background image

English

19

[2-49]=  Te target temperature during simultaneous operation

Default value=5

Change [2-49]=2-7 in function of required operation method 
during simultaneous operation.

[2-51]=  Cooling comfort setting

Default value=1

Change [2-51]=0, 1, 2 or 3 in function of required limitation.
This setting is used in conjunction with setting [2-8].

[2-52]=  Heating comfort setting

Default value=1

Change [2-52]=0, 1, 2 or 3 in function of required limitation.
This setting is used in conjunction with setting [2-9].

Several patterns are available and explained below. Modify the param-
eters to the needs of your building and to realize the best balance 
between energy consumption and comfort.

12-1-1 Two main operation methods are available:

Automatic

The refrigerant temperature is set by default to a certain start value 
(defined by field setting). Depending on the load of the indoor units, 
the refrigerant temperature is adjusted. When there is a big/small 
load, according behaviour to match this load is executed.
Depending on the operation mode (cooling, heating or heat recov-
ery), field settings are available to define the standard refrigerant 
temperature start point. They are explained below.
E.g., when your system is operating in cooling, you do not need as 
much cooling under low ambient temperatures (e.g., 77°F (25°C)) as 
under high ambient temperatures (e.g., 95°F (35°C)).
Using this idea, the system automatically starts increasing its refrig-
erant temperature, automatically reducing the delivered capacity 
and increasing the system's efficiency based on indoor unit load 
feedback.

To define the start value during cooling operation, change field 
setting [2-8] = 5 (default; corresponding to Te = 48°F (9°C) to the 
required value).

E.g., when your system is operating in heating, you do not need as 
much heating under high ambient temperatures (e.g., 59°F (15°C)) 
as under low ambient temperatures (e.g., 23°F (–5°C)).
Using this idea, the system automatically starts decreasing its refrig-
erant temperature, automatically reducing the delivered capacity 
and increasing the system’s efficiency.

To define the start value during heating operation, change field 
setting [2-9] = 3 (default; corresponding to Tc = 109°F (43°C) to 
the required value).

When the system is used as a heat recovery system, the start refrig-
erant temperature during heat recovery mode for cooling can be 
selected differently than during cooling operation.
To define the start value for cooling operation during heat recovery 
operation, change field setting [2-49] = 5 (default; corresponding to 
Te = 48°F (9°C) to the required value).

Hi-sensible/economic (cooling/heating)

The refrigerant temperature is set higher/lower (cooling/heating) 
compared to basic operation. The focus under high sensible mode is 
comfort feeling for the customer.
The selection method of indoor units is important and has to be con-
sidered as the available capacity is not the same as under basic 
operation. For details concerning to Hi-sensible applications, please 
contact your dealer.

To activate this setting under cooling operation, change field set-
ting [2-8] to the appropriate value, matching the requirements of 
the pre-designed system containing a high sensible solution.

To activate this setting under heating operation, change field set-
ting [2-9] to the appropriate value, matching the requirements of 
the pre-designed system containing a high sensible solution.

To maintain the target settings, it is required to set the comfort setting to 
Eco.
The comfort modes are explained below.

12-1-2 Several comfort settings are available

For each of above modes a comfort level can be selected. The comfort 
level is related to the timing and the effort (energy consumption) which 
is put in achieving a certain room temperature by temporarily changing 
the refrigerant temperature to different values in order to achieve 
requested conditions more quickly.

Powerful

Overshoot (during heating operation) or undershoot (during cooling 
operation) is allowed compared to the requested refrigerant temper-
ature, in order to achieve the required room temperature very fast. 
The overshoot is allowed from the start up moment.
In case of cooling operation the evaporating temperature is allowed 
to go down to 37°F (3°C) on temporary base depending on the situ-
ation.
In case of heating operation the condense temperature is allowed to 
go up to 120°F (49°C) on temporary base depending on the situa-
tion.
When the request from the indoor units becomes more moderate, 
the system will eventually go to the steady state condition which is 
defined by the operation method above.

To activate the powerful comfort setting under cooling operation, 
change field setting [2-51]=3.
This setting is used in conjunction with setting [2-8].

To activate the powerful comfort setting under heating operation, 
change field setting [2-52]=3.
This setting is used in conjunction with setting [2-9].

Quick

Overshoot (during heating operation) or undershoot (during cooling 
operation) is allowed compared to the requested refrigerant temper-
ature, in order to achieve the required room temperature very fast. 
The overshoot is allowed from the start up moment.
In case of cooling operation the evaporating temperature is allowed 
to go down to 43°F (6°C) on temporary base depending on the situ-
ation.
In case of heating operation the condense temperature is allowed to 
go up to 115°F (46°C) on temporary base depending on the situa-
tion.
When the request from the indoor units becomes more moderate, 
the system will eventually go to the steady state condition which is 
defined by the operation method above.

To activate the quick comfort setting under cooling operation, 
change field setting [2-51]=2.
This setting is used in conjunction with setting [2-8].

To activate the quick comfort setting under heating operation, 
change field setting [2-52]=2.
This setting is used in conjunction with setting [2-9].

Te setting (simultaneous operation)

k k k

h h h

k

2. 43°F (6°C)

k

h h h h

k

h

3. 45°F (7°C)

k

h h h h

k k

4. 46°F (8°C)

k

h h h

k

h h

5. 48°F (9°C)(default)

k

h h h

k

h

k

6. 50°F (10°C)

k

h h h

k k

h

7. 52°F (11°C)

k

h h h

k k k

Cooling comfort setting

k k k

h h

k k

0. Eco

k

h h h h h h

1. Mild (default)

k

h h h h h

k

2. Quick

k

h h h h

k

h

3. Powerful

k

h h h h

k k

Heating comfort setting

k k k

h

k

h h

0. Eco

k

h h h h h h

1. Mild (default)

k

h h h h h

k

2. Quick

k

h h h h

k

h

3. Powerful

k

h h h h

k k

Value [2-8]

Te target

3

45°F (7°C)

4

46°F (8°C)

5

48°F (9°C)

6

50°F (10°C)

7

52°F (11°C)

Value [2-9]

Tc target

1

106°F (41°C)

3

109°F (43°C)

01_EN_3P365916_17C.fm  Page 19  Thursday, March 12, 2015  10:47 AM

Summary of Contents for RWEYQ144PCTJ

Page 1: ...ion Keep this manual in a handy place for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de ma...

Page 2: ...100 9 13 16 250 21 5 8 550 30 11 16 780 9 9 5 5 8 10 8 9 7 7 6 6 6 9 7 5 8 5 8 15 3 8 390 4 3 1 2 11 13 16 300 39 3 8 1000 35 7 16 900 19 11 16 500 Unit in mm 1 2 3 4 4 9 3 5 3 4 8 5 6 6 9 7 1 2 3 4...

Page 3: ...2 Q1 Q2 A1P F1 F2 F1 F2 Q1 Q2 A B C C H SELECTOR A5P 12 A B C C H SELECTOR A5P A B C A B C RWEYQ PCYD figure 10 A B C A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5...

Page 4: ...1 Q2 Q1 Q2 Q1 Q2 A1P A5P 1 4 8 9 5 6 6 6 2 3 RWEYQ PCYD A B C 7 1 4 5 2 3 3 4 3 X2M X1M F1 F2 F1 F2 Q1 Q2 X3M A1P A5P 1 2 RWEYQ PCYD A B C figure 13 figure 12 figure 11 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 Q...

Page 5: ...em Heat recovery system 1 2 3 4 5 6 7 8 9 10 11 5 4 12 14 15 16 17 13 figure 17 A B C A B C 1 2 DS1 1 2 3 4 OFF ON O U T I N A1P A5P RWEYQ PCYD A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N A1P RWEYQ PCT...

Page 6: ...system 4 5 3 2 1 figure 24 1 11 1 2 2 4 3 4 3 5 5 R410A R410A 9 7 7 8 13 9 6 6 16 10 10 10 10 17 12 12 14 15 15 18 18 Heat pump system Heat recovery system 1 2 3 4 figure 26 figure 27 figure 23 1 15...

Page 7: ...d to alert against unsafe practices NOTE Indicates situations that may result in equipment or property damage accidents only DANGER Refrigerant gas is heavier than air and replaces oxygen A massive le...

Page 8: ...r Refrigerant Pip ing and follow the procedures Since R410A is a blend the required additional refrigerant must be charged in its liquid state If the refrigerant is charged in a state of gas its compo...

Page 9: ...5 F 20 35 C Water flow rate 15 9gpm 60L min or more During cooling operation when the outside temperature is very low it is possible that the thermostat switches off automatically in order to protect...

Page 10: ...ead Drain pipe in 1 2FPS 2 female Thread 1 2FPS 2 female Thread General RWEYQ216PCYD CTJ RWEYQ252PCYD CTJ Nominal cooling capacity 2 MBH 216 252 Nominal heating capacity 3 MBH 243 283 5 Nominal input...

Page 11: ...hazard could occur leading to serious injury or death Re fer to the chapter Caution for refrigerant leaks NOTE 1 An inverter air conditioner may cause electronic noise generated from AM broadcasting...

Page 12: ...water drainage channel around the foundation to con densate waste water from around the unit If the unit is to be installed on a roof check the strength of the roof and its drainage facilities first M...

Page 13: ...After the test run has been completed inspect the strainer at the inlet piping of the outside unit Clean it if it is dirty 7 3 Daily service and maintenance 1 Management of water quality The plate typ...

Page 14: ...rinse the inner part of the plate type heat exchanger with care using fresh and clean water 6 When using any cleaning agent sold in the market check in advance that such agent has no corrosive featur...

Page 15: ...re and close the cover firmly WARNING Never connect power supply wiring to the terminal block for remote controller wiring as this could damage the entire system Picking power supply and transmission...

Page 16: ...upply to transmission wiring terminal block Otherwise the entire system may break down Refer to figure 14 1 Branch 2 Subbranching For low noise operation it is necessary to get the optional Exter nal...

Page 17: ...th a non return valve 2 Make sure the pump oil does not flow oppositely into the system while the pump is not working 3 Use a vacuum pump which can evacuate to 500 microns 9 1 Selection of piping mate...

Page 18: ...ide of the flares and turn them three or four times at first Use ester oil or ether oil See the following table for tightening torque Applying too much torque may cause the flares to crack After all t...

Page 19: ...ween the outside unit connection piping kit or between the outside units exceeds 80 in 2m create a rise of 8 in 200mm or more in the gas piping within a length of 80 in 2m from the kit Pattern 1 Patte...

Page 20: ...i 23 3 lbs Total length ft m of liquid piping size at 7 8 0 235 lbs ft 0 37 N m Total length ft m of liquid piping size at 3 8 Total length ft m of liquid piping size at 1 4 Total length ft m of liqui...

Page 21: ...r unit etc this must be prevented by caulking the connections etc WARNING Be sure to insulate connection piping as touching them can cause burns 9 8 Checking of device and installation conditions Be s...

Page 22: ...alve operation procedure CAUTION Do not open the stop valve until 1 6 of 9 8 Checking of device and installation conditions are completed If the stop valve is left open without turning on power supply...

Page 23: ...ings made on a sub unit will be ignored After this close the control box cover Always perform configuration after turning ON the power supply To learn the setting method refer to the Service Precautio...

Page 24: ...Default value 3 Change 2 9 1 3 or 6 in function of required operation method during heating Malfunc tion code Installation error Remedial action E3 E4 F3 F6 UF U2 The stop valve of an out side unit i...

Page 25: ...stem containing a high sensible solution To activate this setting under heating operation change field set ting 2 9 to the appropriate value matching the requirements of the pre designed system contai...

Page 26: ...vate the mild comfort setting under heating operation change field setting 2 52 1 This setting is used in conjunction with setting 2 9 Eco The original refrigerant temperature target which is defined...

Page 27: ...imum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the amount of refrigerant lbs kg charged to each sys tem separately NOTE Wher...

Page 28: ...3P365916 17C EM14A009A 1503 HT...

Reviews: