background image

7

English

9.

Piping on liquid side (procured locally)

10.

Piping on gas side (procured locally)

11.

Blazing

12.

To outdoor unit

13.

To indoor unit

(*1) RTSQ14P and RTSQ16P units only (procured locally for others)
(*2) RTSQ12P unit only (procured locally for other)
(*3) RTSYQ14P to RTSYQ20P systems only (procured locally for 

others)

(*4)

<For RTSYQ14P and RTSYQ16P systems>

Refer to figure 16 and the following table, and cut the gas side 
accessory pipe (3).

<RTSYQ20P system>

Refer to the installation manual of the outdoor unit connection 
piping kit and cut the gas side accessory pipe (3).

(Refer to figure 16)

1.

Gas side accessory pipe (3) (Indoor side)

2.

Cut to 130 mm.

3.

Gas side accessory pipe (3) (Outdoor side)

4.

Cut to 73 mm.

5.

Function unit

6.

Outdoor unit

7.

Connecting piping on gas side (procured locally)

8.

To indoor units

Note

The dimensions shown in above table are required when installing 
the piping (procured locally) on the gas side of the outdoor unit in 
the position shown in figure 16.
Refer to the table above and make necessary size adjustment if 
the working conditions of the on-site piping on the gas side differ.

4.

Piping Connections between Outdoor Units (for Multi Outdoor 
Unit System Only)

Observe the restrictions specified below to connect the outdoor 
units.

The outdoor unit multi connection piping kit (sold separately) is 
required for the connection of the piping between the outdoor 
units. For the installation of the outdoor unit multi connection pip-
ing kit, refer to the installation manual provided with the kit. Unless 
the kit is installed properly, the outdoor units may malfunction or 
fail to operate.

(1)

About outdoor unit multi connection piping kit

Install the joint horizontally so that the attached warning 
label faces strait up, and the tilt is within ±15°. 

(Refer to figure 17-1)

Do not install vertically. 

(Refer to figure 17-2)

Maintain a straight portion of 500 mm or more until the split 
of the joint without wrapping any onsite piping around this 
area. 
Over 500 mm of straight area can be maintained by con-
necting at least 120 mm of onsite pipe (straight) to the joint.

(Refer to figure 17-3)

(Refer to figure 17)

1.

Warning label

2.

Horizontal surface

3.

±15° or less

4.

Ground

5.

A-arrow view

6.

B-arrow view

7.

Onsite pipe (120mm length or more)

8.

Straight part of 500mm or more

(2)

Install the piping between the outdoor units horizontally or 
with a rising gradient toward outdoor unit A from outdoor unit 
B in order to prevent oil remaining in the piping.

(3)

To avoid the risk of oil detention in the stopping unit, always 
connect the shutoff valve and the piping between outdoor 
units as shown A or B in the figure below.

System name

Required dimensions for gas side 

accessory pipe (3)

Outdoor side

Indoor side

RTSYQ14 · 16P 

type

73mm

130mm

Pattern 1

Change to pattern 1 or pattern 2

To indoor unit

To indoor unit

Piping between 
units

Front connection

Unit

A

Unit

B

Unit

A

Unit

B

Level

Bottom connection

Piping between 
units

Outdoor unit Function unit

Outdoor unit Function unit

Pattern 2

To indoor unit

To indoor unit

Rising 

gradient

Outdoor unit

Rise

Rise

Function unit

Outdoor unit Function unit

Front connection

Bottom connection

Unit

A

Unit

B

Unit

A

Unit

B

Prohibited pattern

Front connection

Bottom connection

Downward

inclination

Downward inclination

Oil remains in piping

To indoor unit

Outdoor unit Function unit

Unit

A

Unit

B

Downward inclination

Oil remains in piping

Outdoor unit Function unit

Unit

A

Unit

B

A

B

A

B

Front connection

Bottom connection

01_EN_3P201178-10P.fm  Page 7  Wednesday, September 2, 2009  11:10 AM

Summary of Contents for RTSQ10PY1

Page 1: ...nglish Norsk Svenska Deutsch Fran ais Polski Installation manual VRVIII C System air conditioner Installationsanleitung VRVIII C System Klimaanlage Manuel d installation Conditionneur d air VRVIII C S...

Page 2: ...PY1 RTSYQ16PY1 RTSYQ20PY1 RTSQ8PY1 RTSQ10PY1 RTSQ12PY1 RTSQ14PY1 RTSQ16PY1 BTSQ20PY1 REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1 REYQ20PY1 REYQ22PY1 REYQ24PY1 REYQ26PY1 REYQ28PY1 REYQ30...

Page 3: ...0 300 500 10 50 100 10 100 300 300 500 50 200 200 400 200 200 50 100 10 100 500 50 50 100 50 100 1 3 6 6 6 2 7 6 6 6 9 8 9 8 9 8 9 8 3 4 5 4 5 2 unit mm 1 2 5 4 3 figure 7 727 765 300 460 1 1 2 8 8 5...

Page 4: ...re 11 6 3 4 5 2 8 7 9 10 1 2 4 3 2 1 figure 12 1 3 5 11 11 11 11 9 12 12 13 13 7 10 9 10 4 7 3 6 11 11 11 11 11 11 9 9 8 8 10 10 2 figure 15 figure 21 9 7 8 10 2 3 12 13 7 15 17 18 15 16 14 1 11 4 5 6...

Page 5: ...10 9 1 8 5 7 9 6 4 3 2 figure 26 1 3 2 2 1 3 4 5 6 7 1 10 8 9 figure 30 figure 31 2 3 13 7 8 9 10 12 11 16 6 5 4 14 15 1 17 18 19 20 figure 34 figure 29 figure 23 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1...

Page 6: ...leakage electric shocks or fire Install the air conditioner in accordance with the instructions in this installation manual Improper installation may result in water leakage electric shocks or fire Wh...

Page 7: ...quired additional refrig erant must be charged in its liquid state If the system is charged with refrigerant in its gaseous state due to composition change the system will not function normally Limit...

Page 8: ...both units Do not throw away any of the accessories until installation is com plete They are needed for installation work Request the user to keep the explanation documents after the installation work...

Page 9: ...power wiring and transmission wiring in conduits and ground the conduits Refer to figure 3 1 Indoor unit 2 Branch switch overcurrent breaker 3 Remote controller 4 Personal computer or radio 5 Air outl...

Page 10: ...intless phosphor deoxidized copper pipe Size See 6 5 Example of connection to determine the cor rect size Thickness Select a thickness for the refrigerant piping which complies with national and local...

Page 11: ...tract the gas in the pinch piping 4 Step 2 After the gas is extracted melt the blazing mate rial with a burner and remove the pinch pipes 3 Connecting refrigerant piping to outdoor units and function...

Page 12: ...int horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 17 1 Do not install vertically Refer to figure 17 2 Maintain a straight portion of 500 mm...

Page 13: ...Horizontal surface 2 B arrow view Oil remains in the stopping outdoor unit Rising height 200 mm or more 1 Connect straightly 2 Put rising Prohibited pattern Front connection Bottom connection To indoo...

Page 14: ...nd outdoor units Between outdoor unit and function unit Actual pipe length Equivalent length Actual and Equivalent pipe length Difference in height Difference in height Difference in height Difference...

Page 15: ...s the requirements of Japanease High Pressure Gas Controll low As of Jan 2003 The thickness and material shall be selected in accordance with local code In case of single outdoor unit system In case o...

Page 16: ...at 19 1 Total length m of liquid piping size at 12 7 Total length m of liquid piping size at 6 4 0 37 0 18 0 059 0 26 0 12 0 022 FOR THE SYSTEM SYSTEM NAME THE AMOUNT OF REFRIGERANT Example for refri...

Page 17: ...and an malfunction code will be displayed on the indoor remote controller Never remove thermistor sensor or etc when connecting power wiring and transmission wiring If operated with thermistor sensor...

Page 18: ...board Attach with care See the table below for the tightening torque of the transmission wiring terminals All transmission wiring should use sheathed vinyl cord 0 75 1 25 mm2 or cable duplex Transmiss...

Page 19: ...ing in the power wiring and ground wir ing from the left hand side 6 In the case of pulling in the power wiring and ground wir ing from the right hand side 7 Pull in the transmission wiring from the p...

Page 20: ...rogen gas then depressurize down to 100 7 kPa for an hour using the vacuum pump vacuum drying 2 If the pressure does not reach 100 7 kPa even after depressur izing for at least two hours repeat the va...

Page 21: ...the refrigerant charging operation close the valve of the refrigerant tank immediately The refrigerant charge port of this product have electric expan sion valve The valve will be closed at end of ref...

Page 22: ...cts the main body seal 3 Make sure to tighten the cap securely For the tightening torque refer to the item Tightening Torque 8HP type 10HP type 12HP type 14HP type 16HP type Liquid pipe shutoff valve...

Page 23: ...refrigerant amount in the field and total refrig erant amount of the system to Refrigerant charge label and adhere in the proximity of the refrigerant charge port About Refrigerant charge label refer...

Page 24: ...the remote control ler display shows P9 code After checking push the MODE button BS1 once and the charg ing is complete In case of heating mode 7 Push the TEST button BS4 once within 5 minutes after...

Page 25: ...ve A PA PH The refrigerant tank is empty Close the valve A and replace empty tank to the new tank After changing the tank open the valve A again Beware the fan running The outdoor unit does not stop o...

Page 26: ...tandards may be applicable if local regulations are not available The VRV System like other air conditioning systems uses R410A as refrigerant R410A itself is an entirely safe non toxic non combusti b...

Page 27: ...ntration 4 Dealing with the situations where the result exceeds the maxi mum concentration level Where the installation of a facility results in a concentration in excess of the maximum concentration...

Page 28: ...3P201178 10P EM07A033B 0908 HT 00_CV_3P201178 10P fm Page 5 Wednesday September 2 2009 11 09 AM...

Reviews: