7 Technical data

Installation manual

14

RZQG71~Y1 + RZQSG100~Y1

Split system air conditioners

4P385521-1C – 2019.04

7

Technical data

subset

  of  the  latest  technical  data  is  available  on  the  regional  Daikin  website  (publicly  accessible).  The 

full  set

  of  latest  technical  data  is

available on the Daikin Business Portal (authentication required).

7.1

Service space: Outdoor unit

Suction side

In the illustrations below, the service space at the suction side is based on 35°C DB and cooling operation. Foresee
more space in the following cases:

▪ When the suction side temperature regularly exceeds this temperature.

▪ When the heat load of the outdoor units is expected to regularly exceed the maximum operating capacity.

Discharge side

Take refrigerant piping work into account when positioning the units. If your layout does not match with any of the
layouts below, contact your dealer.

Single unit (

) | Single row of units (

)

See figure 1 on the inside of the front cover.

A,B,C,D

Obstacles (walls/baffle plates)

E

Obstacle (roof)

a,b,c,d,e

Minimum service space between the unit and obstacles A, B, C, D and E

e

B

Maximum distance between the unit and the edge of obstacle E, in the direction of obstacle B

e

D

Maximum distance between the unit and the edge of obstacle E, in the direction of obstacle D

H

U

Height of the unit

H

B

,H

D

Height of obstacles B and D

1

Seal the bottom of the installation frame to prevent discharged air from flowing back to the suction side through the bottom of the unit.

2

Maximum two units can be installed.
Not allowed

Multiple rows of units (

)

See figure 2 on the inside of the front cover.

Stacked units (max. 2 levels) (

)

See figure 3 on the inside of the front cover.

A1=>A2

(A1) If there is danger of drainage dripping and freezing between the upper and lower units…
(A2) Then install a 

roof

 between the upper and lower units. Install the upper unit high enough above the lower unit to prevent ice buildup at the

upper unit's bottom plate.

B1=>B2

(B1) If there is no danger of drainage dripping and freezing between the upper and lower units…
(B2) Then it is not required to install a roof, but 

seal the gap

 between the upper and lower units to prevent discharged air from flowing back to the

suction side through the bottom of the unit.

7.2

Piping diagram: Outdoor unit

R2T

R4T

R6T

R1T

e

d

i

j

h

g

f

a

c

c

b

e

Y1E

Y1S

M1F-M2F

M1C

S1PL

S1PH

R5T

R3T

a

Field piping (liquid: Ø9.5 flare connection)

b

Field piping (gas: Ø15.9 flare connection)

c

Stop valve (with service port 5/16")

d

Accumulator

e

Filter

f

Heat exchanger

g

Internal service port 5/16"

h

Switch box cooling (only for RZQ(S)G_V1)

i

Compressor accumulator

j

Check valve (only for RZQG71, RZQSG100 and
RZQSG125)

M1C

Motor (compressor)

M1F‑M2F

Motor (upper and lower fan)

R1T

Thermistor (air)

R2T

Thermistor (discharge)

R3T

Thermistor (suction)

R4T

Thermistor (heat exchanger)

R5T

Thermistor (heat exchanger middle)

R6T

Thermistor (liquid)

S1PH

High pressure switch

S1PL

Low pressure switch (only for RZQ(S)G_V1)

Y1E

Electronic expansion valve

Y1S

Solenoid valve (4‑way valve)
Heating
Cooling

Summary of Contents for SkyAir RZQG140L7Y1B

Page 1: ...rs English Installation manual Split system air conditioners RZQG71L9V1B RZQG100L9V1B RZQG125L9V1B RZQG140L9V1B RZQG71L8Y1B RZQG100L8Y1B RZQG125L8Y1B RZQG140L7Y1B RZQSG100L9V1B RZQSG125L9V1B RZQSG140L...

Page 2: ...1000 1000 500 HD HU HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB H...

Page 3: ...aslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse...

Page 4: ...missioning 12 5 1 Checklist before commissioning 12 5 2 To perform a test run 12 5 3 Error codes when performing a test run 13 5 4 Dedicated field settings for technical cooling 13 6 Disposal 13 7 Tec...

Page 5: ...FORMATION The recommended height of the upper protruding part of the bolts is 20 mm 20 NOTICE Fix the outdoor unit to the foundation bolts using nuts with resin washers a If the coating on the fasteni...

Page 6: ...kout hole a in the bottom plate or cover plate by tapping on the attachment points with a flat head screwdriver and a hammer Optionally cut out the slits b with a metal saw NOTICE Precautions when mak...

Page 7: ...ressure gauge b Nitrogen c Refrigerant d Weighing machine e Vacuum pump f Stop valve g Main piping h Refrigerant branch kit i Branch piping 4 3 2 To check for leaks NOTICE Do NOT exceed the unit s max...

Page 8: ...o determine the additional refrigerant amount To determine if adding additional refrigerant is necessary If Then L1 L2 L3 L4 L5 L6 L7 chargeless length Chargeless length 10 m size down 30 m standard 1...

Page 9: ...on page 7 4 4 5 To charge additional refrigerant WARNING Only use R410A as refrigerant Other substances may cause explosions and accidents R410A contains fluorinated greenhouse gases Its global warmi...

Page 10: ...nt is connected only to a supply with a short circuit power Ssc greater than or equal to the minimum Ssc value Model Minimum Ssc value RZQG100 140_Y1 RZQSG140_Y1 1170 kVA a a This is the most stringen...

Page 11: ...G insertions can be inserted at the knockout hole When you do not use a wire conduit protect the wires with vinyl tubes to prevent the edge of the knockout hole from cutting the wires a b c d e A B A...

Page 12: ...operly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matc...

Page 13: ...d E7 There is a missing phase in case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three electrical wires L4 The air...

Page 14: ...ed air from flowing back to the suction side through the bottom of the unit 2 Maximum two units can be installed Not allowed Multiple rows of units See figure 2 on the inside of the front cover Stacke...

Page 15: ...2U Fuse F6U Fuse T 3 15 A 250 V F7U F8U Fuse F 1 0 A 250 V F1U F8U RZQG100 140_V1 RZQSG125 140_V1 F1U F4U Fuse F6U Fuse T 5 0 A 250 V F7U F8U Fuse F 1 0 A 250 V F1U F8U RZQ S G_Y1 F1U F2U Fuse 31 5 A...

Page 16: ...ical data Installation manual 16 RZQG71 140L_V1 Y1 RZQSG100 140L_V1 Y1 Split system air conditioners 4P385521 1C 2019 04 Colours BLK Black BLU Blue BRN Brown GRN Green ORG Orange RED Red WHT White YLW...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...4P385521 1C 2019 04 Copyright 2014 Daikin 4P385521 1 B 0000000 4P385521 1 C 0000000...

Reviews: