SiBE041213E
Field Settings
Tips for Servicing
108
3.3
Standby Electricity Saving
Outline
This function turns power supply OFF to the outdoor unit and sets the indoor unit into standby
electricity saving mode, thus reducing the power consumption of the air conditioner.
Detail
For 35/50 class models, following procedure is required for turning ON the function.
1. Check that the main power supply is turned OFF. Turn OFF if it has not been turned OFF.
2. Remove the stop valve cover.
3. Disconnect the selective connector for standby electricity saving.
4. Turn ON the main power supply.
35 class
50 class
Caution
Before connecting or disconnecting the selective connector for standby electricity saving, make
sure that the main power supply is turned OFF.
3.4
Facility Setting Jumper (cooling at low outdoor
temperature)
Outline
This function is limited only for facilities (the target of air conditioning is equipment (such as
computer)). Never use it in a residence or office (the space where there is a human).
35 Class
You can expand the operation range to –15°C by cutting the jumper on the outdoor unit PCB. If
the outdoor temperature falls to –20°C or lower, the operation stops. If the outdoor temperature
rises, the operation starts again.
Main PCB
1
2
3
1
2
3
(R18981)
Function ON
Function OFF
(factory set)
(R18926)
Function ON
Function OFF
(factory set)
S70
S40
S2
S90
J5
J4
J3
(R18253)
Cut the jumper J4.
Summary of Contents for RXS35K2V1B
Page 12: ...SiBE041213E 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Page 14: ...SiBE041213E 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Page 59: ...SiBE041213E Remote Controller 48 Part 5 Remote Controller 1 Remote Controller 49 ...
Page 129: ...Revision History Month Year Version Revised contents 05 2013 SiBE041213E First edition ...