Troubleshooting for Outdoor Unit
SiEN18-622
378
Troubleshooting
7.17 Malfunction of PCB
Remote Control
Display
L1
Applicable
Models
AII outdoor unit models
Method of
Malfunction
Detection
Detect malfunctions by current value during waveform output before compressor startup.
Detect malfunctions by current sensor value during synchronized operation at the time of
startup.
Detect malfunctions using an SP-PAM series capacitor overvoltage sensor.
Malfunction
Decision
Conditions
In case of overcurrent (OCP) during waveform output
When the current sensor malfunctions during synchronized operation
When overvoltage occurs in SP-PAM
In case of IGBT malfunction
Supposed
Causes
Faulty outdoor PCB (A1P)
•
IPM failure
•
Current sensor failure
•
SP-PAM failure
•
Failure of IGBT or drive circuit
Troubleshooting
YES
NO
Turn OFF the power
supply once and then turn
it ON again.
Does
it return normally?
It is believed that
external factors (noise,
etc.) other than failure
caused the malfunction.
Replace the outdoor PC
board (A1P).
PC board equipped with
a resin case
( )
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for Super Multi Plus E-Series
Page 1: ...SiEN18 622 E Series Service Manual Applied Models zSuper Multi Plus Cooling Only Heat Pump...
Page 105: ...Refrigerant Flow for Each Operation Mode SiEN18 622 92 Refrigerant Circuit...
Page 157: ...Indoor Unit SkyAir Models SiEN18 622 144 Function...
Page 312: ...SiEN18 622 Ceiling Mounted Cassette Type System Configuration 300...
Page 424: ...Method of Replacing The Inverter s Power Transistors Modules SiEN18 622 412 Troubleshooting...
Page 446: ...Wiring Diagrams SiEN18 622 434 Appendix...
Page 452: ...SiEN18 622 vi Index...