4 Installation

Installation manual

10

RZQG71~Y1 + RZQSG100~Y1

Split system air conditioners

4P385521-1C – 2019.04

CAUTION

For  use  of  units  in  applications  with  temperature  alarm
settings  it  is  recommended  to  foresee  a  delay  of  10
minutes  for  signalling  the  alarm  in  case  the  alarm
temperature  is  exceeded.  The  unit  may  stop  for  several
minutes during normal operation for "defrosting the unit", or
when in "thermostat stop" operation.

4.5.1

About electrical compliance

RZQ(S)G_V1 + R125_Y1

Equipment  complying  with  EN/IEC  61000‑3‑12  (European/
International  Technical  Standard  setting  the  limits  for  harmonic
currents  produced  by  equipment  connected  to  public  low-voltage
systems with input current >16 A and ≤75 A per phase.).

RZQG100~ RZQSG140_Y1

Equipment complying with:

EN/IEC  61000‑3‑12

  provided  that  the  short-circuit  power  S

sc

  is

greater  than  or  equal  to  the  minimum  S

sc

  value  at  the  interface

point between the user's supply and the public system.

▪ EN/IEC 

61000‑3‑12 

European/International 

Technical

Standard  setting  the  limits  for  harmonic  currents  produced  by
equipment  connected  to  public  low-voltage  systems  with  input
current >16 A and ≤75 A per phase.

▪ It is the responsibility of the installer or user of the equipment to

ensure, by consultation with the distribution network operator if
necessary,  that  the  equipment  is  connected  only  to  a  supply
with  a  short-circuit  power  S

sc

  greater  than  or  equal  to  the

minimum S

sc

 value.

Model

Minimum S

sc

 value

RZQG100~ RZQSG140_Y1

1170 kVA

(a)

(a)

This is the most stringent value. For specific product data,
see the databooks.

4.5.2

Specifications of standard wiring components

Component

RZQG

RZQSG

V1

Y1

V1

Y1

71

100

125+140

71

100

125+140

100

125+140

100

125

140

Power supply cable MCA

(a)

20.6 A

32.0 A

33.5 A

14.0 A

21.0 A

22.5 A

32.0 A

33.5 A

17.7 A

19.2 A

22.5 A

Voltage

230 V

400 V

230 V

400 V

Phase

1~

3N~

1~

3N~

Frequency

50 Hz

Wire sizes

Must comply with applicable legislation

Interconnection cables

Minimum cable section of 2.5 mm² and applicable for 230 V

Recommended field fuse

25 A

40 A

16 A

25 A

40 A

20 A

25 A

Earth leakage circuit breaker

Must comply with applicable legislation

(a)

MCA=Minimum circuit ampacity. Stated values are maximum values (see electrical data of combination with indoor units for exact values).

4.5.3

To connect the electrical wiring on the
outdoor unit

NOTICE

▪ Follow  the  wiring  diagram  (delivered  with  the  unit,

located at the inside of the service cover).

▪ Make  sure  the  electrical  wiring  does  NOT  obstruct

proper reattachment of the service cover.

1

Remove the service cover.

2

Connect  the  interconnection  cables  and  power  supply  as
follows:

c

a

d

e

1~ 50 Hz

220-240 V

3N~ 50 Hz

380-415 V

V1

Y1

L1 L2 L3

L1 L2 L3

N

b

b

a

a

a

I, II, III, IV

Pair, twin, triple, double twin

M, S

Master, slave

a

Interconnection cables

b

Power supply cable

c

Earth leakage circuit breaker

d

Fuse

e

User interface

Summary of Contents for SkyAir RZQG140L7Y1B

Page 1: ...rs English Installation manual Split system air conditioners RZQG71L9V1B RZQG100L9V1B RZQG125L9V1B RZQG140L9V1B RZQG71L8Y1B RZQG100L8Y1B RZQG125L8Y1B RZQG140L7Y1B RZQSG100L9V1B RZQSG125L9V1B RZQSG140L...

Page 2: ...1000 1000 500 HD HU HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB H...

Page 3: ...aslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse...

Page 4: ...missioning 12 5 1 Checklist before commissioning 12 5 2 To perform a test run 12 5 3 Error codes when performing a test run 13 5 4 Dedicated field settings for technical cooling 13 6 Disposal 13 7 Tec...

Page 5: ...FORMATION The recommended height of the upper protruding part of the bolts is 20 mm 20 NOTICE Fix the outdoor unit to the foundation bolts using nuts with resin washers a If the coating on the fasteni...

Page 6: ...kout hole a in the bottom plate or cover plate by tapping on the attachment points with a flat head screwdriver and a hammer Optionally cut out the slits b with a metal saw NOTICE Precautions when mak...

Page 7: ...ressure gauge b Nitrogen c Refrigerant d Weighing machine e Vacuum pump f Stop valve g Main piping h Refrigerant branch kit i Branch piping 4 3 2 To check for leaks NOTICE Do NOT exceed the unit s max...

Page 8: ...o determine the additional refrigerant amount To determine if adding additional refrigerant is necessary If Then L1 L2 L3 L4 L5 L6 L7 chargeless length Chargeless length 10 m size down 30 m standard 1...

Page 9: ...on page 7 4 4 5 To charge additional refrigerant WARNING Only use R410A as refrigerant Other substances may cause explosions and accidents R410A contains fluorinated greenhouse gases Its global warmi...

Page 10: ...nt is connected only to a supply with a short circuit power Ssc greater than or equal to the minimum Ssc value Model Minimum Ssc value RZQG100 140_Y1 RZQSG140_Y1 1170 kVA a a This is the most stringen...

Page 11: ...G insertions can be inserted at the knockout hole When you do not use a wire conduit protect the wires with vinyl tubes to prevent the edge of the knockout hole from cutting the wires a b c d e A B A...

Page 12: ...operly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matc...

Page 13: ...d E7 There is a missing phase in case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three electrical wires L4 The air...

Page 14: ...ed air from flowing back to the suction side through the bottom of the unit 2 Maximum two units can be installed Not allowed Multiple rows of units See figure 2 on the inside of the front cover Stacke...

Page 15: ...2U Fuse F6U Fuse T 3 15 A 250 V F7U F8U Fuse F 1 0 A 250 V F1U F8U RZQG100 140_V1 RZQSG125 140_V1 F1U F4U Fuse F6U Fuse T 5 0 A 250 V F7U F8U Fuse F 1 0 A 250 V F1U F8U RZQ S G_Y1 F1U F2U Fuse 31 5 A...

Page 16: ...ical data Installation manual 16 RZQG71 140L_V1 Y1 RZQSG100 140L_V1 Y1 Split system air conditioners 4P385521 1C 2019 04 Colours BLK Black BLU Blue BRN Brown GRN Green ORG Orange RED Red WHT White YLW...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...4P385521 1C 2019 04 Copyright 2014 Daikin 4P385521 1 B 0000000 4P385521 1 C 0000000...

Reviews: