
The microcomputer automatically sets the temperature and fan settings. The difference
between the room temperature at startup and the temperature set by the microcomputer is
divided into two zones. Then, the unit operates in the dry mode with an appropriate capacity for
each zone to maintain the temperature and humidity at a comfortable level.
Room temperature at
startup
Temperature (ON point)
at which operation starts
Frequency switching
point
Temperature difference
for operation stop
24°C
Room temperature at
startup
0.5°C
1.5°C
18°C
18°C
1.0°C
17°C
—
0.5°C
LHz
LHz
LHz
*
55Hz
*
55Hz
LHz indic
a
te
s
low fre
qu
ency. Item m
a
rked with v
a
rie
s
depending on model
s
.
ON point
OFF point
5 min
5 min
Compre
ss
or
control
S
top
S
top
S
top
S
top
S
top
S
top
Indoor
u
nit f
a
n
Extr
a
-low
a
ir flow
Extr
a
-low
a
ir flow
Low
a
ir flow
Low
a
ir flow
(R1
3
59)
Fre
qu
ency
s
witching
point
Summary of Contents for Super Multi Plus E-Series
Page 1: ...SiEN18 622 E Series Service Manual Applied Models zSuper Multi Plus Cooling Only Heat Pump...
Page 105: ...Refrigerant Flow for Each Operation Mode SiEN18 622 92 Refrigerant Circuit...
Page 157: ...Indoor Unit SkyAir Models SiEN18 622 144 Function...
Page 312: ...SiEN18 622 Ceiling Mounted Cassette Type System Configuration 300...
Page 424: ...Method of Replacing The Inverter s Power Transistors Modules SiEN18 622 412 Troubleshooting...
Page 446: ...Wiring Diagrams SiEN18 622 434 Appendix...
Page 452: ...SiEN18 622 vi Index...