background image

English

6

(2) Mount the canvas ducts to the air outlet and inlet so that the 

vibration of the air conditioner will not be transmitted to the 
duct or ceiling. Apply a sound-absorbing material (insula-
tion material) to the inner wall of the duct and vibration insu-
lation rubber to the suspension bolts (refer to 

8. DUCT 

WORK

).

(3) Open installation holes (if the ceiling already exists).

• Open the installation holes on the ceiling. Lay the refrig-

erant piping, drain piping, power line, transmission wir-
ing, and remote controller wiring for the piping and wiring 
connection port of the unit.
In the case of the installation of a wireless remote con-
troller, refer to the installation manual provided with the 
wireless remote controller.
Refer to 

6. REFRIGERANT PIPING WORK

7. DRAIN 

PIPING WORK

, and 

10. WIRING EXAMPLE AND HOW 

TO SET THE REMOTE CONTROLLER

.

• The ceiling framework may need reinforcement in order 

to keep the ceiling horizontal and prevent the vibration of 
the ceiling after the installation holes are opened. For 
details, consult your construction or interior contractor.

(4) Install the suspension bolts. Make sure that the suspension 

bolts are M10 or the equivalent in size.

• Use hole-in anchors if the suspension bolts already exist; 

otherwise use embedded inserts and embedded founda-
tion bolts so that they will withstand the weight of the unit. 
Adjust the distance to the ceiling surface in advance.

5.

INDOOR UNIT INSTALLATION

It may be easier to install accessories (sold separately) 

before installing the indoor unit. Refer to the installation 
manuals provided to the accessories as well.



Be sure to use the accessories and specified parts for 
installation work.

(1) Temporally install the indoor unit.

• Connect the hangers to the suspension bolts. Be sure to 

use and tighten the nut and washer for hanger (11) for 
each hanger from both upper and lower sides of the 
hanger. 

(Refer to Fig. 3)

 If the washer fixing plate (9) is 

used, the upper side washer for hanger (11) will be pro-
tected from falling off. 

CAUTION

• Keep the air outlet covered with a protective sheet to pre-

vent weld splatter and other foreign materials from enter-
ing the indoor unit, and damaging the resin drain pan.

Water leakage may occur if holes or cracks are generated in 
the resin drain pan.

(2) Make adjustments so that the unit will be in the right posi-

tion.

(3) Check the level of the unit.
(4) Remove the washer fixing plate (9) used for preventing the 

washer for hanger (11) from dropping, tighten the upper 
side nuts, and securely fix the unit. 

Note)   All the above parts are field supplied. 

Installation example

Ceiling slab

Anchor

Long nut or turn-buckle

Suspension bolt

Indoor unit

Washer for hanger (11) 
(accessory)

Part to be procured in the field

Washer fixing plate (9) 
(accessory)

Insert

Tighten from above and below 
(Double nut)

[Fixing hangers]

[Fixing method of washers]

Fig. 3

Nut on the upper side

Hanger

Bottom of product

Level

Vinyl tube

01_EN_3P530815-1.fm  Page 6  Tuesday, July 10, 2018  6:20 PM

Summary of Contents for SkyAir FBQ24PVJU

Page 1: ...dy place for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure...

Page 2: ...ant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation work check that the re frigerant gas does not l...

Page 3: ...t is released Therefore take proper measures to check for the tightness of the refrigerant piping installation Read the chapter REFRIGERANT PIPING WORK and follow the procedures Since R410A is a blend...

Page 4: ...alt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels This unit both indoor and outdoor is suitable for installation in a commercia...

Page 5: ...the outdoor unit Remote controller Model Wired type BRC1E73 Wireless type 2 speed BRC4C82 3 speed BRC082A43 Items to be checked If not properly done what is likely to occur Check Are the indoor and ou...

Page 6: ...0 450 for the control box and inspection hatch 2 for the lower part of the product see arrow view A 1 Refer to Fig 2 3 3 Inspection hatch 3 for the lower part of the product and the lower part of the...

Page 7: ...ust the distance to the ceiling surface in advance 5 INDOOR UNIT INSTALLATION It may be easier to install accessories sold separately before installing the indoor unit Refer to the installation manual...

Page 8: ...ut provided with the unit Do not use a different flare nut such as a type 1 flare nut or otherwise refrigerant leakage may result To prevent contamination or moisture from getting into the piping take...

Page 9: ...alloy BCuP 2 BCu 93P 710 795 which does not require flux for brazing Flux has a bad influence on the refrigerant piping Chlo rine based flux will cause piping corrosion Furthermore if it contains flu...

Page 10: ...conditioner is finished 1 Remove the control box cover and connect the single phase electric wires to terminals L1 and L2 of the ter minal block and the ground wiring to the ground ter minal Perform w...

Page 11: ...the sputter will not come in contact with the drain pan or the filter If the metal duct pass through a metal lath wire lath or metal plate of a wooden structure separate the duct and wall elec tricall...

Page 12: ...CTRICAL CHARACTERISTICS MCA Minimum Circuit Ampacity A MOP Maximum Overcurrent Protective Device A KW Fan Motor Rated Output kW FLA Full Load Ampere A 9 3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND W...

Page 13: ...d insulat ing tube and secure it with the included clamp separately When using the insulating tube Cut off the insulation tube at needed length WARNING Trim and lay the wiring neatly and attach the co...

Page 14: ...too small and the terminal screws will not be tightened properly Do not tighten the terminal screws excessively or otherwise the screw heads may be damaged Refer to the table below for the required t...

Page 15: ...osed on the indoor and outdoor units Field setting must be made from the remote controller in accordance with the installation conditions Setting can be made by changing the Mode No FIRST CODE NO and...

Page 16: ...s that 02 is set for the SECOND CODE NO in Table 2 If the air conditioner does not stop operating automatically or the SECOND CODE NO is not 02 repeat steps from 3 If the outdoor unit is not turned ON...

Page 17: ...ish work is completed If the air conditioner is operated the inside of the indoor unit may be polluted by substances generated from the coating and adhesives used for the interior finish work and caus...

Page 18: ...1809 HT 3P530815 1 EM18A001...

Reviews: