5

English

CAUTION

• Install the indoor and outdoor units, power supply wiring and 

connecting wires at least 3.3 ft (1 m) away from televisions or 
radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 3.3 ft (1 m) may 
not be sufficient enough to eliminate the noise.)

• In the case of the installation of the wireless remote controller, 

the transmission distance of the wireless remote controller may 
be shortened if the room has a fluorescent light of electronic 
lighting type (i.e., an inverter or rapid-start fluorescent light).
Keep the distance between the receiver and the fluorescent 
light as far as possible.

(2) Use suspension bolts to install the indoor unit. Check that 

the place of installation withstands the weight of the indoor 
unit. Secure the suspension bolts with proper beams if nec-
essary.

4.

PREPARATIONS BEFORE INSTALLATION

(1) Check the positional relationship between the ceiling open-

ing hole and the suspension bolt of the unit. [unit: in. (mm)]

• For the maintenance, inspection, and other servicing 

purposes of the control box and drain pump, prepare one 
of the following service spaces.
1. Inspection hatch 1 (17-3/4 × 17-3/4 (450 × 450)) for 

the control box and a minimum space of 12 in. (300) 
for the lower part of the product. 

(Refer to Fig. 2-2)

2. Inspection hatch 1 (17-3/4 × 17-3/4 (450 × 450)) for 

the control box and inspection hatch 2 for the lower 
part of the product (see arrow view A-1). 

(Refer to 

Fig. 2-3)

3. Inspection hatch 3 for the lower part of the product 

and the lower part of the control box (see arrow view 
A-2). 

(Refer to Fig. 2-3)

[unit: in. (mm)]

Ceiling

Floor surface

• The H1 dimension indicates the 

height of the product.

• Determine the H2 dimension by 

maintaining a downward slope of 
at least 1/100 as specified in 
“7. DRAIN PIPING WORK”.

Min. 1 (20)

Min. 12 

(300)

Min. 18 

(450)

Min. 99 (2500)

Min. 28 (700)

(service space)

(If no ceiling board is provided.)

*H1=12 (300)

*H2=Min. 25 (620)

[Required installation place]

The dimensions indicate the 
minimum required space of 
installation.

Fig. 2-1

28 (700)

24-13/16 (631)

(Suspension bolt pitch)

Inspection hatch 1 
(17-3/4×17-3/4)
(450×450)

Inspection hatch

Control box

Control box

Ceiling

B

C

(Suspension bolt pitch)

Bottom of unit

Air inlet

Air outlet

Suspension bolt (× 4)

*H3=Min. 12 

(300)

Fig. 2-2

Case 1

[unit: in. (mm)]

28 (700)

28 (700)

Inspection hatch

Inspection hatch 1 
(17-3/4×17-3/4) (450×450)

Inspection 
hatch 2

Inspection hatch 3

(Same as the indoor 
unit size +12 (300) or more)

Control box

Control box

Control box

Inspection hatch

(Ceiling opening)

Ceiling

Arrow view A-1

Arrow view A-2

Min. D=B+12 

(300)

Min. 8 (200)

B

*H3=Min. 3/4 (20)

Model

B

C

D

40

(1000)

40-7/8
(1038)

52

(1300)

56

(1400)

56-5/8
(1438)

68

(1700)

18 • 24 • 30 type

36 • 42 • 48 type

[unit: in. (mm)]

A

Fig. 2-3

Case 2, 3

(Same as the 
indoor unit 
size or more)

• Determine the H3 

dimension by maintaining a 
downward slope of at least 
1/100 as specified in 
“7. DRAIN PIPING WORK”.

01_EN_3P530815-1.fm  Page 5  Tuesday, July 10, 2018  6:20 PM

Summary of Contents for SkyAir FBQ24PVJU

Page 1: ...dy place for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure...

Page 2: ...ant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation work check that the re frigerant gas does not l...

Page 3: ...t is released Therefore take proper measures to check for the tightness of the refrigerant piping installation Read the chapter REFRIGERANT PIPING WORK and follow the procedures Since R410A is a blend...

Page 4: ...alt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels This unit both indoor and outdoor is suitable for installation in a commercia...

Page 5: ...the outdoor unit Remote controller Model Wired type BRC1E73 Wireless type 2 speed BRC4C82 3 speed BRC082A43 Items to be checked If not properly done what is likely to occur Check Are the indoor and ou...

Page 6: ...0 450 for the control box and inspection hatch 2 for the lower part of the product see arrow view A 1 Refer to Fig 2 3 3 Inspection hatch 3 for the lower part of the product and the lower part of the...

Page 7: ...ust the distance to the ceiling surface in advance 5 INDOOR UNIT INSTALLATION It may be easier to install accessories sold separately before installing the indoor unit Refer to the installation manual...

Page 8: ...ut provided with the unit Do not use a different flare nut such as a type 1 flare nut or otherwise refrigerant leakage may result To prevent contamination or moisture from getting into the piping take...

Page 9: ...alloy BCuP 2 BCu 93P 710 795 which does not require flux for brazing Flux has a bad influence on the refrigerant piping Chlo rine based flux will cause piping corrosion Furthermore if it contains flu...

Page 10: ...conditioner is finished 1 Remove the control box cover and connect the single phase electric wires to terminals L1 and L2 of the ter minal block and the ground wiring to the ground ter minal Perform w...

Page 11: ...the sputter will not come in contact with the drain pan or the filter If the metal duct pass through a metal lath wire lath or metal plate of a wooden structure separate the duct and wall elec tricall...

Page 12: ...CTRICAL CHARACTERISTICS MCA Minimum Circuit Ampacity A MOP Maximum Overcurrent Protective Device A KW Fan Motor Rated Output kW FLA Full Load Ampere A 9 3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND W...

Page 13: ...d insulat ing tube and secure it with the included clamp separately When using the insulating tube Cut off the insulation tube at needed length WARNING Trim and lay the wiring neatly and attach the co...

Page 14: ...too small and the terminal screws will not be tightened properly Do not tighten the terminal screws excessively or otherwise the screw heads may be damaged Refer to the table below for the required t...

Page 15: ...osed on the indoor and outdoor units Field setting must be made from the remote controller in accordance with the installation conditions Setting can be made by changing the Mode No FIRST CODE NO and...

Page 16: ...s that 02 is set for the SECOND CODE NO in Table 2 If the air conditioner does not stop operating automatically or the SECOND CODE NO is not 02 repeat steps from 3 If the outdoor unit is not turned ON...

Page 17: ...ish work is completed If the air conditioner is operated the inside of the indoor unit may be polluted by substances generated from the coating and adhesives used for the interior finish work and caus...

Page 18: ...1809 HT 3P530815 1 EM18A001...

Reviews: