4 Installation

Installation manual

11

RZQG71~Y1 + RZQSG100~Y1
Split system air conditioners
4P385521-1C – 2019.04

a

b

V1

Y1

c

c

c

c

d

d

e

e

f

f

a

Switch box

b

Stop valve attachment plate

c

Earth

d

Cable tie

e

Interconnection cable

f

Power supply cable

3

Fix the cables (power supply and interconnection cable) with a
cable tie to the stop valve attachment plate and route the wiring
according to the illustration above.

4

Choose  a  knockout  hole  and  remove  the  knockout  hole  by
tapping  on  the  attachment  points  with  a  flat  head  screwdriver
and a hammer.

5

Route  the  wiring  through  the  frame  and  connect  the  wiring  to
the frame at the knockout hole.

Routing through
the frame

Choose one of the 3 possibilities:

a

b

a

b

a

b

2

3

1

a

 Power supply cable

b

 Interconnection cable

Connecting to the
frame

When cables are routed from the unit, a
protection sleeve for the conduits (PG
insertions) can be inserted at the knockout
hole.

When you do not use a wire conduit,
protect the wires with vinyl tubes to
prevent the edge of the knockout hole from
cutting the wires.

a b c

d

e

A B

A

 Inside of the outdoor unit

B

 Outside of the outdoor unit

a

 Wire

b

 Bush

c

 Nut

d

 Frame

e

 Hose

NOTICE

Precautions when making knockout holes:

▪ Avoid damaging the casing and underlying piping.

▪ After  making  the  knockout  holes,  we  recommend  to

remove  the  burrs  and  paint  the  edges  and  areas
around the edges using repair paint to prevent rusting.

▪ When  passing  electrical  wiring  through  the  knockout

holes,  wrap  the  wiring  with  protective  tape  to  prevent
damage.

6

Reattach the service cover.

7

Connect an earth leakage circuit breaker and fuse to the power
supply line.

4.6

Finishing the outdoor unit
installation

4.6.1

To finish the outdoor unit installation

1

Insulate and fix the refrigerant piping and interconnection cable
as follows:

f

b

a

e

d

c

a

Gas pipe

b

Gas pipe insulation

c

Interconnection cable

d

Liquid pipe

e

Liquid pipe insulation

f

Finishing tape

2

Install the service cover.

Summary of Contents for SkyAir RZQG140L7Y1B

Page 1: ...rs English Installation manual Split system air conditioners RZQG71L9V1B RZQG100L9V1B RZQG125L9V1B RZQG140L9V1B RZQG71L8Y1B RZQG100L8Y1B RZQG125L8Y1B RZQG140L7Y1B RZQSG100L9V1B RZQSG125L9V1B RZQSG140L...

Page 2: ...1000 1000 500 HD HU HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB H...

Page 3: ...aslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse...

Page 4: ...missioning 12 5 1 Checklist before commissioning 12 5 2 To perform a test run 12 5 3 Error codes when performing a test run 13 5 4 Dedicated field settings for technical cooling 13 6 Disposal 13 7 Tec...

Page 5: ...FORMATION The recommended height of the upper protruding part of the bolts is 20 mm 20 NOTICE Fix the outdoor unit to the foundation bolts using nuts with resin washers a If the coating on the fasteni...

Page 6: ...kout hole a in the bottom plate or cover plate by tapping on the attachment points with a flat head screwdriver and a hammer Optionally cut out the slits b with a metal saw NOTICE Precautions when mak...

Page 7: ...ressure gauge b Nitrogen c Refrigerant d Weighing machine e Vacuum pump f Stop valve g Main piping h Refrigerant branch kit i Branch piping 4 3 2 To check for leaks NOTICE Do NOT exceed the unit s max...

Page 8: ...o determine the additional refrigerant amount To determine if adding additional refrigerant is necessary If Then L1 L2 L3 L4 L5 L6 L7 chargeless length Chargeless length 10 m size down 30 m standard 1...

Page 9: ...on page 7 4 4 5 To charge additional refrigerant WARNING Only use R410A as refrigerant Other substances may cause explosions and accidents R410A contains fluorinated greenhouse gases Its global warmi...

Page 10: ...nt is connected only to a supply with a short circuit power Ssc greater than or equal to the minimum Ssc value Model Minimum Ssc value RZQG100 140_Y1 RZQSG140_Y1 1170 kVA a a This is the most stringen...

Page 11: ...G insertions can be inserted at the knockout hole When you do not use a wire conduit protect the wires with vinyl tubes to prevent the edge of the knockout hole from cutting the wires a b c d e A B A...

Page 12: ...operly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matc...

Page 13: ...d E7 There is a missing phase in case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three electrical wires L4 The air...

Page 14: ...ed air from flowing back to the suction side through the bottom of the unit 2 Maximum two units can be installed Not allowed Multiple rows of units See figure 2 on the inside of the front cover Stacke...

Page 15: ...2U Fuse F6U Fuse T 3 15 A 250 V F7U F8U Fuse F 1 0 A 250 V F1U F8U RZQG100 140_V1 RZQSG125 140_V1 F1U F4U Fuse F6U Fuse T 5 0 A 250 V F7U F8U Fuse F 1 0 A 250 V F1U F8U RZQ S G_Y1 F1U F2U Fuse 31 5 A...

Page 16: ...ical data Installation manual 16 RZQG71 140L_V1 Y1 RZQSG100 140L_V1 Y1 Split system air conditioners 4P385521 1C 2019 04 Colours BLK Black BLU Blue BRN Brown GRN Green ORG Orange RED Red WHT White YLW...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...4P385521 1C 2019 04 Copyright 2014 Daikin 4P385521 1 B 0000000 4P385521 1 C 0000000...

Reviews: