background image

18

English

Cautions for check operation

• If the system is started within about 12 minutes after the outside/

indoor units are turned ON, the compressor will not run and H2P 
lights up. Before starting an operation, always verify that the LED dis-
play shows the contents of the table in 

11-3 Check operation

 (6).

• The system may require up to 10 minutes until it can start the com-

pressor after an operation start. This is a normal operation to equal-
ize the refrigerant distribution.

• The check operation does not provide any means of checking the 

indoor units individually. For that purpose, perform normal operation 
using the remote controller after the check operation.

• Check operation is not possible in other modes such as collection mode.
• If the setting of indoor remote controller is changed before the check 

operation, it may not be performed correctly and malfunction code 
“UF” may be displayed.

Remote controller displays malfunction code

11-4 Check of normal operation

After the check operation is completed, operate the unit normally.
Check the below items.

Make sure the indoor and outside units are operating normally (If a 
knocking sound can be heard in the liquid compression of the com-
pressor, stop the unit immediately and then energize the heater for a 
sufficient length of time before restarting the operation.)

Run each indoor unit one at a time and make sure the corre-
sponding outside unit is also running.

Check to see if cold (or hot) air is coming out of the indoor unit.

Press the fan direction and fan strength buttons on the indoor unit 
to check if they operate properly.

NOTE

Cautions for normal operation check

Once stopped, the compressor will not restart in about 5 minutes 
even if the 

On/Off

 button of an indoor unit in the same system is 

pressed.

When the system operation is stopped by the remote controller, the out-
side units may continue operating for further 5 minutes at maximum.

If the system has not undergone any check operation by the test 
operation button since it was first installed, an malfunction code 
“U3” is displayed. In this case, perform check operation referring 
to 

11-3 Check operation

.

After the test operation, when handing the unit over to the cus-
tomer, make sure the control box cover, the inspection door, and 
the unit casing are all attached.

12. ONSITE SETTINGS

12-1 Energy saving and optimum operation

This VRV pump system is equipped with advanced energy saving func-
tionality. Depending on the priority, emphasizes can be put on energy 
saving or comfort level. Several parameters can be selected, resulting in 
the optimal balance between energy consumption and comfort for the 
particular application.

[2-8]=

Te target temperature during cooling operation

Default value=5

Change [2-8]=2-7 in function of required operation method dur-
ing cooling.

[2-9]=  Tc target temperature during heating operation

Default value=3

Change [2-9]=1, 3 or 6 in function of required operation method 
during heating.

Malfunc-

tion code

Installation error

Remedial action

E3
E4
F3
F6

UF
U2

The stop valve of an out-
side unit is left closed.

Open the stop valve.
Check referring to the table in 

9-9 Additional refrigerant 
charge

.

U1

The phases of the power 
supply to the outside 
units are reversed.

Exchange two of the three 
phases (L1, L2, L3) to make a 
positive phase connection.

U1
U2
U4

No power is supplied to an 
outside, Branch Selector 
or indoor unit (including 
phase interruption).

Check if the power supply wiring for the 
outside units are connected correctly.
(If the power supply wire is not con-
nected to L2 phase, no malfunction 
display will appear and the com-
pressor will not work.)
Check if the ground fault circuit 
interrupter in the outside unit is ON.

U7

UA

A model which cannot be 
connected in a multi-out-
side-unit system has 
been connected in a 
multi-outside-unit system.

DIP switch setting of 
Branch Selector unit is 
incorrect.

Combination with T 
type (BSQ-TVJ, BS-
Q54TVJ) and P 
type(BSVQ-PVJU, 
BSV-Q36PVJU) cause 
error.

Change to individual piping, and 
disconnect the wiring from the 
multi-outside-unit terminals (Q1, 
Q2).

Set up a DIP switch referring to 
service precautions of Branch 
Selector unit.

Configure the system with only T 
type, or only P type.

UF

Incorrect transmission 
between units

Check if the refrigerant piping 
and the unit transmission wiring 
are consistent with each other.

E3
F6

UF
U2

Refrigerant overcharge

Recalculate the required 
amount of refrigerant from the 
piping length and correct the 
refrigerant charge level by 
recovering any excessive refrig-
erant with a refrigerant recovery 
machine.

E4
F3

Insufficient refrigerant

Check if the additional refrig-
erant charge has been fin-
ished correctly.

Recalculate the required 
amount of refrigerant from the 
piping length and add an ade-
quate amount of refrigerant.

U7
UF

If the multi-outside-unit termi-
nal is connected when there 
is one outside unit installed.

Remove the wiring from the 
multi-outside-unit terminals (Q1, 
Q2).

UF

E4

The operation mode on 
the remote controller was 
changed before the check 
operation.

Set the operation mode on all 
indoor unit remote controllers to 
“cooling.”

HJ

The heat source water is 
not circulating.

Make sure that the water pump 
is running.

U3

The check operation has 
not been performed.

Perform the check operation.

E2
E3

E3 is activated, so On/Off but-
ton is pressed on the remote 
controller, but this does not 
turn E3 off. Or E2 is activated. 
In case of above, there is a 
malfunction of the compres-
sor in the outside unit.

Measure the insulation resis-
tance of the compressor to 
check the condition of the com-
pressor.

Te setting (cooling operation)

k

h h

k

h h h

2. 43°F (6°C)

k

h h h h

k

h

3. 45°F (7°C)

k

h h h h

k k

4. 46°F (8°C)

k

h h h

k

h h

5. 48°F (9°C)(default)

k

h h h

k

h

k

6. 50°F (10°C)

k

h h h

k k

h

7. 52°F (11°C)

k

h h h

k k k

Tc setting (heating operation)

k

h h

k

h h h

1. 106°F (41°C)

k

h h h h h

k

3. 109°F (43°C)(default)

k

h h h h

k k

6. 115°F (46°C)

k

h h h

k k

h

01_EN_3P365916_17C.fm  Page 18  Thursday, March 12, 2015  10:47 AM

Summary of Contents for RWEYQ144PCTJ

Page 1: ...ion Keep this manual in a handy place for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de ma...

Page 2: ...100 9 13 16 250 21 5 8 550 30 11 16 780 9 9 5 5 8 10 8 9 7 7 6 6 6 9 7 5 8 5 8 15 3 8 390 4 3 1 2 11 13 16 300 39 3 8 1000 35 7 16 900 19 11 16 500 Unit in mm 1 2 3 4 4 9 3 5 3 4 8 5 6 6 9 7 1 2 3 4...

Page 3: ...2 Q1 Q2 A1P F1 F2 F1 F2 Q1 Q2 A B C C H SELECTOR A5P 12 A B C C H SELECTOR A5P A B C A B C RWEYQ PCYD figure 10 A B C A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5...

Page 4: ...1 Q2 Q1 Q2 Q1 Q2 A1P A5P 1 4 8 9 5 6 6 6 2 3 RWEYQ PCYD A B C 7 1 4 5 2 3 3 4 3 X2M X1M F1 F2 F1 F2 Q1 Q2 X3M A1P A5P 1 2 RWEYQ PCYD A B C figure 13 figure 12 figure 11 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 Q...

Page 5: ...em Heat recovery system 1 2 3 4 5 6 7 8 9 10 11 5 4 12 14 15 16 17 13 figure 17 A B C A B C 1 2 DS1 1 2 3 4 OFF ON O U T I N A1P A5P RWEYQ PCYD A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N A1P RWEYQ PCT...

Page 6: ...system 4 5 3 2 1 figure 24 1 11 1 2 2 4 3 4 3 5 5 R410A R410A 9 7 7 8 13 9 6 6 16 10 10 10 10 17 12 12 14 15 15 18 18 Heat pump system Heat recovery system 1 2 3 4 figure 26 figure 27 figure 23 1 15...

Page 7: ...d to alert against unsafe practices NOTE Indicates situations that may result in equipment or property damage accidents only DANGER Refrigerant gas is heavier than air and replaces oxygen A massive le...

Page 8: ...r Refrigerant Pip ing and follow the procedures Since R410A is a blend the required additional refrigerant must be charged in its liquid state If the refrigerant is charged in a state of gas its compo...

Page 9: ...5 F 20 35 C Water flow rate 15 9gpm 60L min or more During cooling operation when the outside temperature is very low it is possible that the thermostat switches off automatically in order to protect...

Page 10: ...ead Drain pipe in 1 2FPS 2 female Thread 1 2FPS 2 female Thread General RWEYQ216PCYD CTJ RWEYQ252PCYD CTJ Nominal cooling capacity 2 MBH 216 252 Nominal heating capacity 3 MBH 243 283 5 Nominal input...

Page 11: ...hazard could occur leading to serious injury or death Re fer to the chapter Caution for refrigerant leaks NOTE 1 An inverter air conditioner may cause electronic noise generated from AM broadcasting...

Page 12: ...water drainage channel around the foundation to con densate waste water from around the unit If the unit is to be installed on a roof check the strength of the roof and its drainage facilities first M...

Page 13: ...After the test run has been completed inspect the strainer at the inlet piping of the outside unit Clean it if it is dirty 7 3 Daily service and maintenance 1 Management of water quality The plate typ...

Page 14: ...rinse the inner part of the plate type heat exchanger with care using fresh and clean water 6 When using any cleaning agent sold in the market check in advance that such agent has no corrosive featur...

Page 15: ...re and close the cover firmly WARNING Never connect power supply wiring to the terminal block for remote controller wiring as this could damage the entire system Picking power supply and transmission...

Page 16: ...upply to transmission wiring terminal block Otherwise the entire system may break down Refer to figure 14 1 Branch 2 Subbranching For low noise operation it is necessary to get the optional Exter nal...

Page 17: ...th a non return valve 2 Make sure the pump oil does not flow oppositely into the system while the pump is not working 3 Use a vacuum pump which can evacuate to 500 microns 9 1 Selection of piping mate...

Page 18: ...ide of the flares and turn them three or four times at first Use ester oil or ether oil See the following table for tightening torque Applying too much torque may cause the flares to crack After all t...

Page 19: ...ween the outside unit connection piping kit or between the outside units exceeds 80 in 2m create a rise of 8 in 200mm or more in the gas piping within a length of 80 in 2m from the kit Pattern 1 Patte...

Page 20: ...i 23 3 lbs Total length ft m of liquid piping size at 7 8 0 235 lbs ft 0 37 N m Total length ft m of liquid piping size at 3 8 Total length ft m of liquid piping size at 1 4 Total length ft m of liqui...

Page 21: ...r unit etc this must be prevented by caulking the connections etc WARNING Be sure to insulate connection piping as touching them can cause burns 9 8 Checking of device and installation conditions Be s...

Page 22: ...alve operation procedure CAUTION Do not open the stop valve until 1 6 of 9 8 Checking of device and installation conditions are completed If the stop valve is left open without turning on power supply...

Page 23: ...ings made on a sub unit will be ignored After this close the control box cover Always perform configuration after turning ON the power supply To learn the setting method refer to the Service Precautio...

Page 24: ...Default value 3 Change 2 9 1 3 or 6 in function of required operation method during heating Malfunc tion code Installation error Remedial action E3 E4 F3 F6 UF U2 The stop valve of an out side unit i...

Page 25: ...stem containing a high sensible solution To activate this setting under heating operation change field set ting 2 9 to the appropriate value matching the requirements of the pre designed system contai...

Page 26: ...vate the mild comfort setting under heating operation change field setting 2 52 1 This setting is used in conjunction with setting 2 9 Eco The original refrigerant temperature target which is defined...

Page 27: ...imum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the amount of refrigerant lbs kg charged to each sys tem separately NOTE Wher...

Page 28: ...3P365916 17C EM14A009A 1503 HT...

Reviews: