background image

7

English

CAUTION

• Use the level and check that the unit is installed horizontally.

(4-directions)

• In the case of using a vinyl tube (filled with water) in place of 

the level, align the bottom of the unit to the water surface at 
both edges of the vinyl tube to make levelness adjustment.
If the unit is installed at a slant with the drain pipe side set 
high, in particular, the float switch will not operate normally 
and water leakage may result.

6.

REFRIGERANT PIPING WORK

As for the refrigerant piping of the outdoor unit, refer to the 

installation manual provided to the outdoor unit.



Perform thermal insulation work on both gas piping and 

liquid piping, or otherwise water leakage may result.



Use the insulation material that withstands a temperature 

of 250°F (120°C).



Reinforce the insulation material for the refrigerant piping if 

the ambient temperature is high, or otherwise dew conden-
sation may result on the surface of the insulation material.



Make sure that the refrigerant is R410A before refrigerant 

piping work. If the refrigerant is different, the air condi-
tioner will not operate normally.



CAUTION

This product uses new refrigerant (R410A) only. Be sure to 
keep the following items and conduct the installation work.

• Use a dedicated pipe cutter and a flaring tool for R410A.
• When connecting the flare, apply ether oil or ester oil 

only to inner side of the flare.

• Be sure to use the flare nut provided with the unit. (Do 

not use a different flare nut (such as a type-1 flare nut), 
or otherwise refrigerant leakage may result.)

• To prevent contamination or moisture from getting into 

the piping, take measures such as pinching or taping the 
ends of the pipes.

• Be sure to use the specified type of refrigerant for the 

refrigeration cycle and do not contaminate the refrigerant 
with air.

• Ventilate the room in case of refrigerant leakage during 

installation work.

(1) Connect the piping.

• The refrigerant is pre-charged in the outdoor unit.
• When connecting or disconnecting piping to or from the 

unit, 

be sure to use a spanner and a torque wrench. 

(Refer to Fig. 4)

• Refer to Table 1 for the processing dimensions of the 

flare.

• Use the flare nut provided with the unit.

Apply ether oil or ester oil only to inner side of the 
flare

 and screw in the flare nut three to four turns first by 

hand at the time of connecting the flare nut. 

(Refer to Fig. 5)

• Refer to Table 1 for the corresponding tightening torque.

Table 1

CAUTION

• Do not excessively tighten the flare nut.

Doing so will break the flare nut and refrigerant leakage may 
occur.

• Make sure that all parts around the flare are free of oil.

The drain pan and the resin part may be deteriorated if oil is 
attached.

Piping 

size 

[in. (mm)]

Tightening 

torque 

[lbf·ft. (N·m)]

Dimension for 

processing flare 

A [in. (mm)]

Flare shape

[in. (mm)]



 3/8 

(9.5)

24.1 – 29.4 

(36.3±3.6)

0.504 – 0.520 

(13.0±0.2)



 5/8 

(15.9)

45.6 – 55.6 

(68.6±6.8)

0.760 – 0.776 

(19.5±0.2)

Torque wrench

Spanner

Piping union

Flare nut

Fig. 4

Fig. 5

Apply ester oil or ether oil 
only to inner side of flare.

R0.016-0.031

(0.4-0.8)

A

01_EN_3P530815-1.fm  Page 7  Tuesday, July 10, 2018  6:20 PM

Summary of Contents for SkyAir FBQ24PVJU

Page 1: ...dy place for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure...

Page 2: ...ant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation work check that the re frigerant gas does not l...

Page 3: ...t is released Therefore take proper measures to check for the tightness of the refrigerant piping installation Read the chapter REFRIGERANT PIPING WORK and follow the procedures Since R410A is a blend...

Page 4: ...alt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels This unit both indoor and outdoor is suitable for installation in a commercia...

Page 5: ...the outdoor unit Remote controller Model Wired type BRC1E73 Wireless type 2 speed BRC4C82 3 speed BRC082A43 Items to be checked If not properly done what is likely to occur Check Are the indoor and ou...

Page 6: ...0 450 for the control box and inspection hatch 2 for the lower part of the product see arrow view A 1 Refer to Fig 2 3 3 Inspection hatch 3 for the lower part of the product and the lower part of the...

Page 7: ...ust the distance to the ceiling surface in advance 5 INDOOR UNIT INSTALLATION It may be easier to install accessories sold separately before installing the indoor unit Refer to the installation manual...

Page 8: ...ut provided with the unit Do not use a different flare nut such as a type 1 flare nut or otherwise refrigerant leakage may result To prevent contamination or moisture from getting into the piping take...

Page 9: ...alloy BCuP 2 BCu 93P 710 795 which does not require flux for brazing Flux has a bad influence on the refrigerant piping Chlo rine based flux will cause piping corrosion Furthermore if it contains flu...

Page 10: ...conditioner is finished 1 Remove the control box cover and connect the single phase electric wires to terminals L1 and L2 of the ter minal block and the ground wiring to the ground ter minal Perform w...

Page 11: ...the sputter will not come in contact with the drain pan or the filter If the metal duct pass through a metal lath wire lath or metal plate of a wooden structure separate the duct and wall elec tricall...

Page 12: ...CTRICAL CHARACTERISTICS MCA Minimum Circuit Ampacity A MOP Maximum Overcurrent Protective Device A KW Fan Motor Rated Output kW FLA Full Load Ampere A 9 3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND W...

Page 13: ...d insulat ing tube and secure it with the included clamp separately When using the insulating tube Cut off the insulation tube at needed length WARNING Trim and lay the wiring neatly and attach the co...

Page 14: ...too small and the terminal screws will not be tightened properly Do not tighten the terminal screws excessively or otherwise the screw heads may be damaged Refer to the table below for the required t...

Page 15: ...osed on the indoor and outdoor units Field setting must be made from the remote controller in accordance with the installation conditions Setting can be made by changing the Mode No FIRST CODE NO and...

Page 16: ...s that 02 is set for the SECOND CODE NO in Table 2 If the air conditioner does not stop operating automatically or the SECOND CODE NO is not 02 repeat steps from 3 If the outdoor unit is not turned ON...

Page 17: ...ish work is completed If the air conditioner is operated the inside of the indoor unit may be polluted by substances generated from the coating and adhesives used for the interior finish work and caus...

Page 18: ...1809 HT 3P530815 1 EM18A001...

Reviews: