background image

6

English

WARNING

Do not install in the following locations.

• Locations such as kitchens which contain a lot of mineral oil or steam 

in the atmosphere or where oil may splatter on the unit.
Resin parts may deteriorate, causing the unit to fall or leak.

• Locations where sulfurous acids and other corrosive gases may be 

present in the atmosphere.
Copper piping and soldered joints may corrode, causing refrigerant 
to leak.

• Locations where equipment that produces electromagnetic waves is 

found.
The electromagnetic waves may cause the control system to mal-
function, preventing normal operation.

4.

INSPECTING AND HANDLING THE UNIT

At delivery, the package should be checked and any damage should be 
reported immediately to the carrier claims agent.

When handling the unit, take into account the following:

1.

Fragile, handle the unit with care.

Keep the unit upright in order to avoid compressor damage.

2.

Choose the path along which the unit is to be brought in ahead of 
time.

3.

In order to prevent any damage to the unit during installation, use 
slings (cloth) or patch plates and lift the unit referring to figure 4.

4.

Lift the unit preferably with a crane and 2 belts of at least 27 ft. (8 m)  
long.

5.

When lifting the unit with a crane, always use protectors to prevent 
belt damage and pay attention to the position of the unit’s center of 
gravity.

6.

Be sure use the standard supplied accessories and dedicated parts 
as installation parts.

(Refer to figure 4)

1.

Patch plates or clothes

2.

Belt sling

NOTE

Use belt sling of 13/16 in. (20 mm) width or less which adequately 
bears the weight of the product. 

5.

UNPACKING AND PLACING THE UNIT

• Make sure the area around the machine drains properly by setting up 

drainage grooves around the foundation.

• Make sure the unit is installed level on a sufficiently strong base to 

prevent vibration and noise.

• Secure the unit to its base using foundation bolts. (Use four commer-

cially available 7/16 in. (M12) foundation bolts, nuts, and washers.)

• The foundation bolt should protrude 13/16 in. 

(20 mm) from the foundation surface. 

• Fix 4 foundation bolts.
• Support the unit with the foundation which is 

larger than the hatched area shown in figure 5.

(Refer to figure 5)

1.

Front side

2.

Position of foundation bolts

3.

Hole for a foundation bolt
(

φ

11/16 in. (17 mm) holes at 4 corners)

4.

Avoid such a foundation where the unit is supported by 
4 corner points.

NOTE

In unavoidable circumstances, where the unit has to be installed 
either touching or close to a wall; place the unit such that transmis-
sion of vibration can be restricted or minimized. Vibrations can be 
dampened by using cushions, foam etc.

NOTE

Prepare a water drainage channel around the foundation to con-
densate waste water from around the unit.

If the unit is to be installed on a roof, check the strength of the roof 
and its drainage facilities first.

Make sure the area around the machine drains properly by setting up 
drainage grooves around the foundation.
(Condensate water is sometimes discharged from the outside unit 
when it is running.)

Use a nut with a resin clip plate to protect the nut tightening part from 
rusting.

6.

WATER PIPING WORK

• The water pressure resistance of water piping of this outside unit is 

285 psig.

• The connection port for water piping is located in the front. The con-

nection ports for drain piping are located in the front and back. When 
using the back port, change the cast iron plug from the back to the 
front and securely close it.

• In indoor use, piping work should be such that now water drops on 

the outer plate.

• The lateral protruding section of the drain piping should be short 

(within 15-3/4 in. (400 mm)) and installed in a downward direction. 
The diameter of drain pipe should be the same as the diameter of 
unit connection (1/2 in.) or more.

• The diameter of water pipe should be the same as the diameter of 

unit connection (1-1/4 in.) or more.

• Install an air purge valve in the midway of the water piping to prevent 

cavitation.

• After completing the drain piping work, make sure that the water runs 

smoothly without any clogging by dust.

• Do not connect the drain outlet to the water outlet.
• Install a strainer (50 mesh or more) in the inlet of water piping within 

a distance of 4.9 ft. (1.5 m) from the outside unit. 
(If sand, waste or rust particles are mixed in the water circulation 
system, metal materials will become corrosive.)

• Install insulation on the inlet/outlet of water piping to prevent conden-

sation and freezing.
At installing insulation on water in/outlet pipe, use Polyurethane form 
thickness 3/16 in. (5 mm) for insulation of water piping socket on heat 
exchanger.

• Install insulation up to the base of heat exchanger as shown in the 

figure 6.

• Install a gate valve for chemical cleaning in an easy position to han-

dle.

• Use water pipes compliant with the local and national codes.
• Run the water pump to flush inside of water piping.

Then, clean the strainer.

• If there is a possibility of freezing, take measures to prevent freezing.
• Tighten securely the connection of water piping and socket with 

tightening torque of 220 ft.·lbf. (300 N·m) or less.
(If a large torque is applied, the unit may be damaged.)

(Refer to figure 6)

1.

Air purge

2.

Outlet of water

3.

Inlet of water

4.

Gate valve

5.

Water piping socket

6.

Water piping

7.

Insulation

8.

Heat exchanger

9.

Strainer

10.

Drain valve

11.

Connection port to draining piping

12.

Insulation cover

13.

3-1/8 in. (80 mm) or less

14.

Insulation of water piping socket

15.

Drain piping

13/16 in.

(20 mm)

Resin clip plate

01_EN_3P365916_17C.fm  Page 6  Thursday, March 12, 2015  10:47 AM

Summary of Contents for RWEYQ144PCTJ

Page 1: ...ion Keep this manual in a handy place for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de ma...

Page 2: ...100 9 13 16 250 21 5 8 550 30 11 16 780 9 9 5 5 8 10 8 9 7 7 6 6 6 9 7 5 8 5 8 15 3 8 390 4 3 1 2 11 13 16 300 39 3 8 1000 35 7 16 900 19 11 16 500 Unit in mm 1 2 3 4 4 9 3 5 3 4 8 5 6 6 9 7 1 2 3 4...

Page 3: ...2 Q1 Q2 A1P F1 F2 F1 F2 Q1 Q2 A B C C H SELECTOR A5P 12 A B C C H SELECTOR A5P A B C A B C RWEYQ PCYD figure 10 A B C A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5...

Page 4: ...1 Q2 Q1 Q2 Q1 Q2 A1P A5P 1 4 8 9 5 6 6 6 2 3 RWEYQ PCYD A B C 7 1 4 5 2 3 3 4 3 X2M X1M F1 F2 F1 F2 Q1 Q2 X3M A1P A5P 1 2 RWEYQ PCYD A B C figure 13 figure 12 figure 11 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 Q...

Page 5: ...em Heat recovery system 1 2 3 4 5 6 7 8 9 10 11 5 4 12 14 15 16 17 13 figure 17 A B C A B C 1 2 DS1 1 2 3 4 OFF ON O U T I N A1P A5P RWEYQ PCYD A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N A1P RWEYQ PCT...

Page 6: ...system 4 5 3 2 1 figure 24 1 11 1 2 2 4 3 4 3 5 5 R410A R410A 9 7 7 8 13 9 6 6 16 10 10 10 10 17 12 12 14 15 15 18 18 Heat pump system Heat recovery system 1 2 3 4 figure 26 figure 27 figure 23 1 15...

Page 7: ...d to alert against unsafe practices NOTE Indicates situations that may result in equipment or property damage accidents only DANGER Refrigerant gas is heavier than air and replaces oxygen A massive le...

Page 8: ...r Refrigerant Pip ing and follow the procedures Since R410A is a blend the required additional refrigerant must be charged in its liquid state If the refrigerant is charged in a state of gas its compo...

Page 9: ...5 F 20 35 C Water flow rate 15 9gpm 60L min or more During cooling operation when the outside temperature is very low it is possible that the thermostat switches off automatically in order to protect...

Page 10: ...ead Drain pipe in 1 2FPS 2 female Thread 1 2FPS 2 female Thread General RWEYQ216PCYD CTJ RWEYQ252PCYD CTJ Nominal cooling capacity 2 MBH 216 252 Nominal heating capacity 3 MBH 243 283 5 Nominal input...

Page 11: ...hazard could occur leading to serious injury or death Re fer to the chapter Caution for refrigerant leaks NOTE 1 An inverter air conditioner may cause electronic noise generated from AM broadcasting...

Page 12: ...water drainage channel around the foundation to con densate waste water from around the unit If the unit is to be installed on a roof check the strength of the roof and its drainage facilities first M...

Page 13: ...After the test run has been completed inspect the strainer at the inlet piping of the outside unit Clean it if it is dirty 7 3 Daily service and maintenance 1 Management of water quality The plate typ...

Page 14: ...rinse the inner part of the plate type heat exchanger with care using fresh and clean water 6 When using any cleaning agent sold in the market check in advance that such agent has no corrosive featur...

Page 15: ...re and close the cover firmly WARNING Never connect power supply wiring to the terminal block for remote controller wiring as this could damage the entire system Picking power supply and transmission...

Page 16: ...upply to transmission wiring terminal block Otherwise the entire system may break down Refer to figure 14 1 Branch 2 Subbranching For low noise operation it is necessary to get the optional Exter nal...

Page 17: ...th a non return valve 2 Make sure the pump oil does not flow oppositely into the system while the pump is not working 3 Use a vacuum pump which can evacuate to 500 microns 9 1 Selection of piping mate...

Page 18: ...ide of the flares and turn them three or four times at first Use ester oil or ether oil See the following table for tightening torque Applying too much torque may cause the flares to crack After all t...

Page 19: ...ween the outside unit connection piping kit or between the outside units exceeds 80 in 2m create a rise of 8 in 200mm or more in the gas piping within a length of 80 in 2m from the kit Pattern 1 Patte...

Page 20: ...i 23 3 lbs Total length ft m of liquid piping size at 7 8 0 235 lbs ft 0 37 N m Total length ft m of liquid piping size at 3 8 Total length ft m of liquid piping size at 1 4 Total length ft m of liqui...

Page 21: ...r unit etc this must be prevented by caulking the connections etc WARNING Be sure to insulate connection piping as touching them can cause burns 9 8 Checking of device and installation conditions Be s...

Page 22: ...alve operation procedure CAUTION Do not open the stop valve until 1 6 of 9 8 Checking of device and installation conditions are completed If the stop valve is left open without turning on power supply...

Page 23: ...ings made on a sub unit will be ignored After this close the control box cover Always perform configuration after turning ON the power supply To learn the setting method refer to the Service Precautio...

Page 24: ...Default value 3 Change 2 9 1 3 or 6 in function of required operation method during heating Malfunc tion code Installation error Remedial action E3 E4 F3 F6 UF U2 The stop valve of an out side unit i...

Page 25: ...stem containing a high sensible solution To activate this setting under heating operation change field set ting 2 9 to the appropriate value matching the requirements of the pre designed system contai...

Page 26: ...vate the mild comfort setting under heating operation change field setting 2 52 1 This setting is used in conjunction with setting 2 9 Eco The original refrigerant temperature target which is defined...

Page 27: ...imum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the amount of refrigerant lbs kg charged to each sys tem separately NOTE Wher...

Page 28: ...3P365916 17C EM14A009A 1503 HT...

Reviews: