![Daikin Super Multi Plus E-Series Service Manual Download Page 37](http://html1.mh-extra.com/html/daikin/super-multi-plus-e-series/super-multi-plus-e-series_service-manual_3601835037.webp)
Specifications
SiEN18-622
24
Specifications
50Hz 220-230-240V / 60Hz 220-230V
50Hz 240V
Model
FTKS60FVMA
FTKS71FVMA
Rated Capacity
6.0kW Class
7.1kW Class
Front Panel Color
White
White
Air Flow Rates
m³/min
(cfm)
H
16.2 (572)
17.4 (614)
M
13.9 (491)
14.6 (516)
L
11.5 (406)
11.9 (420)
SL
10.0 (353)
11.2 (395)
Fan
Type
Cross Flow Fan
Cross Flow Fan
Motor Output
W
43
43
Speed
Steps
5 Steps, Silent, Auto
5 Steps, Silent, Auto
Air Direction Control
Right, Left, Horizontal, Downward
Right, Left, Horizontal, Downward
Air Filter
Removable-Washable-Mildew Proof
Removable-Washable-Mildew Proof
Running Current (Rated)
A
0.19-0.18-0.17/0.19-0.18
0.21-0.20-0.19/0.21-0.20
Power Consumption (Rated)
W
40
45
Power Factor
%
95.7-96.6-98.0/95.7-96.6
97.4-97.8-98.7/97.4-97.8
Temperature Control
Microcomputer Control
Microcomputer Control
Dimensions (H×W×D)
mm
290×1,050×238
290×1,050×238
Packaged Dimensions (H×W×D)
mm
337×1,147×366
337×1,147×366
Weight
kg
12
12
Gross Weight
kg
17
17
Operation
Sound
H/M/L/SL
dBA
45/41/36/33
46/42/37/34
Sound Power
H
dBA
61
62
Heat Insulation
Both Liquid and Gas Pipes
Both Liquid and Gas Pipes
Piping Connection
Liquid
mm
φ
6.4
φ
6.4
Gas
mm
φ
12.7
φ
15.9
Drain
mm
φ
18.0
φ
18.0
Drawing No.
3D054877
3D054878
Model
FTKS50BVMA8
FTKS60BVMA8
Rated Capacity
5.0kW Class
6.0kW Class
Front Panel Color
White
White
Air Flow Rates
m³/min
(cfm)
H
11.4 (402)
16.2 (573)
M
9.8 (346)
13.9 (490)
L
8.7 (306)
11.9 (420)
SL
7.7 (271)
10.7 (378)
Fan
Type
Cross Flow Fan
Cross Flow Fan
Motor Output
W
40
43
Speed
Steps
5 Steps, Silent, Auto
5 Steps, Silent, Auto
Air Direction Control
Right, Left, Horizontal, Downward
Right, Left, Horizontal, Downward
Air Filter
Removable-Washable-Mildew Proof
Removable-Washable-Mildew Proof
Running Current (Rated)
A
0.17
0.19
Power Consumption (Rated)
W
40
45
Power Factor
%
98
98.7
Temperature Control
Microcomputer Control
Microcomputer Control
Dimensions (H×W×D)
mm
290×795×238
290×1,050×238
Packaged Dimensions (H×W×D)
mm
280×840×338
337×1,147×366
Weight
kg
9
12
Gross Weight
kg
13
17
Operation
Sound
H/M/L/SL
dBA
44/40/35/32
45/41/36/33
Sound Power
H
dBA
63
63
Heat Insulation
Both Liquid and Gas Pipes
Both Liquid and Gas Pipes
Piping Connection
Liquid
mm
φ
6.4
φ
6.4
Gas
mm
φ
12.7
φ
12.7
Drain
mm
φ
18.0
φ
18.0
Drawing No.s
3D047569
3D047570
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Summary of Contents for Super Multi Plus E-Series
Page 1: ...SiEN18 622 E Series Service Manual Applied Models zSuper Multi Plus Cooling Only Heat Pump...
Page 105: ...Refrigerant Flow for Each Operation Mode SiEN18 622 92 Refrigerant Circuit...
Page 157: ...Indoor Unit SkyAir Models SiEN18 622 144 Function...
Page 312: ...SiEN18 622 Ceiling Mounted Cassette Type System Configuration 300...
Page 424: ...Method of Replacing The Inverter s Power Transistors Modules SiEN18 622 412 Troubleshooting...
Page 446: ...Wiring Diagrams SiEN18 622 434 Appendix...
Page 452: ...SiEN18 622 vi Index...