background image

English

8

(2) On completion of installation work, 

check that there is no 

gas leakage

.

(3) Refer to the following illustration and be sure to perform 

thermal insulation work on the piping joints after gas leak-
age checks. 

(Refer to Fig. 6)

• Use the insulation for fitting (4) and (5) provided to the 

liquid piping and gas piping, respectively, and conduct 
thermal insulation work.
(Tighten both edges of the insulation for fitting (4) and (5) 
for each joint with the clamp (8).)

• Make sure that the joint of the insulation for fitting (4) and 

(5) for the joint on the liquid piping and gas piping side 
faces upward.

• Wrap the middle sealing material (7) around the insula-

tion for fitting (4) and (5) for the joint (flare nut part).

CAUTION

• Be sure to perform the thermal insulation of the local pip-

ing up to the piping joint.

If the piping is exposed, dew condensation may result. Fur-
thermore, a burn may be caused if a human body comes in 
contact with the piping.

• Perform nitrogen substitution or apply nitrogen into the 

refrigerant piping (see NOTE 1) in the case of refrigerant 
piping brazing (see NOTE 2). Then perform the flare con-
nection of the indoor unit. 

(Refer to Fig. 7)

CAUTION

• Do not use any antioxidant at the time of piping brazing.

The piping may be clogged with a residual antioxidant and 
parts may malfunction.

NOTE

1. At the time of brazing, set the pressure of nitrogen to 

approximately 2.9 PSI (0.02 MPa) (close to the pressure 
of a breeze coming in contact with the cheek) with a pres-
sure-reducing valve.

2. Do not use flux at the time of brazing and connecting the 

refrigerant piping. Use a copper phosphorus brazing alloy 
(BCuP-2/BCu 93P-710/795), which does not require flux, 
for brazing.
(Flux has a bad influence on the refrigerant piping. Chlo-
rine-based flux will cause piping corrosion. Furthermore, if 
it contains fluorine, the flux will deteriorate refrigerant oil.)

7.

DRAIN PIPING WORK

(1) Conduct drain piping work.

Check that the piping 
ensures proper draining.

• Make sure that the diam-

eter of the piping exclud-
ing the rising part is the 
same as or larger than 
the diameter of the con-
necting pipe (vinyl chloride pipe with an outer diameter 
of 1-1/4 in. (32 mm) and a nominal inner diameter of 1 in. 
(25 mm)).

• Make sure that the piping is short enough 

with a down-

ward slope of at least 1/100

 and that there is no air 

bank formed. No drain trap is required.

Thermal insulation procedure for gas piping

Insulation material 
for piping 
(on unit side)

Insulation material 
for piping (field supply)

Make sure that 
the seam faces 
upward.

Clamp (8) 
(accessory)

Gas pipe

Liquid pipe

Flare nut joint

Attached to 
the surface.

Insulation for fitting (5) (accessory)

Middle sealing pad (7) 
(accessory)

Wrap the insulation material 
around the portion from the 
surface of the main unit to the 
upper part of the flare nut joint.

Insulation material 
for piping (field supply)

Wrap the insulation material 
around the portion from the 
surface of the main unit to the 
upper part of the flare nut joint.

Fig. 6

Thermal insulation procedure for liquid piping

Insulation material 
for piping 
(on unit side)

Make sure that 
the seam faces 
upward.

Clamp (8) 
(accessory)

Main unit

Flare nut joint

Attached to 
the surface.

Insulation for fitting (4) (accessory)

Middle sealing pad (7) 
(accessory)

Nitrogen

Refrigerant 
piping

Part to be 
brazed 

Taping

Pressure-reducing valve

hand 
valve

Nitrogen

Fig. 7

Refrigerant 
piping

Drain socket 

Socket for 
maintenance 
(with rubber cap)

01_EN_3P530815-1.fm  Page 8  Tuesday, July 10, 2018  6:20 PM

Summary of Contents for SkyAir FBQ24PVJU

Page 1: ...dy place for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure...

Page 2: ...ant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation work check that the re frigerant gas does not l...

Page 3: ...t is released Therefore take proper measures to check for the tightness of the refrigerant piping installation Read the chapter REFRIGERANT PIPING WORK and follow the procedures Since R410A is a blend...

Page 4: ...alt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels This unit both indoor and outdoor is suitable for installation in a commercia...

Page 5: ...the outdoor unit Remote controller Model Wired type BRC1E73 Wireless type 2 speed BRC4C82 3 speed BRC082A43 Items to be checked If not properly done what is likely to occur Check Are the indoor and ou...

Page 6: ...0 450 for the control box and inspection hatch 2 for the lower part of the product see arrow view A 1 Refer to Fig 2 3 3 Inspection hatch 3 for the lower part of the product and the lower part of the...

Page 7: ...ust the distance to the ceiling surface in advance 5 INDOOR UNIT INSTALLATION It may be easier to install accessories sold separately before installing the indoor unit Refer to the installation manual...

Page 8: ...ut provided with the unit Do not use a different flare nut such as a type 1 flare nut or otherwise refrigerant leakage may result To prevent contamination or moisture from getting into the piping take...

Page 9: ...alloy BCuP 2 BCu 93P 710 795 which does not require flux for brazing Flux has a bad influence on the refrigerant piping Chlo rine based flux will cause piping corrosion Furthermore if it contains flu...

Page 10: ...conditioner is finished 1 Remove the control box cover and connect the single phase electric wires to terminals L1 and L2 of the ter minal block and the ground wiring to the ground ter minal Perform w...

Page 11: ...the sputter will not come in contact with the drain pan or the filter If the metal duct pass through a metal lath wire lath or metal plate of a wooden structure separate the duct and wall elec tricall...

Page 12: ...CTRICAL CHARACTERISTICS MCA Minimum Circuit Ampacity A MOP Maximum Overcurrent Protective Device A KW Fan Motor Rated Output kW FLA Full Load Ampere A 9 3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND W...

Page 13: ...d insulat ing tube and secure it with the included clamp separately When using the insulating tube Cut off the insulation tube at needed length WARNING Trim and lay the wiring neatly and attach the co...

Page 14: ...too small and the terminal screws will not be tightened properly Do not tighten the terminal screws excessively or otherwise the screw heads may be damaged Refer to the table below for the required t...

Page 15: ...osed on the indoor and outdoor units Field setting must be made from the remote controller in accordance with the installation conditions Setting can be made by changing the Mode No FIRST CODE NO and...

Page 16: ...s that 02 is set for the SECOND CODE NO in Table 2 If the air conditioner does not stop operating automatically or the SECOND CODE NO is not 02 repeat steps from 3 If the outdoor unit is not turned ON...

Page 17: ...ish work is completed If the air conditioner is operated the inside of the indoor unit may be polluted by substances generated from the coating and adhesives used for the interior finish work and caus...

Page 18: ...1809 HT 3P530815 1 EM18A001...

Reviews: