background image

3

English

The indoor units that combined with RTSYQ-P system for air con-
ditioning are Daikin VRV series indoor units that compatible with 
R410A. To learn which indoor units are compatible with R410A, 
refer to the product catalogs. To combine with other refrigerant 
indoor unit will cause malfunction.

2-2 Technical and Electrical specifications

Refer to the Engineering Data Book for the complete list of specifica-
tions.

2-3 Main components

For main components and function of the main components, refer to 
the Engineering Data Book.

2-4 Combination

The following table shows a list of system names, system config-
uration models, and the capacity of each connectable indoor unit.

<Single outdoor unit system>

* The RTSQ8P or RTSQ12P unit cannot be used as a configura-

tion unit of single outdoor unit system.

<Multi outdoor unit system>

* The RTSQ10P, RTSQ14P, or RTSQ16P unit cannot be used as 

a configuration unit of the multi outdoor unit system.

* The BHFP30AC56 outdoor unit multi connection piping kit (sold 

separately) is required for the piping connections of two outdoor 
units.

Note

Install the function unit on the right-hand side of the outdoor unit. 
If the order of arrangement differs, the shape of the provided pip-
ing will not be compatible, in which case a substitute connection 
pipe will be required on site.

If the total capacity of the connected indoor units exceeds the 
capacity of the outdoor unit, cooling and heating performance 
may drop when running the indoor units. See the capacity table in 
the Engineering Data Book for details.

2-5 Standard supplied accessories

Confirm the following accessories are included. The storage location 
of the accessories is shown in figure 1.

(Refer to figure 1)

1.

Clamps, Manuals, etc.

2.

Accessory pipes

Note

Accessories are divided separately for the outdoor unit and func-
tion unit. Check the accessories for both units.

Do not throw away any of the accessories until installation is com-
plete. They are needed for installation work.
Request the user to keep the explanation documents after the 
installation work is completed.

2-6 Option accessory

To install the outdoor units, the following optional parts are also required. 
To select an optimum kit, refer to “

6. REFRIGERANT PIPING

”.

• Refrigerant branching kit 

• Outdoor unit connection piping kit

• Pipe size reducer

Note

Make sure that any separately purchased accessories are 
designed for use with R410A.

The outdoor unit multi connection piping kit is required for the 
multi outdoor unit system only.

System name

Composition unit

Total capacity 

of indoor units

Outdoor unit

Function unit

RTSYQ10PY1

RTSQ10PY1

BTSQ20PY1

125 - 325

RTSYQ14PY1

RTSQ14PY1

BTSQ20PY1

175 - 455

RTSYQ16PY1

RTSQ16PY1

BTSQ20PY1

200 - 520

System name

Composition unit

Total capacity 

of indoor units

Outdoor unit

Function unit

RTSYQ20PY1

RTSQ8PY1

RTSQ12PY1

BTSQ20PY1

250 - 650

Outdoor unit

Outdoor unit multi 
connection piping kit(*)

Function unit

To indoor units

*Only in case of multi 
  outdoor unit system

A

B

(*)

Shape

Name

Manuals, etc.

Clamp

(1)

(2)

(3)

Quantity

11 pcs.

2 pcs.

1 pc.

1 pc. about each item

(Small)

(Large)

• Operation manual
• Installation manual
• “REQUEST FOR THE 

INDICATION” label
(Installation records)

• Refrigerant charge label
• Declaration of conformity

< Accessories included in outdoor unit >

REFNET header

KHRP26M22H KHRP26M33H KHRP26M72H

REFNET joint

KHRP26A22T KHRP26A33T KHRP26A72T

Kit name

BHFP30A56

for REFNET header

KHRP26M73HP

8  type

12 type

10 type

14 · 16 type

Quantity

Shape

Name

Gas side accessory pipe

(1)

(2)

(3)

(4)

1 pc.

1 pc.

1 pc.

2 pcs.

3 pcs.

2 pcs.

2 pcs.

2 pcs.

φ

25.4

φ

22.2

8  type

12 type

10 type

14 · 16 type

Quantity

Shape

Name

Liquid side accessory pipe

Equalizer side 

accessory pipe

(1)

(2)

(3)

(2)

(1)

1 pc.

1 pc.

2 pcs.

1 pc.

2 pcs.

2 pcs.

1 pc.

2 pcs.

φ

12.7

φ

9.5

Shape

Name

Quantity

2 pcs.

φ

25.4

φ

12.7

< Accessories included in function unit >

2 pcs.

Gas side 

accessory 

pipe(5)

Liquid side 

accessory 

pipe(4)

01_EN_3P201178-10P.fm  Page 3  Wednesday, September 2, 2009  11:10 AM

Summary of Contents for RTSQ10PY1

Page 1: ...nglish Norsk Svenska Deutsch Fran ais Polski Installation manual VRVIII C System air conditioner Installationsanleitung VRVIII C System Klimaanlage Manuel d installation Conditionneur d air VRVIII C S...

Page 2: ...PY1 RTSYQ16PY1 RTSYQ20PY1 RTSQ8PY1 RTSQ10PY1 RTSQ12PY1 RTSQ14PY1 RTSQ16PY1 BTSQ20PY1 REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1 REYQ20PY1 REYQ22PY1 REYQ24PY1 REYQ26PY1 REYQ28PY1 REYQ30...

Page 3: ...0 300 500 10 50 100 10 100 300 300 500 50 200 200 400 200 200 50 100 10 100 500 50 50 100 50 100 1 3 6 6 6 2 7 6 6 6 9 8 9 8 9 8 9 8 3 4 5 4 5 2 unit mm 1 2 5 4 3 figure 7 727 765 300 460 1 1 2 8 8 5...

Page 4: ...re 11 6 3 4 5 2 8 7 9 10 1 2 4 3 2 1 figure 12 1 3 5 11 11 11 11 9 12 12 13 13 7 10 9 10 4 7 3 6 11 11 11 11 11 11 9 9 8 8 10 10 2 figure 15 figure 21 9 7 8 10 2 3 12 13 7 15 17 18 15 16 14 1 11 4 5 6...

Page 5: ...10 9 1 8 5 7 9 6 4 3 2 figure 26 1 3 2 2 1 3 4 5 6 7 1 10 8 9 figure 30 figure 31 2 3 13 7 8 9 10 12 11 16 6 5 4 14 15 1 17 18 19 20 figure 34 figure 29 figure 23 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1...

Page 6: ...leakage electric shocks or fire Install the air conditioner in accordance with the instructions in this installation manual Improper installation may result in water leakage electric shocks or fire Wh...

Page 7: ...quired additional refrig erant must be charged in its liquid state If the system is charged with refrigerant in its gaseous state due to composition change the system will not function normally Limit...

Page 8: ...both units Do not throw away any of the accessories until installation is com plete They are needed for installation work Request the user to keep the explanation documents after the installation work...

Page 9: ...power wiring and transmission wiring in conduits and ground the conduits Refer to figure 3 1 Indoor unit 2 Branch switch overcurrent breaker 3 Remote controller 4 Personal computer or radio 5 Air outl...

Page 10: ...intless phosphor deoxidized copper pipe Size See 6 5 Example of connection to determine the cor rect size Thickness Select a thickness for the refrigerant piping which complies with national and local...

Page 11: ...tract the gas in the pinch piping 4 Step 2 After the gas is extracted melt the blazing mate rial with a burner and remove the pinch pipes 3 Connecting refrigerant piping to outdoor units and function...

Page 12: ...int horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 17 1 Do not install vertically Refer to figure 17 2 Maintain a straight portion of 500 mm...

Page 13: ...Horizontal surface 2 B arrow view Oil remains in the stopping outdoor unit Rising height 200 mm or more 1 Connect straightly 2 Put rising Prohibited pattern Front connection Bottom connection To indoo...

Page 14: ...nd outdoor units Between outdoor unit and function unit Actual pipe length Equivalent length Actual and Equivalent pipe length Difference in height Difference in height Difference in height Difference...

Page 15: ...s the requirements of Japanease High Pressure Gas Controll low As of Jan 2003 The thickness and material shall be selected in accordance with local code In case of single outdoor unit system In case o...

Page 16: ...at 19 1 Total length m of liquid piping size at 12 7 Total length m of liquid piping size at 6 4 0 37 0 18 0 059 0 26 0 12 0 022 FOR THE SYSTEM SYSTEM NAME THE AMOUNT OF REFRIGERANT Example for refri...

Page 17: ...and an malfunction code will be displayed on the indoor remote controller Never remove thermistor sensor or etc when connecting power wiring and transmission wiring If operated with thermistor sensor...

Page 18: ...board Attach with care See the table below for the tightening torque of the transmission wiring terminals All transmission wiring should use sheathed vinyl cord 0 75 1 25 mm2 or cable duplex Transmiss...

Page 19: ...ing in the power wiring and ground wir ing from the left hand side 6 In the case of pulling in the power wiring and ground wir ing from the right hand side 7 Pull in the transmission wiring from the p...

Page 20: ...rogen gas then depressurize down to 100 7 kPa for an hour using the vacuum pump vacuum drying 2 If the pressure does not reach 100 7 kPa even after depressur izing for at least two hours repeat the va...

Page 21: ...the refrigerant charging operation close the valve of the refrigerant tank immediately The refrigerant charge port of this product have electric expan sion valve The valve will be closed at end of ref...

Page 22: ...cts the main body seal 3 Make sure to tighten the cap securely For the tightening torque refer to the item Tightening Torque 8HP type 10HP type 12HP type 14HP type 16HP type Liquid pipe shutoff valve...

Page 23: ...refrigerant amount in the field and total refrig erant amount of the system to Refrigerant charge label and adhere in the proximity of the refrigerant charge port About Refrigerant charge label refer...

Page 24: ...the remote control ler display shows P9 code After checking push the MODE button BS1 once and the charg ing is complete In case of heating mode 7 Push the TEST button BS4 once within 5 minutes after...

Page 25: ...ve A PA PH The refrigerant tank is empty Close the valve A and replace empty tank to the new tank After changing the tank open the valve A again Beware the fan running The outdoor unit does not stop o...

Page 26: ...tandards may be applicable if local regulations are not available The VRV System like other air conditioning systems uses R410A as refrigerant R410A itself is an entirely safe non toxic non combusti b...

Page 27: ...ntration 4 Dealing with the situations where the result exceeds the maxi mum concentration level Where the installation of a facility results in a concentration in excess of the maximum concentration...

Page 28: ...3P201178 10P EM07A033B 0908 HT 00_CV_3P201178 10P fm Page 5 Wednesday September 2 2009 11 09 AM...

Reviews: