background image

English

7

7.

HANDLING OF THE BRAZED PLATE-
TYPE HEAT EXCHANGER

CAUTION

A brazed plate-type heat exchanger is used for this unit. Because 
its structure is different from a conventional type heat exchanger, it 
must be handled in a different manner.

7-1 When designing the equipment

1.

Install a strainer (50 mesh or more) at the water inlet side adjacent to 
the outside unit in order to prevent any foreign materials such as 
dust, sand, etc. from entering.

2.

Depending on the water quality, scale may stick to the plate-type 
heat exchanger. In order to remove scale, it is necessary to use 
chemicals to clean it at regular intervals. To this end, install a gate 
valve in the water piping. Set up a piping connection port on the pip-
ing between this gate valve and the outside unit for cleaning by 
chemicals.

3.

For the purpose of cleaning and water drain-off from the outside unit 
(water draining during a long period of non-use in winter, draining 
upon starting of season-off), install an “air discharge valve” and a 
“water draining plug” at the inlet/outlet ports of water piping. In addi-
tion, install an “automatic air discharging valve” at the top of riser pip-
ing or at the top of a portion where air tends to stay.

4.

Independent of the piping inlet of the outside unit, install a cleanable 
strainer at a portion close to the pump piping inlet.

5.

Carry out complete cooling/thermal insulation of water piping and 
outdoor dehumidification. If complete cooling or thermal insulation 
has not been carried out, any damage may be caused during severe 
winter due to freezing, in addition to thermal loss.

6.

When you stop operation during night or winter, it is necessary to take 
measures to prevent water-related circuits from natural freezing in the 
area the ambient temperature drops below 32°F (0°C) (by water drain 
off, keeping the circulation pump running, warming up by a heater, 
etc.) Freezing of water related circuits may result in any damage to 
the plate-type heat exchanger. Therefore, take appropriate measures 
depending on the circumstances of use.

(Refer to figure 7)

1.

Example of piping

2.

Water inlet piping

3.

Strainer

4.

Air discharge valve (for joint use with cleaning port)

5.

Cleaning device

6.

Strainer for pump

7.

Automatic air discharge valve

8.

Water outlet piping

9.

Joint use with water draining plug

10.

Plate-type heat exchanger

11.

Outside unit

7-2 Before starting a test run

1.

Before starting a test run, please make sure that the piping work has 
been carried out in a proper manner. Especially, make sure that the 
strainer, air discharge valve, automatic water supply valve, expansion 
tank and cistern are positioned at their places correctly.

2.

After water has been completely filled in, first run the pump only, and 
then make sure that no air has been caught in the water circulation 
system and that the water flow rate is correct. If any air has been 
caught or the flow rate is not enough, the plate-type heat exchanger 
may freeze. Measure any water pressure loss before and after the 
outside unit and make sure that the flow rate is as designed. In case 
of any abnormality, stop the test run immediately and carry out trou-
ble shooting to resolve the trouble.

3.

Following the installation manual, carry out a test run of the outside 
unit.

4.

After the test run has been completed, inspect the strainer at the inlet 
piping of the outside unit. Clean it if it is dirty.

7-3 Daily service and maintenance

1.

Management of water quality
The plate-type heat exchanger has a structure that does not permit 
dismantling and cleaning, or replacing any parts. Please pay attention 
carefully to the quality of water to be used for the plate-type heat 
exchanger in order to prevent corrosion and sticking of scale.
The water to be used for the plate-type heat exchanger should have at 
least the quality as specified in the table below.
When using any corrosion prevention agent, scale depressant agent, 
etc., such agent should have no corrosive features against stainless 
steel and copper.

2.

Management of condenser water flow rate
If the condenser water flow rate is not enough, it will result in freezing 
damage to the plate-type heat exchanger. Check for any clogging of 
the strainer, any air being caught, any reduction in the flow rate due 
to failure of the circulation pump by measuring the temperature and 
pressure differences at the inlet and outlet ports of the plate-type 
heat exchanger. If the aged difference in the temperature or pressure 
has increased beyond the proper range, the flow rate should have 
decreased. Stop the operation and remove the cause before restart-
ing the operation.

3.

Steps to be taken if a freeze-protection device is activated
If the freeze-protection device is activated during operation, be sure 
to remove the cause before restarting the operation. If the freeze-pro-
tection device has been once activated, a partial freezing has already 
occurred. If you restart the operation without removing the cause, the 
plate-type heat exchanger will be closed and the ice cannot be 
melted, and in addition, the freezing process will be repeated, result-
ing in any damage to the plate-type heat exchanger, and this can lead 
to refrigerant leaking or water entering the refrigerant circuit.

7-4 Water quality

Water quality standards for condenser water, hot water and 
makeup water (4) (6)

Item (5)

Cooling water system (3)

Hot water system (2)

Tendency (1)

Circulation system

Circulation 

water

Makeup

water

Circulation 

water 

(68 to 140°F 

(20 to 60°C))

Makeup

water

Corrosion

Scale

Standard items

pH (77°F (25°C))

6.5 to 8.2 6.0 to 8.0 7.0 to 8.0 7.0 to 8.0

{

{

Electrical Conductivity

(mS/ft. (mS/m))
(77°F (25°C))

Less than 

24.4 (80)

Less than 

9.1 (30)

Less than 

9.1 (30)

Less than 

9.1 (30)

{

{

Chloride ions 
(mgcl

/L)

Less than 

200

Less than 

50

Less than 

50

Less than 

50

{

Sulfate ions 
(mgSO

4

2-

 /L)

Less than 

200

Less than 

50

Less than 

50

Less than 

50

{

Acid consumption 

(pH4.8) (mgCaCO

3

/L)

Less than 

100

Less than 

50

Less than 

50

Less than 

50

{

Total hardness 

(mgCaCO

3

/L)

Less than 

200

Less than 

70

Less than 

70

Less than 

70

{

Calcium hardness
(mgCaCO

3

/L)

Less than 

150

Less than 

50

Less than 

50

Less than 

50

{

Ionic-state silica 

(mgSiO

2

/L)

Less than 

50

Less than 

30

Less than 

30

Less than 

30

{

Reference items

Iron (mgFe/L)

Less than 

1.0

Less than 

0.3

Less than 

1.0

Less than 

0.3

{

{

Copper (mgCu/L)

Less than 

0.3

Less than 

0.1

Less than 

1.0

Less than 

0.1

{

Sulfate ion 
(mgS 

2-

 /L)

Shall not be 

detected

Shall not be 

detected

Shall not be 

detected

Shall not be 

detected

{

Ammonium ion 
(mgNH

4

+

/L)

Less than 

1.0

Less than 

0.1

Less than 

0.3

Less than 

0.1

{

Residual chlorine

(mgCl/L)

Less than 

0.3

Less than 

0.3

Less than 

0.25

Less than 

0.3

{

Free carbon dioxide 

(mgCO

2

/L)

Less than 

4.0

Less than 

4.0

Less than 

0.4

Less than 

4.0

{

Stability index

6.0 to 7.0

{

{

01_EN_3P365916_17C.fm  Page 7  Thursday, March 12, 2015  10:47 AM

Summary of Contents for RWEYQ144PCTJ

Page 1: ...ion Keep this manual in a handy place for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de ma...

Page 2: ...100 9 13 16 250 21 5 8 550 30 11 16 780 9 9 5 5 8 10 8 9 7 7 6 6 6 9 7 5 8 5 8 15 3 8 390 4 3 1 2 11 13 16 300 39 3 8 1000 35 7 16 900 19 11 16 500 Unit in mm 1 2 3 4 4 9 3 5 3 4 8 5 6 6 9 7 1 2 3 4...

Page 3: ...2 Q1 Q2 A1P F1 F2 F1 F2 Q1 Q2 A B C C H SELECTOR A5P 12 A B C C H SELECTOR A5P A B C A B C RWEYQ PCYD figure 10 A B C A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5...

Page 4: ...1 Q2 Q1 Q2 Q1 Q2 A1P A5P 1 4 8 9 5 6 6 6 2 3 RWEYQ PCYD A B C 7 1 4 5 2 3 3 4 3 X2M X1M F1 F2 F1 F2 Q1 Q2 X3M A1P A5P 1 2 RWEYQ PCYD A B C figure 13 figure 12 figure 11 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 Q...

Page 5: ...em Heat recovery system 1 2 3 4 5 6 7 8 9 10 11 5 4 12 14 15 16 17 13 figure 17 A B C A B C 1 2 DS1 1 2 3 4 OFF ON O U T I N A1P A5P RWEYQ PCYD A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N A1P RWEYQ PCT...

Page 6: ...system 4 5 3 2 1 figure 24 1 11 1 2 2 4 3 4 3 5 5 R410A R410A 9 7 7 8 13 9 6 6 16 10 10 10 10 17 12 12 14 15 15 18 18 Heat pump system Heat recovery system 1 2 3 4 figure 26 figure 27 figure 23 1 15...

Page 7: ...d to alert against unsafe practices NOTE Indicates situations that may result in equipment or property damage accidents only DANGER Refrigerant gas is heavier than air and replaces oxygen A massive le...

Page 8: ...r Refrigerant Pip ing and follow the procedures Since R410A is a blend the required additional refrigerant must be charged in its liquid state If the refrigerant is charged in a state of gas its compo...

Page 9: ...5 F 20 35 C Water flow rate 15 9gpm 60L min or more During cooling operation when the outside temperature is very low it is possible that the thermostat switches off automatically in order to protect...

Page 10: ...ead Drain pipe in 1 2FPS 2 female Thread 1 2FPS 2 female Thread General RWEYQ216PCYD CTJ RWEYQ252PCYD CTJ Nominal cooling capacity 2 MBH 216 252 Nominal heating capacity 3 MBH 243 283 5 Nominal input...

Page 11: ...hazard could occur leading to serious injury or death Re fer to the chapter Caution for refrigerant leaks NOTE 1 An inverter air conditioner may cause electronic noise generated from AM broadcasting...

Page 12: ...water drainage channel around the foundation to con densate waste water from around the unit If the unit is to be installed on a roof check the strength of the roof and its drainage facilities first M...

Page 13: ...After the test run has been completed inspect the strainer at the inlet piping of the outside unit Clean it if it is dirty 7 3 Daily service and maintenance 1 Management of water quality The plate typ...

Page 14: ...rinse the inner part of the plate type heat exchanger with care using fresh and clean water 6 When using any cleaning agent sold in the market check in advance that such agent has no corrosive featur...

Page 15: ...re and close the cover firmly WARNING Never connect power supply wiring to the terminal block for remote controller wiring as this could damage the entire system Picking power supply and transmission...

Page 16: ...upply to transmission wiring terminal block Otherwise the entire system may break down Refer to figure 14 1 Branch 2 Subbranching For low noise operation it is necessary to get the optional Exter nal...

Page 17: ...th a non return valve 2 Make sure the pump oil does not flow oppositely into the system while the pump is not working 3 Use a vacuum pump which can evacuate to 500 microns 9 1 Selection of piping mate...

Page 18: ...ide of the flares and turn them three or four times at first Use ester oil or ether oil See the following table for tightening torque Applying too much torque may cause the flares to crack After all t...

Page 19: ...ween the outside unit connection piping kit or between the outside units exceeds 80 in 2m create a rise of 8 in 200mm or more in the gas piping within a length of 80 in 2m from the kit Pattern 1 Patte...

Page 20: ...i 23 3 lbs Total length ft m of liquid piping size at 7 8 0 235 lbs ft 0 37 N m Total length ft m of liquid piping size at 3 8 Total length ft m of liquid piping size at 1 4 Total length ft m of liqui...

Page 21: ...r unit etc this must be prevented by caulking the connections etc WARNING Be sure to insulate connection piping as touching them can cause burns 9 8 Checking of device and installation conditions Be s...

Page 22: ...alve operation procedure CAUTION Do not open the stop valve until 1 6 of 9 8 Checking of device and installation conditions are completed If the stop valve is left open without turning on power supply...

Page 23: ...ings made on a sub unit will be ignored After this close the control box cover Always perform configuration after turning ON the power supply To learn the setting method refer to the Service Precautio...

Page 24: ...Default value 3 Change 2 9 1 3 or 6 in function of required operation method during heating Malfunc tion code Installation error Remedial action E3 E4 F3 F6 UF U2 The stop valve of an out side unit i...

Page 25: ...stem containing a high sensible solution To activate this setting under heating operation change field set ting 2 9 to the appropriate value matching the requirements of the pre designed system contai...

Page 26: ...vate the mild comfort setting under heating operation change field setting 2 52 1 This setting is used in conjunction with setting 2 9 Eco The original refrigerant temperature target which is defined...

Page 27: ...imum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the amount of refrigerant lbs kg charged to each sys tem separately NOTE Wher...

Page 28: ...3P365916 17C EM14A009A 1503 HT...

Reviews: