background image

English

10

Outdoor unit multi connection piping kit and

Refrigerant branch kit selection

Pipe size selection

 Refrigerant branch kits can only be used with R410A.

 When multi outdoor system are installed, be sure to use the 

special separately sold Outdoor unit multi connection piping 

kit. (BHFP30A56).

(For how to select the proper kit, follow the table at right.)

How to select the REFNET joint

Piping between outdoor unit (*2) and refrigerant branch kit (part A)

How to select the REFNET header

When using REFNET joint at the first branch counted from the outdoor unit side,

choose from the following table in accordance with the outdoor system capacity 

type. (Example : REFNET joint A)

Choose from the following table in accordance with the outdoor unit system capacity type.

Piping between outdoor unit multi connection piping kit and outdoor unit (part B)

Temper grade and wall thickness for pipes

(Temper grade, O type and 1/2H type indicate the material type specified in JIS H 3300.)

Choose from the following table in accordance with the capacity type of

the outdoor unit connected.

Choose from the following table in accordance with the total capacity index of all

the indoor units connected below the REFNET header.

250 type indoor unit can not be connected below the REFNET header.

How to select the outdoor unit multi connection piping kit

(This is required when the system is multi outdoor unit system.)

Choose from the following table in accordance with the number of outdoor units.

Choose the REFNET joints other than the first branch from the following table in 

accordance with the total capacity index of all the indoor units connected below 

the REFNET joint.

Outdoor system capacity type

10HP type

14~20HP type

Refrigerant branch kit name

KHRP26A33T

KHRP26A72T

Refrigerant branch kit name

KHRP26A22T

KHRP26A33T

KHRP26A72T

Number of outdoor unit

2 units

Connecting piping kit name

BHFP30AP56    

Example for indoor units

connected downstream

Example REFNET joint C : Indoor units  3  +  4  +  5  +  6  +  7  +  8

Example REFNET joint B : Indoor units  7  +  8

Example REFNET header : Indoor units  1  +  2  +  3  +  4  +  5  +  6

Example REFNET header :

Indoor units  1  +  2  +  3  +  4  +  5  +  6  +  7  +  8

The thickness of the pipes in the table shows 

the requirements of Japanease High Pressure 

Gas Controll low. (As of Jan. 2003)

The thickness and material shall be selected in 

accordance with local code.

<In case of single outdoor unit system>

<In case of multi outdoor unit system>

Piping between 

outdoor unit (*2) and

refrigerant branch 

kit (part A)

Piping between outdoor unit and

outdoor unit multi connection 

piping kit (part B)

Piping between outdoor unit and 

refrigerant branch kit (part A)

Outdoor unit

Outdoor unit

Function unit

Function unit

Outdoor system

capacity type

10HP type

14,16HP type

20HP type

Piping size (O. D.)

Piping size (O. D.)

Gas pipe

φ

22.2

φ

28.6

Liquid pipe

φ

9.5

φ

12.7

φ

15.9

Outdoor unit

capacity type

RTSP8 type

RTSP12 type

Copper tube O. D.

Temper grade

Wall thickness

(Min. requirement)

Gas pipe

φ

22.2

φ

28.6

Liquid pipe

φ

9.5

φ

12.7

φ

6.4

0.80

φ

9.5

0.80

φ

12.7

0.80

φ

15.9

0.99

φ

19.1

0.80

φ

22.2

0.80

φ

25.4

0.88

φ

28.6

0.99

φ

31.8

1.10

φ

34.9

1.21

φ

38.1

1.32

φ

41.3

1.43

Piping between refrigerant branch kits

Choose from the following table in accordance with the total capacity type of all the

indoor units connected downstream.

Do not let the connection piping exceed the main refrigerant piping size (Part A).

If the piping size selected from the following table exceeds the piping size of part A, 

decide the piping size in either of the following methods.

(1)

Reduce the size of the connection piping to the piping size of part A.

