background image

English

9

8-3 General

• Make sure to connect the power supply wire to the power supply ter-

minal block and to clamp it as shown in figure 8, chapter “Field wiring 
connection”.

• As this unit is equipped with an inverter, installing a phase advancing 

capacitor will not only reduce the power factor improvement effect, 
but also may cause the capacitor to overheat due to high-frequency 
waves. Therefore, never install a phase advancing capacitor.

• Keep power supply imbalance within 2% of the supply rating.

1.

Large imbalance will shorten the life of the smoothing capacitor.

2.

As a protective measure, the product will stop operating and an 
error indication will be made, when power supply imbalance 
exceeds 4% of the supply rating.

• Follow the “wiring diagram” when carrying out any electrical wiring.
• Only proceed with wiring work after blocking off all power supply.
• Always ground wires. (In accordance with national regulations of the 

pertinent country.)

This unit uses an inverter, and therefore generates noise, which will
have to be reduced to avoid interfering with other devices. The outer
casing of the product may take on an electrical charge due to leaked
electrical current, which will have to be discharged with the ground-
ing.

This unit has a negative phase protection circuit. (If it operates, only
operate the unit after correcting the wiring.)

WARNING

• Do not ground units to gas pipes, sewage pipes, lightning rods, or 

telephone ground wires because incomplete grounding could 
cause a severe shock hazard resulting in severe injury or death.

Gas pipes:

 can explode or catch fire if there is a gas leak.

Sewage pipes:

 no grounding effect is possible if hard plastic pip-

ing is used.

Telephone ground wires and lightning rods:

 dangerous when 

struck by lightning due to an abnormal rise in electrical potential in 
the grounding.

8-4 Examples

System example (Refer to figure 8)

1.

Field power supply

2.

Main switch

3.

Disconnect switch

4.

Fuse

5.

Remote controller

6.

Outside unit

7.

Branch Selector unit

8.

Indoor unit

9.

Cool/Heat selector

power supply wiring (sheathed wire)

transmission wiring (sheathed wire)

CAUTION

• Use a conduit for the power supply wiring.
• Outside the unit, make sure the low-voltage electric wiring (i.e. for the 

remote controller, transmission, etc.) and the high-voltage electric wir-
ing do not pass near each other, keeping them at least 5 in. apart. Prox-
imity may cause electrical interference, malfunctions, and breakage.

• Be sure to connect the power supply wiring to the power supply ter-

minal block and secure it as described in 

Field wiring connection

.

• Transmission wiring should be secured as described in

 Field wiring 

connection.

• Secure the wiring with the accessory clamps so that it does not touch 

the piping.

• Make sure the wiring and the control box cover do not stick up above 

the structure, and close the cover firmly.

WARNING

Never connect power supply wiring to the terminal block for remote 
controller wiring as this could damage the entire system.

Picking power supply and transmission wiring

(Refer to figure 9)

1.

Power supply wiring and wiring for pump operation 
(High voltage)

2.

Transmission wiring
(Low voltage)

3.

Set apart

Connect the wire to the terminal block on printed circuit board with care 
since too much pressure may cause breakage of the printed circuit board.
Field wiring connection: transmission wiring, interlock circuit, pump 
operation output and Cool/Heat selector.
Power supply and transmission wiring: Connect it using conduit 
mounting plates.

[In case of single outside unit]

(Refer to figure 10)

1.

Cool/Heat selector

2.

Printed circuit board (A1P)

3.

Take care of the polarity

4.

Use the conductor of sheathed wire (2 wire) (no polarity)

5.

Terminal board (field supply)

6.

Indoor unit

7.

Never connect the power supply wire.

8.

Branch Selector unit A

9.

Branch Selector unit B

10.

Last Branch Selector unit

11.

Cooling only unit

12.

ABC I/P printed circuit board (A5P)

[In case of multiple outside units]

(Refer to figure 11)

1.

Unit A (Master unit)

2.

Unit B

3.

Unit C

4.

TO IN/D UNIT

5.

TO OUT/D UNIT

6.

TO MULTI UNIT

7.

To Cool/Heat selector (only Heat pump system)

8.

To indoor unit

9.

To other systems

• The transmission wiring between the outside units in the same pipe 

line must be connected to the Q1/Q2 (TO MULTI UNIT) terminals.
Connecting the wires to the F1/F2 (TO OUT/D UNIT) terminals 
results in system malfunction.

• The wiring for the other pipe line must be connected to the F1/F2 (TO 

OUT/D UNIT) terminals of the printed circuit board in the outside unit 
to which the transmission wiring for the indoor units is connected.

• The outside unit to which the transmission wiring for the indoor units 

is connected is master unit.

• The transmission wiring between the outside units must be 98 ft. 

(30 m) in length at maximum.

NOTE

• Be sure to keep the power supply and transmission wiring apart from 

each other.
Be careful about polarity of the transmission wiring.
Make sure that the transmission wiring is clamped as shown in the 
figure in chapter “Field wiring connection”.
Check that wiring does not make contact with refrigerant piping.
Firmly close the cover and arrange the electric wires so as to prevent 
the cover or other parts from coming loose.

[Setting the interlock circuit and pump operation output.]

Pump operation output [high voltage]

• Use insulated wires of the size as mentioned below having rated volt-

age of 250 V or more:
For single core: AWG16 or larger (conduit pipe work)
For multiple cores: AWG18 or larger

 *The wiring for pump operation output is to be procured locally.

(Refer to figure 12)

1.

Pump operation output terminal (X2M).
When water pump is linked with system operation, water 
pump operation circuit shall be set between terminals (1) 
and (2).
Contact specification --- 220 VAC, 3 mA-0.5 A

Top plate

Conduit 
(field supply)

Lock nut 
(field supply)

Conduit 
mounting 
plate 
(accessory)

Top plate

01_EN_3P365916_17C.fm  Page 9  Thursday, March 12, 2015  10:47 AM

Summary of Contents for RWEYQ144PCTJ

Page 1: ...ion Keep this manual in a handy place for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de ma...

Page 2: ...100 9 13 16 250 21 5 8 550 30 11 16 780 9 9 5 5 8 10 8 9 7 7 6 6 6 9 7 5 8 5 8 15 3 8 390 4 3 1 2 11 13 16 300 39 3 8 1000 35 7 16 900 19 11 16 500 Unit in mm 1 2 3 4 4 9 3 5 3 4 8 5 6 6 9 7 1 2 3 4...

Page 3: ...2 Q1 Q2 A1P F1 F2 F1 F2 Q1 Q2 A B C C H SELECTOR A5P 12 A B C C H SELECTOR A5P A B C A B C RWEYQ PCYD figure 10 A B C A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5...

Page 4: ...1 Q2 Q1 Q2 Q1 Q2 A1P A5P 1 4 8 9 5 6 6 6 2 3 RWEYQ PCYD A B C 7 1 4 5 2 3 3 4 3 X2M X1M F1 F2 F1 F2 Q1 Q2 X3M A1P A5P 1 2 RWEYQ PCYD A B C figure 13 figure 12 figure 11 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 Q...

Page 5: ...em Heat recovery system 1 2 3 4 5 6 7 8 9 10 11 5 4 12 14 15 16 17 13 figure 17 A B C A B C 1 2 DS1 1 2 3 4 OFF ON O U T I N A1P A5P RWEYQ PCYD A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N A1P RWEYQ PCT...

Page 6: ...system 4 5 3 2 1 figure 24 1 11 1 2 2 4 3 4 3 5 5 R410A R410A 9 7 7 8 13 9 6 6 16 10 10 10 10 17 12 12 14 15 15 18 18 Heat pump system Heat recovery system 1 2 3 4 figure 26 figure 27 figure 23 1 15...

Page 7: ...d to alert against unsafe practices NOTE Indicates situations that may result in equipment or property damage accidents only DANGER Refrigerant gas is heavier than air and replaces oxygen A massive le...

Page 8: ...r Refrigerant Pip ing and follow the procedures Since R410A is a blend the required additional refrigerant must be charged in its liquid state If the refrigerant is charged in a state of gas its compo...

Page 9: ...5 F 20 35 C Water flow rate 15 9gpm 60L min or more During cooling operation when the outside temperature is very low it is possible that the thermostat switches off automatically in order to protect...

Page 10: ...ead Drain pipe in 1 2FPS 2 female Thread 1 2FPS 2 female Thread General RWEYQ216PCYD CTJ RWEYQ252PCYD CTJ Nominal cooling capacity 2 MBH 216 252 Nominal heating capacity 3 MBH 243 283 5 Nominal input...

Page 11: ...hazard could occur leading to serious injury or death Re fer to the chapter Caution for refrigerant leaks NOTE 1 An inverter air conditioner may cause electronic noise generated from AM broadcasting...

Page 12: ...water drainage channel around the foundation to con densate waste water from around the unit If the unit is to be installed on a roof check the strength of the roof and its drainage facilities first M...

Page 13: ...After the test run has been completed inspect the strainer at the inlet piping of the outside unit Clean it if it is dirty 7 3 Daily service and maintenance 1 Management of water quality The plate typ...

Page 14: ...rinse the inner part of the plate type heat exchanger with care using fresh and clean water 6 When using any cleaning agent sold in the market check in advance that such agent has no corrosive featur...

Page 15: ...re and close the cover firmly WARNING Never connect power supply wiring to the terminal block for remote controller wiring as this could damage the entire system Picking power supply and transmission...

Page 16: ...upply to transmission wiring terminal block Otherwise the entire system may break down Refer to figure 14 1 Branch 2 Subbranching For low noise operation it is necessary to get the optional Exter nal...

Page 17: ...th a non return valve 2 Make sure the pump oil does not flow oppositely into the system while the pump is not working 3 Use a vacuum pump which can evacuate to 500 microns 9 1 Selection of piping mate...

Page 18: ...ide of the flares and turn them three or four times at first Use ester oil or ether oil See the following table for tightening torque Applying too much torque may cause the flares to crack After all t...

Page 19: ...ween the outside unit connection piping kit or between the outside units exceeds 80 in 2m create a rise of 8 in 200mm or more in the gas piping within a length of 80 in 2m from the kit Pattern 1 Patte...

Page 20: ...i 23 3 lbs Total length ft m of liquid piping size at 7 8 0 235 lbs ft 0 37 N m Total length ft m of liquid piping size at 3 8 Total length ft m of liquid piping size at 1 4 Total length ft m of liqui...

Page 21: ...r unit etc this must be prevented by caulking the connections etc WARNING Be sure to insulate connection piping as touching them can cause burns 9 8 Checking of device and installation conditions Be s...

Page 22: ...alve operation procedure CAUTION Do not open the stop valve until 1 6 of 9 8 Checking of device and installation conditions are completed If the stop valve is left open without turning on power supply...

Page 23: ...ings made on a sub unit will be ignored After this close the control box cover Always perform configuration after turning ON the power supply To learn the setting method refer to the Service Precautio...

Page 24: ...Default value 3 Change 2 9 1 3 or 6 in function of required operation method during heating Malfunc tion code Installation error Remedial action E3 E4 F3 F6 UF U2 The stop valve of an out side unit i...

Page 25: ...stem containing a high sensible solution To activate this setting under heating operation change field set ting 2 9 to the appropriate value matching the requirements of the pre designed system contai...

Page 26: ...vate the mild comfort setting under heating operation change field setting 2 52 1 This setting is used in conjunction with setting 2 9 Eco The original refrigerant temperature target which is defined...

Page 27: ...imum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the amount of refrigerant lbs kg charged to each sys tem separately NOTE Wher...

Page 28: ...3P365916 17C EM14A009A 1503 HT...

Reviews: