4 Installation

Installation manual

7

RZQG71~Y1 + RZQSG100~Y1
Split system air conditioners
4P385521-1C – 2019.04

a

WARNING

Provide adequate measures to prevent that the unit can be
used  as  a  shelter  by  small  animals.  Small  animals  that
make contact with electrical parts can cause malfunctions,
smoke or fire.

NOTICE

Make  sure  to  open  the  stop  valves  after  installing  the
refrigerant  piping  and  performing  vacuum  drying.  Running
the  system  with  the  stop  valves  closed  may  break  the
compressor.

4.2.2

To determine if oil traps are required

If oil flows back into the outdoor unit's compressor, this might cause
liquid compression or deterioration of oil return. Oil traps in the rising
gas piping can prevent this.

If

Then

The indoor unit is installed
higher than the outdoor
unit

Install an oil trap every 10 m (height
difference).

a

b

10 m

a

 Rising gas piping with oil trap

b

 Liquid piping

The outdoor unit is
installed higher than the
indoor unit

Oil traps are NOT required.

4.3

Checking the refrigerant piping

4.3.1

Checking refrigerant piping: Setup

a

c

f

c

f

b

d

e h

g

i

a

b

A

B

d

e

R410A

R410A

A

Setup in case of pair

B

Setup in case of twin

a

Pressure gauge

b

Nitrogen

c

Refrigerant

d

Weighing machine

e

Vacuum pump

f

Stop valve

g

Main piping

h

Refrigerant branch kit

i

Branch piping

4.3.2

To check for leaks

NOTICE

Do NOT exceed the unit's maximum working pressure (see
"PS High" on the unit name plate).

NOTICE

Make  sure  to  use  a  recommended  bubble  test  solution
from  your  wholesaler.  Do  not  use  soap  water,  which  may
cause cracking of flare nuts (soap water may contain salt,
which  absorbs  moisture  that  will  freeze  when  the  piping
gets  cold),  and/or  lead  to  corrosion  of  flared  joints  (soap
water  may  contain  ammonia  which  causes  a  corrosive
effect between the brass flare nut and the copper flare).

1

Charge the system with nitrogen gas up to a gauge pressure of
at  least  200  kPa  (2  bar).  It  is  recommended  to  pressurize  to
3000 kPa (30 bar) in order to detect small leaks.

2

Check  for  leaks  by  applying  the  bubble  test  solution  to  all
connections.

3

Discharge all nitrogen gas.

4.3.3

To perform vacuum drying

NOTICE

▪ Connect  the  vacuum  pump  to 

both

  the  service  port  of

the  gas  stop  valve  and  the  service  port  of  the  liquid
stop valve to increase efficiency.

▪ Make sure that the gas stop valve and liquid stop valve

are  firmly  closed  before  performing  the  leak  test  or
vacuum drying.

1

Vacuum the system until the pressure on the manifold indicates
−0.1 MPa (−1 bar).

2

Leave as is for 4-5 minutes and check the pressure:

Summary of Contents for SkyAir RZQG140L7Y1B

Page 1: ...rs English Installation manual Split system air conditioners RZQG71L9V1B RZQG100L9V1B RZQG125L9V1B RZQG140L9V1B RZQG71L8Y1B RZQG100L8Y1B RZQG125L8Y1B RZQG140L7Y1B RZQSG100L9V1B RZQSG125L9V1B RZQSG140L...

Page 2: ...1000 1000 500 HD HU HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB H...

Page 3: ...aslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse...

Page 4: ...missioning 12 5 1 Checklist before commissioning 12 5 2 To perform a test run 12 5 3 Error codes when performing a test run 13 5 4 Dedicated field settings for technical cooling 13 6 Disposal 13 7 Tec...

Page 5: ...FORMATION The recommended height of the upper protruding part of the bolts is 20 mm 20 NOTICE Fix the outdoor unit to the foundation bolts using nuts with resin washers a If the coating on the fasteni...

Page 6: ...kout hole a in the bottom plate or cover plate by tapping on the attachment points with a flat head screwdriver and a hammer Optionally cut out the slits b with a metal saw NOTICE Precautions when mak...

Page 7: ...ressure gauge b Nitrogen c Refrigerant d Weighing machine e Vacuum pump f Stop valve g Main piping h Refrigerant branch kit i Branch piping 4 3 2 To check for leaks NOTICE Do NOT exceed the unit s max...

Page 8: ...o determine the additional refrigerant amount To determine if adding additional refrigerant is necessary If Then L1 L2 L3 L4 L5 L6 L7 chargeless length Chargeless length 10 m size down 30 m standard 1...

Page 9: ...on page 7 4 4 5 To charge additional refrigerant WARNING Only use R410A as refrigerant Other substances may cause explosions and accidents R410A contains fluorinated greenhouse gases Its global warmi...

Page 10: ...nt is connected only to a supply with a short circuit power Ssc greater than or equal to the minimum Ssc value Model Minimum Ssc value RZQG100 140_Y1 RZQSG140_Y1 1170 kVA a a This is the most stringen...

Page 11: ...G insertions can be inserted at the knockout hole When you do not use a wire conduit protect the wires with vinyl tubes to prevent the edge of the knockout hole from cutting the wires a b c d e A B A...

Page 12: ...operly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matc...

Page 13: ...d E7 There is a missing phase in case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three electrical wires L4 The air...

Page 14: ...ed air from flowing back to the suction side through the bottom of the unit 2 Maximum two units can be installed Not allowed Multiple rows of units See figure 2 on the inside of the front cover Stacke...

Page 15: ...2U Fuse F6U Fuse T 3 15 A 250 V F7U F8U Fuse F 1 0 A 250 V F1U F8U RZQG100 140_V1 RZQSG125 140_V1 F1U F4U Fuse F6U Fuse T 5 0 A 250 V F7U F8U Fuse F 1 0 A 250 V F1U F8U RZQ S G_Y1 F1U F2U Fuse 31 5 A...

Page 16: ...ical data Installation manual 16 RZQG71 140L_V1 Y1 RZQSG100 140L_V1 Y1 Split system air conditioners 4P385521 1C 2019 04 Colours BLK Black BLU Blue BRN Brown GRN Green ORG Orange RED Red WHT White YLW...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...4P385521 1C 2019 04 Copyright 2014 Daikin 4P385521 1 B 0000000 4P385521 1 C 0000000...

Reviews: