• When wiring, position the wires so that the control box cover 

can be securely fastened. Improper positioning of the control 
box cover may result in electric shocks, fire, or the terminals 
overheating.

• Before touching electrical parts, turn off the unit.

• This equipment can be installed with a Ground-Fault Circuit 

Interrupter (GFCI). Although this is a recognized measure for 
additional protection, with the grounding system in North 
America, a dedicated GFCI may not be necessary.

• Securely fasten the outside unit terminal cover (panel). If the 

terminal cover/panel is not installed properly, dust or water 
may enter the outside unit causing fire or electric shock.

• When installing or relocating the system, keep the refrigerant 

circuit free from substances other than the specified refriger-
ant (R410A) such as air. Any presence of air or other foreign 
substance in the refrigerant circuit can cause an abnormal 
pressure rise or rupture, resulting in injury.

• Do not change the setting of the protection devices. If the 

pressure switch, thermal switch, or other protection device is 
shorted and operated forcibly, or parts other than those spec-
ified by Daikin are used, fire or explosion may occur.

CAUTION

• Do not touch the switch with wet fingers. Touching a switch

with wet fingers can cause electric shock.

• Do not allow children to play on or around the unit to prevent 

injury.

• Do not touch the refrigerant pipes during and immediately af-

ter operation as the refrigerant pipes may be hot or cold, de-
pending on the condition of the refrigerant flowing through 
the refrigerant piping, compressor, and other refrigerant cycle 
parts. Your hands may suffer burns or frostbite if you touch 
the refrigerant pipes. To avoid injury, give the pipes time to re-
turn to normal temperature or, if you must touch them, be sure 
to wear proper gloves.

• Heat exchanger fins are sharp enough to cut.

To avoid injury wear glove or cover the fins when working 
around them.

• Install drain piping to proper drainage. Improper drain piping 

may result in water leakage and property damage.

• Insulate piping to prevent condensation.

• Be careful when transporting the product.

• Do not turn off the power supply immediately after stopping 

operation. Always wait for at least 5 minutes before turning off 
the power supply. Otherwise, water leakage may occur.

• Do not use a charging cylinder. Using a charging cylinder may 

cause the refrigerant to deteriorate.

• Refrigerant R410A in the system must be kept clean, dry, and 

tight.

(a) Clean and Dry -- Foreign materials (including mineral oils 

such as SUNISO oil or moisture) should be prevented from 
getting into the system.

(b) Tight -- R410A does not contain any chlorine, does not 

destroy the ozone layer, and does not reduce the earth’s pro-
tection again harmful ultraviolet radiation. R410A can con-
tribute to the greenhouse effect if it is released. Therefore 
take proper measures to check for the tightness of the refrig-
erant piping installation. Read the chapter Refrigerant Pip-
ing and follow the procedures.

• Since R410A is a blend, the required additional refrigerant 

must be charged in its liquid state. If the refrigerant is charged 
in a state of gas, its composition can change and the system 
will not work properly.

• The indoor unit is for R410A. See the catalog for indoor mod-

els that can be connected. Normal operation is not possible 
when connected to other units.

• Remote controller (wireless kit) transmitting distance can be 

shorter than expected in rooms with electronic fluorescent 
lamps (inverter or rapid start types). Install the indoor unit far 
away from fluorescent lamps as much as possible.

• Indoor and outside units are for indoor installation only.

• Do not install the air conditioner in the following locations:

(a) Where a mineral oil mist or oil spray or vapor is produced, 

for example, in a kitchen.
Plastic parts may deteriorate and fall off or result in water 
leakage.

(b) Where corrosive gas, such as sulfurous acid gas, is pro-

duced.
Corroding copper pipes or soldered parts may result in 
refrigerant leakage.

(c) Near machinery emitting electromagnetic waves.

Electromagnetic waves may disturb the operation of the 
control system and cause the unit to malfunction.

(d) Where flammable gas may leak, where there is carbon fiber, 

or ignitable dust suspension in the air, or where volatile 
flammables such as thinner or gasoline are handled. Operat-
ing the unit in such conditions can cause a fire.

• Take adequate measures to prevent the outside unit from be-

ing used as a shelter by small animals. Small animals making 
contact with electrical parts can cause malfunctions, smoke, 
or fire. Instruct the customer to keep the area around the unit 
clean.

NOTE

• Install the power supply and transmission wires for the indoor 

and outside units at least 3.5 feet (1 m) away from televisions 
or radios to prevent image interference or noise. Depending 
on the radio waves, a distance of 3.5 feet (1 m) may not be suf-
ficient to eliminate the noise.

• Dismantling the unit, treatment of the refrigerant, oil and addi-

tional parts must be done in accordance with the relevant lo-
cal, state, and national regulations.

• Do not use the following tools that are used with conventional 

refrigerants: gauge manifold, charge hose, gas leak detector, 
reverse flow check valve, refrigerant charge base, vacuum 
gauge, or refrigerant recovery equipment.

• If the conventional refrigerant and refrigerator oil are mixed in 

R410A, the refrigerant may deteriorate.

• This air conditioner is an appliance that should not be acces-

sible to the general public.

• The wall thickness of field-installed pipes should be selected 

in accordance with the relevant local, state, and national reg-
ulations.

Codes and Regulations

This product is designed and manufactured to comply with national 
codes. Installation in accordance with such codes and/or prevailing 
local codes/regulations is the responsibility of the installer. The manu-
facturer assumes no responsibility for equipment installed in violation of 
any codes or regulations. Rated performance is achieved after charge 
adjustment (sub-cooling of 14±1°F (8±0.5°C) and superheat of 3±1°F 
(1.7±0.5°C)) and 72 hours of operation.

01_EN_3P365916_17C.fm  Page 2  Thursday, March 12, 2015  10:47 AM

Summary of Contents for RWEYQ144PCTJ

Page 1: ...ion Keep this manual in a handy place for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de ma...

Page 2: ...100 9 13 16 250 21 5 8 550 30 11 16 780 9 9 5 5 8 10 8 9 7 7 6 6 6 9 7 5 8 5 8 15 3 8 390 4 3 1 2 11 13 16 300 39 3 8 1000 35 7 16 900 19 11 16 500 Unit in mm 1 2 3 4 4 9 3 5 3 4 8 5 6 6 9 7 1 2 3 4...

Page 3: ...2 Q1 Q2 A1P F1 F2 F1 F2 Q1 Q2 A B C C H SELECTOR A5P 12 A B C C H SELECTOR A5P A B C A B C RWEYQ PCYD figure 10 A B C A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5...

Page 4: ...1 Q2 Q1 Q2 Q1 Q2 A1P A5P 1 4 8 9 5 6 6 6 2 3 RWEYQ PCYD A B C 7 1 4 5 2 3 3 4 3 X2M X1M F1 F2 F1 F2 Q1 Q2 X3M A1P A5P 1 2 RWEYQ PCYD A B C figure 13 figure 12 figure 11 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 Q...

Page 5: ...em Heat recovery system 1 2 3 4 5 6 7 8 9 10 11 5 4 12 14 15 16 17 13 figure 17 A B C A B C 1 2 DS1 1 2 3 4 OFF ON O U T I N A1P A5P RWEYQ PCYD A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N A1P RWEYQ PCT...

Page 6: ...system 4 5 3 2 1 figure 24 1 11 1 2 2 4 3 4 3 5 5 R410A R410A 9 7 7 8 13 9 6 6 16 10 10 10 10 17 12 12 14 15 15 18 18 Heat pump system Heat recovery system 1 2 3 4 figure 26 figure 27 figure 23 1 15...

Page 7: ...d to alert against unsafe practices NOTE Indicates situations that may result in equipment or property damage accidents only DANGER Refrigerant gas is heavier than air and replaces oxygen A massive le...

Page 8: ...r Refrigerant Pip ing and follow the procedures Since R410A is a blend the required additional refrigerant must be charged in its liquid state If the refrigerant is charged in a state of gas its compo...

Page 9: ...5 F 20 35 C Water flow rate 15 9gpm 60L min or more During cooling operation when the outside temperature is very low it is possible that the thermostat switches off automatically in order to protect...

Page 10: ...ead Drain pipe in 1 2FPS 2 female Thread 1 2FPS 2 female Thread General RWEYQ216PCYD CTJ RWEYQ252PCYD CTJ Nominal cooling capacity 2 MBH 216 252 Nominal heating capacity 3 MBH 243 283 5 Nominal input...

Page 11: ...hazard could occur leading to serious injury or death Re fer to the chapter Caution for refrigerant leaks NOTE 1 An inverter air conditioner may cause electronic noise generated from AM broadcasting...

Page 12: ...water drainage channel around the foundation to con densate waste water from around the unit If the unit is to be installed on a roof check the strength of the roof and its drainage facilities first M...

Page 13: ...After the test run has been completed inspect the strainer at the inlet piping of the outside unit Clean it if it is dirty 7 3 Daily service and maintenance 1 Management of water quality The plate typ...

Page 14: ...rinse the inner part of the plate type heat exchanger with care using fresh and clean water 6 When using any cleaning agent sold in the market check in advance that such agent has no corrosive featur...

Page 15: ...re and close the cover firmly WARNING Never connect power supply wiring to the terminal block for remote controller wiring as this could damage the entire system Picking power supply and transmission...

Page 16: ...upply to transmission wiring terminal block Otherwise the entire system may break down Refer to figure 14 1 Branch 2 Subbranching For low noise operation it is necessary to get the optional Exter nal...

Page 17: ...th a non return valve 2 Make sure the pump oil does not flow oppositely into the system while the pump is not working 3 Use a vacuum pump which can evacuate to 500 microns 9 1 Selection of piping mate...

Page 18: ...ide of the flares and turn them three or four times at first Use ester oil or ether oil See the following table for tightening torque Applying too much torque may cause the flares to crack After all t...

Page 19: ...ween the outside unit connection piping kit or between the outside units exceeds 80 in 2m create a rise of 8 in 200mm or more in the gas piping within a length of 80 in 2m from the kit Pattern 1 Patte...

Page 20: ...i 23 3 lbs Total length ft m of liquid piping size at 7 8 0 235 lbs ft 0 37 N m Total length ft m of liquid piping size at 3 8 Total length ft m of liquid piping size at 1 4 Total length ft m of liqui...

Page 21: ...r unit etc this must be prevented by caulking the connections etc WARNING Be sure to insulate connection piping as touching them can cause burns 9 8 Checking of device and installation conditions Be s...

Page 22: ...alve operation procedure CAUTION Do not open the stop valve until 1 6 of 9 8 Checking of device and installation conditions are completed If the stop valve is left open without turning on power supply...

Page 23: ...ings made on a sub unit will be ignored After this close the control box cover Always perform configuration after turning ON the power supply To learn the setting method refer to the Service Precautio...

Page 24: ...Default value 3 Change 2 9 1 3 or 6 in function of required operation method during heating Malfunc tion code Installation error Remedial action E3 E4 F3 F6 UF U2 The stop valve of an out side unit i...

Page 25: ...stem containing a high sensible solution To activate this setting under heating operation change field set ting 2 9 to the appropriate value matching the requirements of the pre designed system contai...

Page 26: ...vate the mild comfort setting under heating operation change field setting 2 52 1 This setting is used in conjunction with setting 2 9 Eco The original refrigerant temperature target which is defined...

Page 27: ...imum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the amount of refrigerant lbs kg charged to each sys tem separately NOTE Wher...