background image

English

18

[How to Check How Many Units are Connected]

It is possible to find out how many indoor or outdoor (function) unit in the system are turned on by operating the push button on the PC-board 
(A1P) of outdoor unit (In case of multi system master unit).
Follow the procedure below to check how many indoor or outdoor units are turned on.

(*5) The number include the function unit.

Note

Press the “MODE button” (BS1) if you get confused while operating.
This returns to 

Setting Mode 1

 (H1P : OFF, default).

9-2 Procedure of Additional Refrigerant charging
1.

Make sure the following works are complete in accordance with 
the installation manual.

„

Piping work

„

Wiring work

„

Air tight test and Vacuum drying

„

Installation work for indoor unit

2.

Calculate the “additional charging amount” using “How to calcu-
late the additional refrigerant to be charged” in “

6-5 Example of 

connection

”.

3.

Open the valve B (

See the figure 34

. The valve A,C and the shut-

off valves of outdoor unit must be left closed), and charge the 
refrigerant of the “additional charging amount” from the liquid pipe 
service port of function unit.

4.

Close valve B when the refrigerant is charged as much as possi-
ble. 

(Refer to figure 34)

5.

Perform the automatic refrigerant charging operation according to 
the [Automatic refirgerant charging operation procedure] and fill 
the remaining quantity of refrigerant.
Go to step 6 if the additional quantity of refrigerant to be replen-
ished is known and no automatic charging operation is performed 
or the contraction of working hours is required.

6.

If the additional quantity of refrigerant was not replenished in step 
5 (automatic refrigerant charging operation), perform the addi-
tional refrigerant charging operation in service mode and replenish 
the refrigerant through the refrigerant charging port.
Refer to the “Additional refrigerant charging method” described in 
the [Service precautions] label (below) on the EL.COMPO.BOX lid 
of the outdoor unit for the additional refrigerant charging operation 
in service mode.

7.

After completing the additional refrigerant charging, record the 
charging amount on the accessory “REQUEST FOR THE INDI-
CATON” label (Installation records) and adhere it to the back side 
of the front panel. Also, record the factory charged refrigerant 
amount, additional refrigerant amount in the field and total refrig-
erant amount of the system to “Refrigerant charge label” and 
adhere in the proximity of the refrigerant charge port.
About “Refrigerant charge label”, refer to [Important information 
regarding the refrigerant used] in “

1-2 Special notice of prod-

uct

”.

(Refer to figure 34)

1.

Measuring device

2.

R410A tank (with siphon)

3.

Charge hose

4.

Refrigerant charge port

5.

Liquid pipe shutoff valve

6.

Gas shutoff valve

7.

Equaliger pipe shutoff valve

8.

Outdoor unit A

9.

Outdoor unit B (for multi outdoor unit)

10.

Function unit

11.

Liquid pipe service port

12.

Gas pipe service port

13.

Valve A

14.

Valve C

15.

Valve B

16.

To indoor unit

17.

Local piping

18.

Flow of refrigerant

19.

Shutoff valve

20.

Service port

[Automatic refirgerant charging operation procedure]

Note

For performing the automatic refrigerant charging operation, the 
push button on the PC-bord (A1) of outdoor unit are used. (See 
figure 32.)
And the refrigerant are charged from the refrigerant charge port 
via the valve A. (See figure 34.) For operating the push button and 
opening or closeing the valves, follow the procedure.

During Automatic refrigerant charging operation, the system will 
select charging mode (cooling mode or heating mode) by the tem-
perature condition as follows.

When cahrging in cooling mode, the system will stop operation 
when the required amount of refrigerant is charged.

(LED display: 

h

 ...OFF  

i

 ...ON  

j

 ...Blinking  

 ...Uncertain)

LED display

H1P

H2P

H3P

H4P

H5P

H6P

H7P

(1) Press the MODE button (BS1) once at 

Setting Mode 1

 (H1P : off), and set the MON-

ITOR MODE (H1P : Blinking).

j

h

h

h

h

h

h

(2) Press the SET button (BS2) the number of times until the 

LED display matches that at right.

For checking the number 
of outdoor units (*1) : 
eight times

j

h

h

i

h

h

h

For checking the number 
of indoor units : five times

j

h

h

h

i

h

i

(3) Press the RETURN button (BS3) and read the number of units from the display of 

H2P through H7P.
[Reading Method]
The display of H2P through H7P should be read as a binary number, with 

j

 standing 

for “1” and 

h

 standing for “0”.

j

j

h

j

h

j

j

h

(4) Press the MODE button (BS1) once. This returns to 

Setting Mode 1 

(H1P : OFF, default).

h

h

i

h

h

h

h

Ex: For the LED display at right, this would be “0 1 0 1 1 0 ”, 
which would mean 22 units are connected.

Note: “000000” indicates 64 units.

32 × 

0

 + 16 × 

1

 + 8 × 

0

 + 4 × 

1

 + 2 × 

1

 + 1 × 

0

 = 22 units

Outdoor temp. : 0˚C DB ~  43˚C DB
Indoor temp. :

10˚C DB ~  32˚C DB

Less than above range

Cooling mode

Heating mode

01_EN_3P201178-10P.fm  Page 18  Wednesday, September 2, 2009  11:10 AM

Summary of Contents for RTSQ10PY1

Page 1: ...nglish Norsk Svenska Deutsch Fran ais Polski Installation manual VRVIII C System air conditioner Installationsanleitung VRVIII C System Klimaanlage Manuel d installation Conditionneur d air VRVIII C S...

Page 2: ...PY1 RTSYQ16PY1 RTSYQ20PY1 RTSQ8PY1 RTSQ10PY1 RTSQ12PY1 RTSQ14PY1 RTSQ16PY1 BTSQ20PY1 REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1 REYQ20PY1 REYQ22PY1 REYQ24PY1 REYQ26PY1 REYQ28PY1 REYQ30...

Page 3: ...0 300 500 10 50 100 10 100 300 300 500 50 200 200 400 200 200 50 100 10 100 500 50 50 100 50 100 1 3 6 6 6 2 7 6 6 6 9 8 9 8 9 8 9 8 3 4 5 4 5 2 unit mm 1 2 5 4 3 figure 7 727 765 300 460 1 1 2 8 8 5...

Page 4: ...re 11 6 3 4 5 2 8 7 9 10 1 2 4 3 2 1 figure 12 1 3 5 11 11 11 11 9 12 12 13 13 7 10 9 10 4 7 3 6 11 11 11 11 11 11 9 9 8 8 10 10 2 figure 15 figure 21 9 7 8 10 2 3 12 13 7 15 17 18 15 16 14 1 11 4 5 6...

Page 5: ...10 9 1 8 5 7 9 6 4 3 2 figure 26 1 3 2 2 1 3 4 5 6 7 1 10 8 9 figure 30 figure 31 2 3 13 7 8 9 10 12 11 16 6 5 4 14 15 1 17 18 19 20 figure 34 figure 29 figure 23 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1...

Page 6: ...leakage electric shocks or fire Install the air conditioner in accordance with the instructions in this installation manual Improper installation may result in water leakage electric shocks or fire Wh...

Page 7: ...quired additional refrig erant must be charged in its liquid state If the system is charged with refrigerant in its gaseous state due to composition change the system will not function normally Limit...

Page 8: ...both units Do not throw away any of the accessories until installation is com plete They are needed for installation work Request the user to keep the explanation documents after the installation work...

Page 9: ...power wiring and transmission wiring in conduits and ground the conduits Refer to figure 3 1 Indoor unit 2 Branch switch overcurrent breaker 3 Remote controller 4 Personal computer or radio 5 Air outl...

Page 10: ...intless phosphor deoxidized copper pipe Size See 6 5 Example of connection to determine the cor rect size Thickness Select a thickness for the refrigerant piping which complies with national and local...

Page 11: ...tract the gas in the pinch piping 4 Step 2 After the gas is extracted melt the blazing mate rial with a burner and remove the pinch pipes 3 Connecting refrigerant piping to outdoor units and function...

Page 12: ...int horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 17 1 Do not install vertically Refer to figure 17 2 Maintain a straight portion of 500 mm...

Page 13: ...Horizontal surface 2 B arrow view Oil remains in the stopping outdoor unit Rising height 200 mm or more 1 Connect straightly 2 Put rising Prohibited pattern Front connection Bottom connection To indoo...

Page 14: ...nd outdoor units Between outdoor unit and function unit Actual pipe length Equivalent length Actual and Equivalent pipe length Difference in height Difference in height Difference in height Difference...

Page 15: ...s the requirements of Japanease High Pressure Gas Controll low As of Jan 2003 The thickness and material shall be selected in accordance with local code In case of single outdoor unit system In case o...

Page 16: ...at 19 1 Total length m of liquid piping size at 12 7 Total length m of liquid piping size at 6 4 0 37 0 18 0 059 0 26 0 12 0 022 FOR THE SYSTEM SYSTEM NAME THE AMOUNT OF REFRIGERANT Example for refri...

Page 17: ...and an malfunction code will be displayed on the indoor remote controller Never remove thermistor sensor or etc when connecting power wiring and transmission wiring If operated with thermistor sensor...

Page 18: ...board Attach with care See the table below for the tightening torque of the transmission wiring terminals All transmission wiring should use sheathed vinyl cord 0 75 1 25 mm2 or cable duplex Transmiss...

Page 19: ...ing in the power wiring and ground wir ing from the left hand side 6 In the case of pulling in the power wiring and ground wir ing from the right hand side 7 Pull in the transmission wiring from the p...

Page 20: ...rogen gas then depressurize down to 100 7 kPa for an hour using the vacuum pump vacuum drying 2 If the pressure does not reach 100 7 kPa even after depressur izing for at least two hours repeat the va...

Page 21: ...the refrigerant charging operation close the valve of the refrigerant tank immediately The refrigerant charge port of this product have electric expan sion valve The valve will be closed at end of ref...

Page 22: ...cts the main body seal 3 Make sure to tighten the cap securely For the tightening torque refer to the item Tightening Torque 8HP type 10HP type 12HP type 14HP type 16HP type Liquid pipe shutoff valve...

Page 23: ...refrigerant amount in the field and total refrig erant amount of the system to Refrigerant charge label and adhere in the proximity of the refrigerant charge port About Refrigerant charge label refer...

Page 24: ...the remote control ler display shows P9 code After checking push the MODE button BS1 once and the charg ing is complete In case of heating mode 7 Push the TEST button BS4 once within 5 minutes after...

Page 25: ...ve A PA PH The refrigerant tank is empty Close the valve A and replace empty tank to the new tank After changing the tank open the valve A again Beware the fan running The outdoor unit does not stop o...

Page 26: ...tandards may be applicable if local regulations are not available The VRV System like other air conditioning systems uses R410A as refrigerant R410A itself is an entirely safe non toxic non combusti b...

Page 27: ...ntration 4 Dealing with the situations where the result exceeds the maxi mum concentration level Where the installation of a facility results in a concentration in excess of the maximum concentration...

Page 28: ...3P201178 10P EM07A033B 0908 HT 00_CV_3P201178 10P fm Page 5 Wednesday September 2 2009 11 09 AM...

Reviews: