SiBE041213E
Check
Service Diagnosis
96
<42 class>
Activate power transistor test operation from indoor unit.
1) Turn the power on.
2) Select FAN operation with the [MODE] button on the remote controller.
3) Press the center of the [TEMP] button and the [MODE] button at the same time.
→
00
is displayed with the figure of ten's place blinking.
4) Press the [MODE] button.
→
00
is displayed with the figure of one's place blinking.
5) Press the [MODE] button.
→
T
is displayed.
6) Press the [ON/OFF] button.
→
Power transistor test operation starts.
Diagnose method (Diagnose according to 6 LEDs lighting status.)
(1) If all the LEDs are lit uniformly, the compressor is defective.
→
Replace the compressor.
(2) If the LEDs are not lit uniformly, check the power module.
→
Refer to
Check No.22
.
(3) If NG in
Check No.22
, replace the power module.
(Replace the main PCB. The power module is united with the main PCB.)
If OK in
Check No.22
, check if there is any solder cracking on the PCB.
(4) If any solder cracking is found, replace the PCB or repair the soldered section.
If there is no solder cracking, replace the PCB.
Caution
(1) When the output frequency is low, the LEDs blink slowly. As the output frequency increases,
the LEDs blink quicker. (The LEDs look like they are lit.)
(2) On completion of the inverter analyzer diagnosis, be sure to re-crimp the FASTON terminals.
Otherwise, the terminals may be burned due to loosening.
(R15292)
Direction of crimp
FASTON terminal
This size is shortened
by the crimp.
Summary of Contents for RXS35K2V1B
Page 12: ...SiBE041213E 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Page 14: ...SiBE041213E 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Page 59: ...SiBE041213E Remote Controller 48 Part 5 Remote Controller 1 Remote Controller 49 ...
Page 129: ...Revision History Month Year Version Revised contents 05 2013 SiBE041213E First edition ...