background image

13

English

7-3 Leading wire Procedure

The power wiring and ground wiring are passed out from the 
power wiring hole on the sides, the front (knock hole) or the bot-
tom frame (knock hole) .

The transmission wiring is passed out from the wiring hole (knock 
hole) on the front of the unit or from a piping hole.

(Refer to figure 21)

1.

Outdoor unit

2.

Function unit

3.

Electric wiring diagram (Rear side of EL.COMPO.BOX 
lid)

4.

Power wring and ground wiring

5.

Conduit

6.

Piping outlet

7.

Transmission wiring

8.

To Indoor unit and function unit

9.

Wiring inlet (front)

10.

Through cover

11.

Cut off the hatching parts.

12.

Power wiring and ground wiring

13.

Inside conduit

14.

To outdoor unit

15.

Knock hole

16.

For transmission wring

17.

For power wiring and ground wiring

18.

Burr

Note

Open the knock holes with a hammer or the like.

After knocking out the holes, we recommend you remove any 
burrs and paint them using the repair paint to prevent rusting. 

(Refer to figure 21)

When passing wiring through the knock holes, remove burrs 
around the knock holes and protect the wiring with conduit or pro-
tective tape.

If small animals might enter the unit, block off any gaps (hatching 
parts in figure 21) with material (field supply).

7-4 Transmission Wiring Connection Procedure

Referring to figure 22 connect the transmission wiring between 
outdoor unit and function unit, outdoor unit and outdoor unit of 
same system (Only in case multi outdoor unit system), outdoor 
unit and indoor unit, outdoor unit and outdoor unit of other system.

(Refer to figure 22)

1.

For single outdoor unit system

2.

For multi outdoor unit system

3.

Outdoor unit

4.

Function unit

5.

Master outdoor unit A (*)

6.

Slave outdoor unit B (*)

7.

To outdoor unit in other refrigerant system

8.

Indoor unit

9.

Use 2-core cable (with no polarity).

10.

Never connect power wiring.

(*) In the case of the multi outdoor unit system, the outdoor 

unit connecting the transmission wiring to the indoor unit 
(outdoor unit A in figure 22) is the master and the other 
outdoor unit is the slave. Operate the control PCB (A1P) 
of the master for commissioning at the time of installation 
or local settings at the time of servicing.

Note

Do not connect the power wiring to terminals for the transmission 
wiring. Doing so would destroy the entire system.

When connecting wires to the terminal block on the PC-board, too 
much heat or tightening could damage the PC-board. Attach with 
care.
See the table below for the tightening torque of the transmission 
wiring terminals.

All transmission wiring should use sheathed vinyl cord 

0.75-1.25 mm

2

 or cable (duplex).

Transmission wiring should be done within the following limita-
tions.
If they are exceeded, transmission problems may occur.

Between outdoor unit and indoor unit
Between outdoor unit and outdoor unit of other systems

Max. wiring length

:1,000 m

Max. total wiring length

:2,000 m

Max. no. of branches

:16

[Note] 
No branch is allowed after branch (

See figure 23

)

Max. no. of outdoor units of other system 
that can be connected

: 10

Between outdoor unit and function unit
Between outdoor unit and outdoor unit of same system

Max.wiring length

:30 m

(Refer to figure 23)

1.

Branch

2.

Branch after branch

The transmission wiring inside the EL.COMPO.BOX should be 
secured using the clamp (1) as shown in figure 24.

(Refer to figure 24)

1.

Outdoor unit

2.

Function unit

3.

Inside EL.COMPO.BOX

4.

Fix two portions in the EL.COMPO.BOX with the 
included clamp (1).

5.

Fix a single portion in the EL.COMPO.BOX with the 
included clamp (1).

6.

Never connect power wiring.

Outside the units, the transmission wiring must be finished simul-
taneously with the local refrigerant piping, and wound with tape 
(field supply) as shown in figure 25.

(Refer to figure 25)

1.

Gas pipe

2.

Liquid pipe

3.

Transmission wiring

4.

Insulation material

5.

Finishing tape

Wiring to other systems should be connected to terminals F1 and 
F2 (TO OUT/D UNIT) on the PC-board of the unit. Connecting the 
wires to the Q1, Q2 (TO MULTI UNIT) terminals results in mal-
function.

7-5 Power Wiring Connection Procedure

Be sure to connect the power supply wiring to the power supply 
terminal block and hold it in place using the included clamp (1) as 
shown in the figure 26.

The ground wiring should be bound to the power wiring using the 
included clamp (1) to prevent outside force from being applied to 
the terminal.

(Refer to figure 26)

1.

Power supply (3N ~ 50 Hz, 380 - 415 V)

2.

Earth leakage circuit breaker

3.

Fuse

4.

Ground wiring

5.

Outdoor unit

6.

Function unit

7.

Power supply terminal block

8.

Ground terminal

9.

Clamp (1) (accessories)

10.

Power wiring and ground wiring (to power supply)

11.

Attach the insulating sleeve.

12.

Lay and connect from the upper side

Warning

Be sure to install an earth leakage circuit breaker.

The installation of an earth leakage circuit breaker is a must in 
order to prevent electric shock or fire prevention.

Screw size

Tightening torque (N · m)

M3.5 (A1P)

0.80 - 0.96

01_EN_3P201178-10P.fm  Page 13  Wednesday, September 2, 2009  11:10 AM

Summary of Contents for RTSQ10PY1

Page 1: ...nglish Norsk Svenska Deutsch Fran ais Polski Installation manual VRVIII C System air conditioner Installationsanleitung VRVIII C System Klimaanlage Manuel d installation Conditionneur d air VRVIII C S...

Page 2: ...PY1 RTSYQ16PY1 RTSYQ20PY1 RTSQ8PY1 RTSQ10PY1 RTSQ12PY1 RTSQ14PY1 RTSQ16PY1 BTSQ20PY1 REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1 REYQ20PY1 REYQ22PY1 REYQ24PY1 REYQ26PY1 REYQ28PY1 REYQ30...

Page 3: ...0 300 500 10 50 100 10 100 300 300 500 50 200 200 400 200 200 50 100 10 100 500 50 50 100 50 100 1 3 6 6 6 2 7 6 6 6 9 8 9 8 9 8 9 8 3 4 5 4 5 2 unit mm 1 2 5 4 3 figure 7 727 765 300 460 1 1 2 8 8 5...

Page 4: ...re 11 6 3 4 5 2 8 7 9 10 1 2 4 3 2 1 figure 12 1 3 5 11 11 11 11 9 12 12 13 13 7 10 9 10 4 7 3 6 11 11 11 11 11 11 9 9 8 8 10 10 2 figure 15 figure 21 9 7 8 10 2 3 12 13 7 15 17 18 15 16 14 1 11 4 5 6...

Page 5: ...10 9 1 8 5 7 9 6 4 3 2 figure 26 1 3 2 2 1 3 4 5 6 7 1 10 8 9 figure 30 figure 31 2 3 13 7 8 9 10 12 11 16 6 5 4 14 15 1 17 18 19 20 figure 34 figure 29 figure 23 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1...

Page 6: ...leakage electric shocks or fire Install the air conditioner in accordance with the instructions in this installation manual Improper installation may result in water leakage electric shocks or fire Wh...

Page 7: ...quired additional refrig erant must be charged in its liquid state If the system is charged with refrigerant in its gaseous state due to composition change the system will not function normally Limit...

Page 8: ...both units Do not throw away any of the accessories until installation is com plete They are needed for installation work Request the user to keep the explanation documents after the installation work...

Page 9: ...power wiring and transmission wiring in conduits and ground the conduits Refer to figure 3 1 Indoor unit 2 Branch switch overcurrent breaker 3 Remote controller 4 Personal computer or radio 5 Air outl...

Page 10: ...intless phosphor deoxidized copper pipe Size See 6 5 Example of connection to determine the cor rect size Thickness Select a thickness for the refrigerant piping which complies with national and local...

Page 11: ...tract the gas in the pinch piping 4 Step 2 After the gas is extracted melt the blazing mate rial with a burner and remove the pinch pipes 3 Connecting refrigerant piping to outdoor units and function...

Page 12: ...int horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 17 1 Do not install vertically Refer to figure 17 2 Maintain a straight portion of 500 mm...

Page 13: ...Horizontal surface 2 B arrow view Oil remains in the stopping outdoor unit Rising height 200 mm or more 1 Connect straightly 2 Put rising Prohibited pattern Front connection Bottom connection To indoo...

Page 14: ...nd outdoor units Between outdoor unit and function unit Actual pipe length Equivalent length Actual and Equivalent pipe length Difference in height Difference in height Difference in height Difference...

Page 15: ...s the requirements of Japanease High Pressure Gas Controll low As of Jan 2003 The thickness and material shall be selected in accordance with local code In case of single outdoor unit system In case o...

Page 16: ...at 19 1 Total length m of liquid piping size at 12 7 Total length m of liquid piping size at 6 4 0 37 0 18 0 059 0 26 0 12 0 022 FOR THE SYSTEM SYSTEM NAME THE AMOUNT OF REFRIGERANT Example for refri...

Page 17: ...and an malfunction code will be displayed on the indoor remote controller Never remove thermistor sensor or etc when connecting power wiring and transmission wiring If operated with thermistor sensor...

Page 18: ...board Attach with care See the table below for the tightening torque of the transmission wiring terminals All transmission wiring should use sheathed vinyl cord 0 75 1 25 mm2 or cable duplex Transmiss...

Page 19: ...ing in the power wiring and ground wir ing from the left hand side 6 In the case of pulling in the power wiring and ground wir ing from the right hand side 7 Pull in the transmission wiring from the p...

Page 20: ...rogen gas then depressurize down to 100 7 kPa for an hour using the vacuum pump vacuum drying 2 If the pressure does not reach 100 7 kPa even after depressur izing for at least two hours repeat the va...

Page 21: ...the refrigerant charging operation close the valve of the refrigerant tank immediately The refrigerant charge port of this product have electric expan sion valve The valve will be closed at end of ref...

Page 22: ...cts the main body seal 3 Make sure to tighten the cap securely For the tightening torque refer to the item Tightening Torque 8HP type 10HP type 12HP type 14HP type 16HP type Liquid pipe shutoff valve...

Page 23: ...refrigerant amount in the field and total refrig erant amount of the system to Refrigerant charge label and adhere in the proximity of the refrigerant charge port About Refrigerant charge label refer...

Page 24: ...the remote control ler display shows P9 code After checking push the MODE button BS1 once and the charg ing is complete In case of heating mode 7 Push the TEST button BS4 once within 5 minutes after...

Page 25: ...ve A PA PH The refrigerant tank is empty Close the valve A and replace empty tank to the new tank After changing the tank open the valve A again Beware the fan running The outdoor unit does not stop o...

Page 26: ...tandards may be applicable if local regulations are not available The VRV System like other air conditioning systems uses R410A as refrigerant R410A itself is an entirely safe non toxic non combusti b...

Page 27: ...ntration 4 Dealing with the situations where the result exceeds the maxi mum concentration level Where the installation of a facility results in a concentration in excess of the maximum concentration...

Page 28: ...3P201178 10P EM07A033B 0908 HT 00_CV_3P201178 10P fm Page 5 Wednesday September 2 2009 11 09 AM...

Reviews: