ESIE17-08
|
Part 2. Troubleshooting
2.2. Error based troubleshooting
Page 42
15/11/18
|
Version 1.1
R32 Sky-Air RZAG-M
2.2.4. Others
Not applicable.
Possible cause
Check
Corrective action
Faulty wiring between indoor and outdoor
unit.
Check wiring between indoor and outdoor
unit.
Correct wiring.
Refrigerant shortage (incorrect
charge/leakage).
Check for refrigerant shortage.
Perform a leak test.
If required, repair the leak and charge the
correct amount of refrigerant.
Refrigerant circuit is clogged.
Check for possible blockage (Blockages
can be checked by measuring the refriger-
ant/pipe temperature. Sudden drop in
temperature could indicate a blockage.
(Remark: This is not valid for the expan-
sion valve.)).