(2)

Replace the piping of part A with piping that is a size larger (see the table in 

Note 1) so that it will be the same as the size of the connection piping.

Piping between refrigerant branch kit, and indoor unit

Equalizer pipe (part D) (multi outdoor unit system only)

Match to the size of the connection piping on the indoor unit.

Indoor capacity index

x < 150

150 

 x < 200

200 

 x < 290

290 

 x < 420

420 

 x < 640

Gas pipe

φ

15.9

φ

19.1

φ

22.2

φ

28.6

Liquid pipe

φ

9.5

φ

12.7

φ

15.9

Indoor unit capacity type

20 · 25 · 32 · 40 · 50 type

63 · 80 · 100 · 125 type

200 type

250 type

Gas pipe

φ

12.7

φ

15.9

φ

19.1

φ

22.2

Liquid pipe

φ

6.4

φ

9.5

Piping size (O. D.)

φ

19.1

 (unit : mm)

 (unit : mm)

Piping size (O. D.)

 (unit : mm)

Piping size (O. D.)

 (unit : mm)

 (unit : mm)

1/2H type

O type

Indoor unit total capacity index

x < 200

200 

 x < 290

290 

 x < 640

Refrigerant branch kit name

KHRP26M22H or KHRP26A33H

KHRP26M33H

KHRP26M72H

KHRP KHRP26M73HP

Indoor unit total capacity index

x < 200

200 

 x < 290

290 

 x < 640

640 

 x

Equalizer pipe (part C)

01_EN_3P201178-10P.fm  Page 10  Wednesday, September 2, 2009  11:10 AM

Summary of Contents for RTSQ10PY1

Page 1: ...nglish Norsk Svenska Deutsch Fran ais Polski Installation manual VRVIII C System air conditioner Installationsanleitung VRVIII C System Klimaanlage Manuel d installation Conditionneur d air VRVIII C S...

Page 2: ...PY1 RTSYQ16PY1 RTSYQ20PY1 RTSQ8PY1 RTSQ10PY1 RTSQ12PY1 RTSQ14PY1 RTSQ16PY1 BTSQ20PY1 REYQ8PY1 REYQ10PY1 REYQ12PY1 REYQ14PY1 REYQ16PY1 REYQ18PY1 REYQ20PY1 REYQ22PY1 REYQ24PY1 REYQ26PY1 REYQ28PY1 REYQ30...

Page 3: ...0 300 500 10 50 100 10 100 300 300 500 50 200 200 400 200 200 50 100 10 100 500 50 50 100 50 100 1 3 6 6 6 2 7 6 6 6 9 8 9 8 9 8 9 8 3 4 5 4 5 2 unit mm 1 2 5 4 3 figure 7 727 765 300 460 1 1 2 8 8 5...

Page 4: ...re 11 6 3 4 5 2 8 7 9 10 1 2 4 3 2 1 figure 12 1 3 5 11 11 11 11 9 12 12 13 13 7 10 9 10 4 7 3 6 11 11 11 11 11 11 9 9 8 8 10 10 2 figure 15 figure 21 9 7 8 10 2 3 12 13 7 15 17 18 15 16 14 1 11 4 5 6...

Page 5: ...10 9 1 8 5 7 9 6 4 3 2 figure 26 1 3 2 2 1 3 4 5 6 7 1 10 8 9 figure 30 figure 31 2 3 13 7 8 9 10 12 11 16 6 5 4 14 15 1 17 18 19 20 figure 34 figure 29 figure 23 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1...

Page 6: ...leakage electric shocks or fire Install the air conditioner in accordance with the instructions in this installation manual Improper installation may result in water leakage electric shocks or fire Wh...

Page 7: ...quired additional refrig erant must be charged in its liquid state If the system is charged with refrigerant in its gaseous state due to composition change the system will not function normally Limit...

Page 8: ...both units Do not throw away any of the accessories until installation is com plete They are needed for installation work Request the user to keep the explanation documents after the installation work...

Page 9: ...power wiring and transmission wiring in conduits and ground the conduits Refer to figure 3 1 Indoor unit 2 Branch switch overcurrent breaker 3 Remote controller 4 Personal computer or radio 5 Air outl...

Page 10: ...intless phosphor deoxidized copper pipe Size See 6 5 Example of connection to determine the cor rect size Thickness Select a thickness for the refrigerant piping which complies with national and local...

Page 11: ...tract the gas in the pinch piping 4 Step 2 After the gas is extracted melt the blazing mate rial with a burner and remove the pinch pipes 3 Connecting refrigerant piping to outdoor units and function...

Page 12: ...int horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 17 1 Do not install vertically Refer to figure 17 2 Maintain a straight portion of 500 mm...

Page 13: ...Horizontal surface 2 B arrow view Oil remains in the stopping outdoor unit Rising height 200 mm or more 1 Connect straightly 2 Put rising Prohibited pattern Front connection Bottom connection To indoo...

Page 14: ...nd outdoor units Between outdoor unit and function unit Actual pipe length Equivalent length Actual and Equivalent pipe length Difference in height Difference in height Difference in height Difference...

Page 15: ...s the requirements of Japanease High Pressure Gas Controll low As of Jan 2003 The thickness and material shall be selected in accordance with local code In case of single outdoor unit system In case o...

Page 16: ...at 19 1 Total length m of liquid piping size at 12 7 Total length m of liquid piping size at 6 4 0 37 0 18 0 059 0 26 0 12 0 022 FOR THE SYSTEM SYSTEM NAME THE AMOUNT OF REFRIGERANT Example for refri...

Page 17: ...and an malfunction code will be displayed on the indoor remote controller Never remove thermistor sensor or etc when connecting power wiring and transmission wiring If operated with thermistor sensor...

Page 18: ...board Attach with care See the table below for the tightening torque of the transmission wiring terminals All transmission wiring should use sheathed vinyl cord 0 75 1 25 mm2 or cable duplex Transmiss...

Page 19: ...ing in the power wiring and ground wir ing from the left hand side 6 In the case of pulling in the power wiring and ground wir ing from the right hand side 7 Pull in the transmission wiring from the p...

Page 20: ...rogen gas then depressurize down to 100 7 kPa for an hour using the vacuum pump vacuum drying 2 If the pressure does not reach 100 7 kPa even after depressur izing for at least two hours repeat the va...

Page 21: ...the refrigerant charging operation close the valve of the refrigerant tank immediately The refrigerant charge port of this product have electric expan sion valve The valve will be closed at end of ref...

Page 22: ...cts the main body seal 3 Make sure to tighten the cap securely For the tightening torque refer to the item Tightening Torque 8HP type 10HP type 12HP type 14HP type 16HP type Liquid pipe shutoff valve...

Page 23: ...refrigerant amount in the field and total refrig erant amount of the system to Refrigerant charge label and adhere in the proximity of the refrigerant charge port About Refrigerant charge label refer...

Page 24: ...the remote control ler display shows P9 code After checking push the MODE button BS1 once and the charg ing is complete In case of heating mode 7 Push the TEST button BS4 once within 5 minutes after...

Page 25: ...ve A PA PH The refrigerant tank is empty Close the valve A and replace empty tank to the new tank After changing the tank open the valve A again Beware the fan running The outdoor unit does not stop o...

Page 26: ...tandards may be applicable if local regulations are not available The VRV System like other air conditioning systems uses R410A as refrigerant R410A itself is an entirely safe non toxic non combusti b...

Page 27: ...ntration 4 Dealing with the situations where the result exceeds the maxi mum concentration level Where the installation of a facility results in a concentration in excess of the maximum concentration...

Page 28: ...3P201178 10P EM07A033B 0908 HT 00_CV_3P201178 10P fm Page 5 Wednesday September 2 2009 11 09 AM...

Reviews: