background image

4 Installation

Installation manual

8

RZQG71~Y1 + RZQSG100~Y1

Split system air conditioners

4P385521-1C – 2019.04

If the pressure…

Then…

Does not change

There is no moisture in the
system. This procedure is
finished.

Increases

There is moisture in the
system. Go to the next step.

3

Vacuum the system for at least 2 hours to a manifold pressure
of −0.1 MPa (−1 bar).

4

After  turning  the  pump  OFF,  check  the  pressure  for  at  least
1 hour.

5

If  you  do  NOT  reach  the  target  vacuum  or  CANNOT  maintain
the vacuum for 1 hour, do the following:

▪ Check for leaks again.
▪ Perform vacuum drying again.

NOTICE

Make  sure  to  open  the  stop  valves  after  installing  the
refrigerant  piping  and  performing  vacuum  drying.  Running
the  system  with  the  stop  valves  closed  may  break  the
compressor.

4.4

Charging refrigerant

4.4.1

Definitions: L1~L7, H1, H2

Pair

(a)

H1

L1

Twin

(a)

H1

H2

L1

L2

L3

Triple

(a)

L2

L3

L4

H1

H2

L1

Double twin

(a)

H1

H2

L1

L2

L3

L4

L5

L6

L7

(a)

Assume that the longest line in the illustration corresponds
with the actual longest pipe, and the highest unit in the
illustration corresponds with the actual highest unit.

L1

Main piping

L2~L7

Branch piping

H1

Height difference between the highest indoor unit and the
outdoor unit

H2

Height difference between the highest and the lowest
indoor unit
Refrigerant branch kit

4.4.2

To determine the additional refrigerant
amount

To determine if adding additional refrigerant is necessary

If

Then

(L1+L2+L3+L4+L5+L6+L7)≤
chargeless length

Chargeless length=

▪ 10 m (size‑down)

▪ 30 m (standard)

▪ 15 m (size‑up)

You do not have to add
additional refrigerant.

(L1+L2+L3+L4+L5+L6+L7)>
chargeless length

You must add additional
refrigerant.

For future servicing, encircle the
selected amount in the tables
below.

INFORMATION

Piping length is the largest one-way length of liquid piping.

To determine the additional refrigerant amount (R in kg) (in
case of pair)

L1 (m)

L1 (standard): 30~40 m 40~50 m 50~60 m

(a)

60~75 m

(a)

L1 (size-up): 15~20 m 20~25 m 25~30 m

(a)

30~35 m

(a)

R:

0.5 kg

1.0 kg

1.5 kg

2.0 kg

(a)

Only for RZQG100~140.

To determine the additional refrigerant amount (R in kg) (in
case of twin, triple and double twin)

1

Determine G1 and G2.

G1 (m)

Total length of <x> liquid piping

x=

Ø9.5 mm

 (standard)

x=

Ø12.7 mm

 (size‑up)

G2 (m)

Total length of 

Ø6.4

 mm liquid piping

2

Determine R1 and R2.

If

Then

G1>30 m

(a)

Use the table below to determine
R1 (length=

G1−30 m

)

(a)

 and R2

(length=

G2

).

G1≤30 m

(a)

(and G1+G2>30 m)

(a)

R1=0.0 kg.

Use the table below to determine
R2 (length=

G1+G2−30 m

)

(a)

.

(a)

In case of size‑up: Replace 30 m by 15 m.

In case of 

standard

 liquid pipe size:

Length

0~10 m

10~20 m

20~30 m

(a)

30~45 m

(a)

R1:

0.5 kg

1.0 kg

1.5 kg

2.0 kg

R2:

0.3 kg

0.6 kg

0.9 kg

1.2 kg

In case of 

size‑up

 liquid pipe size:

Length

0~5 m

5~10 m

10~15 m

(a)

15~20 m

(a)

R1, R2:

0.5 kg

1.0 kg

1.5 kg

2.0 kg

(a)

Only for RZQG100~140.

3

Determine the additional refrigerant amount: R=R1+R2.

Summary of Contents for SkyAir RZQG140L7Y1B

Page 1: ...rs English Installation manual Split system air conditioners RZQG71L9V1B RZQG100L9V1B RZQG125L9V1B RZQG140L9V1B RZQG71L8Y1B RZQG100L8Y1B RZQG125L8Y1B RZQG140L7Y1B RZQSG100L9V1B RZQSG125L9V1B RZQSG140L...

Page 2: ...1000 1000 500 HD HU HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB H...

Page 3: ...aslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse...

Page 4: ...missioning 12 5 1 Checklist before commissioning 12 5 2 To perform a test run 12 5 3 Error codes when performing a test run 13 5 4 Dedicated field settings for technical cooling 13 6 Disposal 13 7 Tec...

Page 5: ...FORMATION The recommended height of the upper protruding part of the bolts is 20 mm 20 NOTICE Fix the outdoor unit to the foundation bolts using nuts with resin washers a If the coating on the fasteni...

Page 6: ...kout hole a in the bottom plate or cover plate by tapping on the attachment points with a flat head screwdriver and a hammer Optionally cut out the slits b with a metal saw NOTICE Precautions when mak...

Page 7: ...ressure gauge b Nitrogen c Refrigerant d Weighing machine e Vacuum pump f Stop valve g Main piping h Refrigerant branch kit i Branch piping 4 3 2 To check for leaks NOTICE Do NOT exceed the unit s max...

Page 8: ...o determine the additional refrigerant amount To determine if adding additional refrigerant is necessary If Then L1 L2 L3 L4 L5 L6 L7 chargeless length Chargeless length 10 m size down 30 m standard 1...

Page 9: ...on page 7 4 4 5 To charge additional refrigerant WARNING Only use R410A as refrigerant Other substances may cause explosions and accidents R410A contains fluorinated greenhouse gases Its global warmi...

Page 10: ...nt is connected only to a supply with a short circuit power Ssc greater than or equal to the minimum Ssc value Model Minimum Ssc value RZQG100 140_Y1 RZQSG140_Y1 1170 kVA a a This is the most stringen...

Page 11: ...G insertions can be inserted at the knockout hole When you do not use a wire conduit protect the wires with vinyl tubes to prevent the edge of the knockout hole from cutting the wires a b c d e A B A...

Page 12: ...operly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matc...

Page 13: ...d E7 There is a missing phase in case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three electrical wires L4 The air...

Page 14: ...ed air from flowing back to the suction side through the bottom of the unit 2 Maximum two units can be installed Not allowed Multiple rows of units See figure 2 on the inside of the front cover Stacke...

Page 15: ...2U Fuse F6U Fuse T 3 15 A 250 V F7U F8U Fuse F 1 0 A 250 V F1U F8U RZQG100 140_V1 RZQSG125 140_V1 F1U F4U Fuse F6U Fuse T 5 0 A 250 V F7U F8U Fuse F 1 0 A 250 V F1U F8U RZQ S G_Y1 F1U F2U Fuse 31 5 A...

Page 16: ...ical data Installation manual 16 RZQG71 140L_V1 Y1 RZQSG100 140L_V1 Y1 Split system air conditioners 4P385521 1C 2019 04 Colours BLK Black BLU Blue BRN Brown GRN Green ORG Orange RED Red WHT White YLW...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...4P385521 1C 2019 04 Copyright 2014 Daikin 4P385521 1 B 0000000 4P385521 1 C 0000000...

Reviews: