background image

English

12

(2) Lay the wires in the control box through the wire inlet on the 

side of the control box.

CAUTION

• Do not lay the remote controller wiring or transmission wiring 

along with the power supply wiring or other electric wiring in 
the same route. Separate the remote controller wiring and 
transmission wiring at least 2 in. (50 mm) from the power sup-
ply wiring or other electric wiring, or otherwise malfunctions or 
failures may be caused by external electric noise that may 
interfere with the remote controller wiring and transmission 
wiring.

• For the installation and wiring of the remote controller, refer to 

the remote controller installation manual provided with the 
remote controller.

• For power supply wiring, refer to the wiring diagram as well.
• Be sure to connect the remote controller wiring and transmis-

sion wiring correctly to the right terminal block.

(3) Follow the instructions below, and lay the wires in the con-

trol box.

Routing wiring

Let the power supply and ground wiring with the conduit pass 
through one of the holes on the side cover, and let the transmis-
sion and remote controller wiring with the conduit pass through 
another hole.

• For protection from uninsulated live parts, thread the high 

and low voltage wirings through each of the included insulat-
ing tube and secure it with the included clamp separately.

When using the insulating tube

• Cut off the insulation tube at needed length.

WARNING

Trim and lay the wiring neatly and attach the control box 
cover securely.

An electric shock or fire may result if the control box cover 
catches any wiring or the wires push up the cover.

Low-voltage wiring inlet

Transmission wiring
(Low voltage)
Remote controller wiring
(Low voltage)

Lock nut
(Field supply)

High-voltage wiring inlet

Power supply wiring (High voltage)
Ground wiring (High voltage)

Conduit
(Field supply) 

Elbow
(Field supply)

L

1

L

2

1

P

2

P

1

F

2

F

1

T

2

T

Fix the wires with 
clamp (8) to the 
wire fixing bracket 
provided to the 
control box.

Insert the wires 
into the wire clip 
provided with the 
control box.

PROHIBITED

Never connect the power 
supply wiring.

Connection method of remote 
controller terminals (X2M) 
• If stranded wires are used, do 
  not solder the front end of the 
 wires.

Twist and fix the upper part so 
that the wires will not drop out.

Fix the wires with the 
clamp (8) to the wire 
fixing bracket provided 
to the control box.

Remote controller 
wiring (No polarity)

Power supply wiring 
(High voltage)
Ground wiring 
(High voltage)

Transmission wiring 
(No polarity)

Transmission 
wiring (Low voltage)
Remote controller 
wiring (Low voltage)

Ground

Connection method of 
power supply terminals 
(X1M)

Insulating tube
(accessory (12))

Conduit
(field supply)

Insulating tube
(accessory (12))

Clamp
(accessory (8))

Wiring

(3 in. (75 mm))

Cut off

01_EN_3P530815-1.fm  Page 12  Tuesday, July 10, 2018  6:20 PM

Summary of Contents for SkyAir FBQ24PVJU

Page 1: ...dy place for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure...

Page 2: ...ant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation work check that the re frigerant gas does not l...

Page 3: ...t is released Therefore take proper measures to check for the tightness of the refrigerant piping installation Read the chapter REFRIGERANT PIPING WORK and follow the procedures Since R410A is a blend...

Page 4: ...alt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels This unit both indoor and outdoor is suitable for installation in a commercia...

Page 5: ...the outdoor unit Remote controller Model Wired type BRC1E73 Wireless type 2 speed BRC4C82 3 speed BRC082A43 Items to be checked If not properly done what is likely to occur Check Are the indoor and ou...

Page 6: ...0 450 for the control box and inspection hatch 2 for the lower part of the product see arrow view A 1 Refer to Fig 2 3 3 Inspection hatch 3 for the lower part of the product and the lower part of the...

Page 7: ...ust the distance to the ceiling surface in advance 5 INDOOR UNIT INSTALLATION It may be easier to install accessories sold separately before installing the indoor unit Refer to the installation manual...

Page 8: ...ut provided with the unit Do not use a different flare nut such as a type 1 flare nut or otherwise refrigerant leakage may result To prevent contamination or moisture from getting into the piping take...

Page 9: ...alloy BCuP 2 BCu 93P 710 795 which does not require flux for brazing Flux has a bad influence on the refrigerant piping Chlo rine based flux will cause piping corrosion Furthermore if it contains flu...

Page 10: ...conditioner is finished 1 Remove the control box cover and connect the single phase electric wires to terminals L1 and L2 of the ter minal block and the ground wiring to the ground ter minal Perform w...

Page 11: ...the sputter will not come in contact with the drain pan or the filter If the metal duct pass through a metal lath wire lath or metal plate of a wooden structure separate the duct and wall elec tricall...

Page 12: ...CTRICAL CHARACTERISTICS MCA Minimum Circuit Ampacity A MOP Maximum Overcurrent Protective Device A KW Fan Motor Rated Output kW FLA Full Load Ampere A 9 3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND W...

Page 13: ...d insulat ing tube and secure it with the included clamp separately When using the insulating tube Cut off the insulation tube at needed length WARNING Trim and lay the wiring neatly and attach the co...

Page 14: ...too small and the terminal screws will not be tightened properly Do not tighten the terminal screws excessively or otherwise the screw heads may be damaged Refer to the table below for the required t...

Page 15: ...osed on the indoor and outdoor units Field setting must be made from the remote controller in accordance with the installation conditions Setting can be made by changing the Mode No FIRST CODE NO and...

Page 16: ...s that 02 is set for the SECOND CODE NO in Table 2 If the air conditioner does not stop operating automatically or the SECOND CODE NO is not 02 repeat steps from 3 If the outdoor unit is not turned ON...

Page 17: ...ish work is completed If the air conditioner is operated the inside of the indoor unit may be polluted by substances generated from the coating and adhesives used for the interior finish work and caus...

Page 18: ...1809 HT 3P530815 1 EM18A001...

Reviews: