SiBE041213E
Field Settings
Tips for Servicing
110
3.5
Jumper Settings
Indoor Unit
For the location of the jumper, refer to page 7.
Outdoor Unit
For the location of the jumper, refer to page
9, 11, 12
.
Caution
Replace the PCB if you accidentally cut a wrong jumper.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of
them.
Function
Jumper
Jumper: connected
(factory set)
Jumper: cut
Fan speed setting when
compressor stops for
thermostat OFF. (effective only
in cooling operation)
JB
Fan speed setting ;
Remote controller
setting
Fan speed setting; “0” (The fan
stops.)
Power failure recovery function
JC
Auto-restart
The unit does not resume
operation after recovering from a
power failure. Timer settings are
cleared.
Function
Jumper
Jumper: connected
(factory set)
Jumper: cut
Improvement of defrost
performance
35/42 class
→
J5
50 class
→
J8
Standard control
Reinforced control (ex.
The frequency
increases, the duration
time of defrost
lengthens.)